Linear Burner Inserts Automated Operation
Page 15
120 VAC
12 VAC
Control Relay or
Switch by others
Grand Effects
Control Panel
Grand Effects
Sub Panel
Flex Gas Hose by
Grand Effects
Grand Effects
Line Burner
Gas Supply
Source
Propane Adder
Hard Pipe by Others
Flex Gas Hose by
Grand Effects
Pilot Ground Wire
Pilot Spark Wire
Pilot Flex Gas Hose
Pre-piped Manifold by
Grand Effects (optional)
Figure 9. Component Overview for Linear Inserts 6’-10’
3.5.1
INSTALLATION OF SUB-PANEL (INNER MOUNT)
120 VAC
Control Relay or
Switch by others
Grand Effects
®
Control Panel
Gas Supply
Source
12 VAC to Grand Effects Sub Panel
Gas Supply to Sub Panel Outside Burner Cavity
Natural Gas 7 W.C. Inches (5” WC min./9” WC max.
NOTE:
Control Panel can be installed
up to 150 ft away from the burner.
GAS LINE PIPE SIZING
NOTE:
Gas line pipe should be sized based upon distance from the source to the
burner, number of elbows and BTU of burner. Use the reference charts from the
latest version of the NFPA 54 Code book or equivalent sizing charts as your guide.
Figure 10. Piping and Electrical Diagram - Inner Mount - Natural Gas
120 VAC
Control Relay or
Switch by others
Grand Effects
Control Panel
Gas Supply
Source
12 VAC to Grand Effects Sub Panel
Gas Supply to Sub Panel Outside Burner Cavity
LP Gas 11 W.C. Inches (9” WC min./13” WC max.
Grand Effects
Propane Adder
NOTE:
Control Panel can be installed
up to 150 ft away from the burner.
GAS LINE PIPE SIZING
NOTE:
Gas line pipe should be sized based upon distance from the source to the
burner, number of elbows and BTU of burner. Use the reference charts from the
latest version of the NFPA 54 Code book or equivalent sizing charts as your guide.
Figure 11. Piping and Electrical Diagram - Inner Mount - Propane Gas