Super Free Match
Service Manual
INSTALLATION
71
4.1.5
Installation of Mounting Plate
1)
Mounting plate should be installed horizontally. As the water drainage pipe for the indoor unit is
two-way type, during installation, the indoor unit should slightly slant to water tray's outlet for smooth
drainage of condenser water.
2)
Fix the mounting plate on the selected location with screws.
3)
Be sure that the mounting plate has been fixed firmly enough to withstand the weight of an adult of
60kg, furthermore, the weight should be evenly shared by each screw.
4.1.6
Drill piping hole
1)
Slant the piping hole (
Φ
55/
Φ
70) on the wall slightly downward to the outdoor side.
2)
Insert the piping-hole sleeve into the hole to prevent the connection piping and wiring from being
damaged when passing through the hole.
4.1.7
Installation of drain hose
1)
Connect the drain hose to the outlet pipe of the indoor unit. Bind the joint with rubber belt.
Содержание GKH(12)BA-K3DNA1A/I
Страница 1: ...SUPER FREE MATCH SERIES SERVICE MANUAL T1 R410A 50Hz GC201405 CENTRAL AIR CONDITIONERS...
Страница 5: ...Super Free Match Service Manual PRODUCT 1 PRODUCT...
Страница 27: ...Super Free Match Service Manual CONTROL 23 CONTROL...
Страница 28: ...Super Free Match Service Manual CONTROL 24 Control 1 OPERATION FLOWCHART...
Страница 30: ...Super Free Match Service Manual CONTROL 26 1 2 Heating Operation...
Страница 64: ...Super Free Match Service Manual INSTALLATION 60 INSTALLATION...
Страница 111: ...Super Free Match Service Manual INSTALLATION 107 7 Electrical Wiring Work 7 1 Wiring Connection Precept 1 Precept 2...
Страница 122: ...Super Free Match Service Manual MAINTENANCE 118 MAINTENANCE...
Страница 144: ...Super Free Match Service Manual MAINTENANCE 140 4 2 3 BU module FXB3A K...
Страница 145: ...Super Free Match Service Manual MAINTENANCE N 141 FXB5A K...
Страница 193: ...Super Free Match Service Manual MAINTENANCE N 189 7 2 3 Cassette type GKH 12 BA K3DNA2A I GKH 18 BA K3DNA2A I...
Страница 207: ...JF00301896...