Integration
333587B
93
Connection Details
Fieldbus
Connect cables to the fieldbus per fieldbus standards.
PROFINET
The EtherNet interface operates at 100M bit, full duplex,
as required by PROFINET. The EtherNet interface is
auto-polarity sensing and auto-crossover capable.
Network Status (NS)
Module Status (MS)
Link/Activity (Link)
State
Description
Comments
Off
Off-line
•
No power
•
No connection with IO
Controller
Green
On-line,
(RUN)
•
Connection with IO
Controller established
•
IO Controller with RUN
state
Flashing
Green
On-line,
(STOP)
•
Connection with IO
Controller established
•
IO Controller in STOP
state
TI11814A
NS
MS
Link
State
Description
Comments
Off
Not initialized
No power or module in
“SETUP” or “NW_INIT”
state
Green
Normal
operation
Diagnostic event(s)
present
Flashing
Green
Initialized,
diagnostic
event(s)
present
Used by engineering tools
to identify node on
network
Red Exception
error
Module in state
“EXCEPTION”
Red
(1 flash)
Configuration
error
Expected Identification
differs from Real
Identification
Red
(2 flashes)
IP Address not
set
Set IP address via system
monitor or DNS server
Red
(3 flashes)
Station Name
not set
Set Station Name via
system monitor
Red
(4 flashes)
Major Internal
Error
Cycle system power;
replace module
State
Description
Off
No Link, no communication present
Green
Link established, no communication present
Green,
flashing
Link established, communication present