Linear Burner Inserts Automated Operation
4. Build structure so that inside dimensions meet requirements as shown
in Tables 1 and 2.
5
.
Do not use fire brick to line the inside of the Linear Fire Pit. Fire brick
will retain heat and may result in overheating of the electronics.
NOTE:
Providing good drainage is critical as shown in Figures 4 and 5.
6. For safety reasons, Propane Systems should not have conventional
drainage, but drainage should occur through ventilation holes that are
located on the sides of the structure.
7. Venting the air gap at the bottom, end walls and structure is required
for safety measures and cooling the electrical components as shown in
Figures 4 and Figure 5.
MULTIPLE VENTS REQUIRED CONSULT GRAND EFFECTS MANUAL
FOR NUMBER AND SIZE
DRAINAGE
DRAINAGE
NOTE: DRAINAGE REQUIRED FOR NATURAL GAS ONLY.
GAS AND ELECTRICAL CONDUIT TO BURNER
Figure 4. Inner Mount Venting - Side View
VENTS
VENTS
VENTS
GAS AND
ELECTRICAL
CONDUITS TO
BURNER
DRAINAGE
REQUIRED FOR
NATURAL GAS ONLY
Figure 5. Outer Mount Venting - Top View
8. Maintain good piping practice by keeping pipe length and elbows to
a minimum to eliminate unnecessary pressure drops. Corrugated flex
gas lines should not be used.