Super Free Match
Service Manual
INSTALLATION
111
and transmission line from damaging by the hole, the rubber ring cannot fall from that, otherwise, it
may cause electrical shock or fire etc.
4)
Connect the power cable of the BU module to the L, N terminals with the sign of Power and as well as
the ground screw.
5)
Connect the transmission line of the BU module to the N(1), 2 terminals with the sign of Outdoor /BU
module.
6)
If the power cable need to be connected to the other BU module, please connect the extra line to the L,
N terminals with the sign of BU module Power and as well as the ground screw.
7)
If the transmission line need to be connected to the other BU module, please connect the extra line to the
N(1), 2 terminals with the sign of BU module.
8)
Connect the power cable of the indoor unit to the N(1), 2 and 3 terminals with the sign of Indoor unit A
(B, C, D and E) and as well as the ground screw.
9)
Fix the power cable and transmission line firmly by cable fixing clip.
10)
Screw the electrical equipment plate.
Caution
!
The transmission line and the power cable must be separated and separated with an interval of at least
2cm; otherwise it may be result in communication problem.
Confirm the each cable connected to the terminal screw is exactly and securely after finishing the electric
work.
Fix each ground wire separately with the ground screw.
When connecting indoor units, make sure to connect refrigerant pipes and power cables to the same
connection ports marked with matching signs.
If the connecting wire is connected to the terminal incorrectly, the unit will not work normally.
Содержание GKH(12)BA-K3DNA1A/I
Страница 1: ...SUPER FREE MATCH SERIES SERVICE MANUAL T1 R410A 50Hz GC201405 CENTRAL AIR CONDITIONERS...
Страница 5: ...Super Free Match Service Manual PRODUCT 1 PRODUCT...
Страница 27: ...Super Free Match Service Manual CONTROL 23 CONTROL...
Страница 28: ...Super Free Match Service Manual CONTROL 24 Control 1 OPERATION FLOWCHART...
Страница 30: ...Super Free Match Service Manual CONTROL 26 1 2 Heating Operation...
Страница 64: ...Super Free Match Service Manual INSTALLATION 60 INSTALLATION...
Страница 111: ...Super Free Match Service Manual INSTALLATION 107 7 Electrical Wiring Work 7 1 Wiring Connection Precept 1 Precept 2...
Страница 122: ...Super Free Match Service Manual MAINTENANCE 118 MAINTENANCE...
Страница 144: ...Super Free Match Service Manual MAINTENANCE 140 4 2 3 BU module FXB3A K...
Страница 145: ...Super Free Match Service Manual MAINTENANCE N 141 FXB5A K...
Страница 193: ...Super Free Match Service Manual MAINTENANCE N 189 7 2 3 Cassette type GKH 12 BA K3DNA2A I GKH 18 BA K3DNA2A I...
Страница 207: ...JF00301896...