U-Match Series DC Inverter Service Manual
99
E2 Freeze Protection
Freeze protection is normal protection but not abnormal malfunction. If freeze protection occurs
frequently during operation, please check if the indoor filter is with filth blockage or if the indoor air outlet is
abnormal. The user is required to clean the filter, check the air outlet and air return pipe periodically to
ensure smooth air return and air outlet.
E3 stands for three statuses:
(1) Low pressure protection;
(2) Refrigerant lacking protection;
(3) Refrigerant recycling mode;
1) If enter refrigerant recycling mode through special operation, the displayed E3 is not an error
code. It will be eliminated when exiting refrigerant recycling mode.
2) If you do not want to have refrigerant lacking protection, you can enter the debugging mode
through wired controller and then cancel the refrigerant lacking protection mode.
Содержание GKH18D3FI
Страница 1: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL T1 R410A 60Hz GC201410...
Страница 4: ...U Match Series DC Inverter Service Manual 1 PRODUCT...
Страница 16: ...U Match Series DC Inverter Service Manual 13 CONTROL...
Страница 55: ...U Match Series DC Inverter Service Manual 52 INSTALLATION...
Страница 96: ...U Match Series DC Inverter Service Manual 93 MAINTENANCE...
Страница 112: ...U Match Series DC Inverter Service Manual 109 H6 DC fan error...
Страница 121: ...U Match Series DC Inverter Service Manual 118 Model GUHD24ND3FO Model GUHD30ND3FO...
Страница 122: ...U Match Series DC Inverter Service Manual 119 Model GUHD36ND3FO Model GUHD42ND3FO...
Страница 126: ...U Match Series DC Inverter Service Manual 123 Model GKH48D3FI...
Страница 191: ...U Match Series DC Inverter Service Manual 188 JF00302305...