Section 3. Installing the Grand Effects
®
Linear Burners
WARNING
Risk of Electrical Shock or Electrocution.
This linear burner
must be installed by a licensed or certified electrician or a qualified pool
serviceman in accordance with the National Electrical Code
®
(Canadian
Electrical Code, in Canada) and all applicable local codes and
ordinances. Improper installation will create an electrical hazard, which
could result in death or serious injury to pool or spa users, installers or
others due to electrical shock, and may also cause damage to property.
Always disconnect the power to the Linear Burner at the circuit breaker
before installing or servicing the bowl. Failure to do so could result in
death or serious injury to serviceman, pool or spa users or others due to
electrical shock.
3.1
Preparing the Linear Burner for Installation
Note:
The electrician must complete preparatory steps before fire pit is
installed.
The National Electrical Code
®
(NEC
®
) allows listed low-voltage gas fired-
luminaires, decorative fireplaces, fire pits, and similar equipment using low
voltage ignitors that do not require grounding, and are supplied by a listed
transformer / power supply with outputs that do not exceed the low-voltage
contact limit (15 V RMS ac, 30 V continuous dc) to be permitted to be
located less than 1.5 m (5 ft) from the inside walls of the pool.
Metallic equipment, including metallic gas piping, shall be bonded in
accordance with the National Electrical Code in the US, and Canadian
Electrical Code in Canada.