24
•
RIELLO GAS BURNERS
o
Natural Gas Maximum CO2 is 10%
o
Propane Gas Maximum CO2 is 12%
o
Maximum Air free PPM reading of CO is 200.
o
If any of these readings exceed the values above, adjust the air gate to
increase the air intake to the burner.
•
CARLIN GAS BURNERS
o
Natural Gas Maximum CO2 is 10.4%
o
Propane Gas Maximum CO2 is 11.8%
o
Maximum Air free PPM reading of CO is 50.
o
If any of these readings exceed the values above, adjust the air gate to
increase the air intake to the burner.
AFTER PLACING THE BOILER IN OPERATION, THE IGNITION SYSTEM MUST BE
TESTED.
THE METHOD OF TESTING IS AS FOLLOWS:
•
Place the boiler in operation, by raising the thermostat, and observe a
normal ignition of the burner.
•
Lower the thermostat. This should shut off the burner.
•
Close the manual shut5off gas valve that is upstream of the gas control.
•
Place the boiler in operation again, by raising the thermostat.
•
After a trial for ignition period, the burner control should go in lockout
mode. A light on the red button on the burner ignition control will indicate
this.
•
To restart the boiler, open again the manual gas shut5off valve that you
closed a few steps back, press the red button on the ignition control, the
burner then should retry its ignition. If this sequence is not respected,
consult the burner manual.