Super Free Match
Service Manual
CONTROL
49
increased 1
℃
in every hour, after 1
℃
the temperature will be maintained, after 7hours, the temperature
will be decreased 1
℃
, after that the unit will keep on running under this temperature;
④
When setting the initial temperature 30
℃
, under this temperature setting, after 7hours, the temperature
will be decreased 1
℃
, after that the unit will keep on running under this temperature;
In Heat mode
:
①
Under the initial presetting temperature 16
℃
, it will run under this setting temperature all along.
②
Under the initial presetting temperature17
℃~
20
℃
, after Sleep function started up, the temperature will
decrease 1
℃
in every hour, after 1
℃
decreased, this temperature will be maintained.
③
Under the initial presetting temperature 21
℃~
27
℃
, after Sleep function started up, the temperature
will decrease 1
℃
in every hour, after 2
℃
decreased, this temperature will be maintained.
④
Under the initial presetting temperature 28
℃~
30
℃
, after Sleep function started up, the temperature
will decrease 1
℃
in every hour, after 3
℃
decreased, this temperature will be maintained.
Sleep 3- the sleep curve setting under Sleep mode by DIY:
①
Under Sleep 3 mode, press "Turbo" button for a long time, remote control enters into user individuation
sleep setting status, at this time, the time of remote control will display "1hour ",
②
Adjust "+" and "-" button, could change the corresponding setting temperature, after adjusted, press
"Trubo" button for confirmation; the setting temperature "88" will display the corresponding
temperature of last setting sleep curve and blink (The first entering will display according to the initial
curve setting value of original factory);
③
At this time, 1hour will be automatically increased at the timer postion on the remote control, (that are
"2hours " or "3hours " or "8hours "), the place of setting temperature "88"will display the corresponding
temperature of last setting sleep curve and blink;
④
Repeat the above step (2)
~
(3) operation, until 8hours temperature setting finished, sleep, curve
setting finished, at this time, the remote control will resume the original timer display; temperature
display will resume to original setting temperature.
Sleep3- the sleep curve setting under Sleep mode by DIY could be inquired:
The user could accord to sleep curve setting method to inquire the presetting sleep curve, enter into user
individuation sleep setting status, but do not change the temperature, press "Turbo" button directly for
confirmation.
Note:
In the above presetting or enquiry procedure, if continuously within 10s, there is no button pressed, the
sleep curve setting within 10s, there is no button pressed, the sleep curve setting status will be automatically quit
and resume to display the original displaying. In the presetting or enquiry procedure, press "ON/OFF" button,
"Mode" button, "Timer" button or "Sleep" button, the sleep curve setting or enquiry status will quit similarly.
3.4.2 Guide for General Operation
1) After powered on, press ON/OFF and then the unit will start to run.
(
Note:
when powered off, the guide louver of the main unit will close automatically).
2) Press MODE to select the desired running mode.
3) Press
+
or
-
to set the desired temperature (it is unnecessary to set the temperature under the AUTO
mode.)
4) Press FAN to set the fan speed, can select AUTO FAN, LOW, MEDIUM-LOW, MEDIUM,
MEDIUM-HIGH and HIGH.
5) Press
and
to select the swing angle.
3.4.3 Guide for Optional Operation
1)
Press SLEEP button, to set sleep.
2)
Press TIMER ON and TIMER OFF button, can set the scheduled timer on timer off.
Содержание GKH(12)BA-K3DNA1A/I
Страница 1: ...SUPER FREE MATCH SERIES SERVICE MANUAL T1 R410A 50Hz GC201405 CENTRAL AIR CONDITIONERS...
Страница 5: ...Super Free Match Service Manual PRODUCT 1 PRODUCT...
Страница 27: ...Super Free Match Service Manual CONTROL 23 CONTROL...
Страница 28: ...Super Free Match Service Manual CONTROL 24 Control 1 OPERATION FLOWCHART...
Страница 30: ...Super Free Match Service Manual CONTROL 26 1 2 Heating Operation...
Страница 64: ...Super Free Match Service Manual INSTALLATION 60 INSTALLATION...
Страница 111: ...Super Free Match Service Manual INSTALLATION 107 7 Electrical Wiring Work 7 1 Wiring Connection Precept 1 Precept 2...
Страница 122: ...Super Free Match Service Manual MAINTENANCE 118 MAINTENANCE...
Страница 144: ...Super Free Match Service Manual MAINTENANCE 140 4 2 3 BU module FXB3A K...
Страница 145: ...Super Free Match Service Manual MAINTENANCE N 141 FXB5A K...
Страница 193: ...Super Free Match Service Manual MAINTENANCE N 189 7 2 3 Cassette type GKH 12 BA K3DNA2A I GKH 18 BA K3DNA2A I...
Страница 207: ...JF00301896...