Troubleshooting and Fault Recovery
50
309738L
Fault
Priority
Fault Name
Fault Description
Causes
13
High Flow
Rate
Measured Flow rate
more than desired flow
rate plus tolerance
Operating below the minimum
regulator operating pressure
Increase fluid pressure above reg-
ulator minimum
Regulator worn or not operating
properly
Repair regulator
Flow meter providing false pulses
Replace flow meter sensor
Incorrect flow fault tolerance or
flow fault time
Enter correct tolerance or flow fault
time
14
Computed
Target
The requested volume
differs from the entered
process target by more
than the entered toler-
ance for style requested
Entered process target incorrectly
Enter correct process target
Entered tolerance incorrectly
Enter correct tolerance
Requested volume incorrect
Check automation program
Automation problem
Verify automation is correct