16
4.
Place in operation the appliance being inspected. Follow the lighting
instructions. Adjust thermostat operation so appliance will operate
continuously.
5.
Test for spillage at the draft regulator outlet / draft hood opening after 5
minutes of main burner operation. Use the flame of a match or candle, or
smoke from a cigarette, cigar, or pipe.
6.
After it has been determined that each appliance remaining connected to the
common venting system properly vents when tested as outlined above, return
doors, windows exhaust fans, fireplace dampers and any other gas5burning
appliance to their previous condition of use.
7.
Any improper operation of the common venting system should be corrected so
the installation conforms with the National fuel gas code ANSI Z223.1/NFPA 54
and/or the Natural gas and propane installation code CAN/CSA B149.1. When
resizing any portion of the common venting system, the common venting
system should be resized to approach the minimum size as determined by the
appropriate tables in chapter 13 of the National fuel gas code ANSI
Z223.1/NFPA 54 and/or the Natural gas and propane installation code
CAN/CSA B149.1.
For boilers connected to gas vent or chimneys, vent installation must be in
accordance with the “Venting of equipment” section of the National fuel gas code
ANSI Z223.1/NFPA 54 or the “Venting systems and air supply for appliances” section
of the Natural gas and propane installation code CAN/CSA B149.1, or applicable
provisions of the local building codes.
Vent connectors serving appliances vented by natural draft shall not be connected
into any portion of mechanical draft system operating under positive pressure.