MAINTENANCE
122
④
Press “Enter” key: the function section display “Fo” code uninterrupted and the data section flashes the
current parameters.
⑤
Switch with the “
+
” “
-
” to the target value, and then press “Enter” key: the function section display
“Fo” code uninterrupted and the data section flashes the new parameters uninterrupted.
3)
After the unit is running in the “Fo” mode, please turn off the liquid stop valve.
4)
Check the low pressure by operating the testing board. If the low pressure is 0.03Mpa for more than 30
second, please turn off the gas stop valve.
Note:
If the operation of Recover the refrigerant is not complete in ten minutes, it will exit automatic.
Содержание GKH(12)BA-K3DNA1A/I
Страница 1: ...SUPER FREE MATCH SERIES SERVICE MANUAL T1 R410A 50Hz GC201405 CENTRAL AIR CONDITIONERS...
Страница 5: ...Super Free Match Service Manual PRODUCT 1 PRODUCT...
Страница 27: ...Super Free Match Service Manual CONTROL 23 CONTROL...
Страница 28: ...Super Free Match Service Manual CONTROL 24 Control 1 OPERATION FLOWCHART...
Страница 30: ...Super Free Match Service Manual CONTROL 26 1 2 Heating Operation...
Страница 64: ...Super Free Match Service Manual INSTALLATION 60 INSTALLATION...
Страница 111: ...Super Free Match Service Manual INSTALLATION 107 7 Electrical Wiring Work 7 1 Wiring Connection Precept 1 Precept 2...
Страница 122: ...Super Free Match Service Manual MAINTENANCE 118 MAINTENANCE...
Страница 144: ...Super Free Match Service Manual MAINTENANCE 140 4 2 3 BU module FXB3A K...
Страница 145: ...Super Free Match Service Manual MAINTENANCE N 141 FXB5A K...
Страница 193: ...Super Free Match Service Manual MAINTENANCE N 189 7 2 3 Cassette type GKH 12 BA K3DNA2A I GKH 18 BA K3DNA2A I...
Страница 207: ...JF00301896...