12

NOTE: 

Do 

NOT

 adjust charge based on suction pressure unless there is a gross

undercharge.

4. Disconnect manifold set.  Installation is complete.

TWO

 SPEED APPLICATION (GPH1648 / GPC1560)

Run the unit on low stage cooling for 10 minutes until refrigerant pressures stabi-
lize.  Follow the guidelines and methods below to check unit operation and ensure
that the refrigerant charge is within limits. Charge the unit on low stage.

1. Purge gauge lines. Connect service gauge manifold to access fittings. Run

system at least 10 minutes to allow pressure to stabilize.

2. Temporarily install thermometer on liquid (small) line near liquid line access

fitting with adequate contact and insulate for best possible reading.

3. Check subcooling and superheat. Two stage systems running on low stage

with TXV application should have a subcooling  and superheat within the
range listed on the chart.

a. If subcooling and superheat are low, 

adjust

 TXV  superheat, then check

subcooling.

NOTE:

 To adjust superheat, turn the valve stem clockwise to increase and

counter clockwise to decrease.

b. If subcooling is low and superheat is high, 

add 

charge to raise subcooling

then check superheat.

c. If subcooling and superheat are high, 

adjust

 TXV valve superheat, then

check subcooling.

d. If subcooling is high and superheat is low, 

adjust 

TXV valve superheat and

remove 

charge to lower the subcooling.

NOTE:

 Do 

NOT 

adjust the charge based on suction pressure unless there is

a gross undercharge.

4. Disconnect manifold set, installation is complete.

ELECTRIC HEAT INSTALLATION & ADJUSTMENT

This series of electric cooling and heat pump package
equipment is designed to accept a field installed electric heat
kit. The unit is equipped to easily install the HKR/HKP Series
Electric Heat Kit. Full Installation Instructions are included
in this kit. Please use this document for guidance in field
equipping the package unit with electric heat.
Choose the heat kit that fits the application for the specific
installation. Permanently mark the unit’s nameplate with the
model being installed. High and low voltage connections are
detailed in the heat kit instructions.
Indoor Blower motor speed tap selection may need to be
modified to accommodate normal continuous operation to
prevent a nuisance trip.  

See tables at right.

MAINTENANCE

The Self Contained Package Air Conditioner and Heat Pump
should operate for many years without excessive service calls
if the unit is installed properly. However it is recommended
that the homeowner inspect the unit before a seasonal start
up.  The coils should be free of debris so adequate airflow is
achieved. The return and supply registers should be free of
any obstructions. The filters should be cleaned or replaced.
These few steps will help to keep the product up time to a
maximum.   The Troubleshooting Chart (on page 16) should
help in identifying problems if the unit does not operate
properly.

TABLE  7A & 7B

TABLE  6A & 6B

Model #

Superheat

± 2°F

Subcooling

± 2°F

GPC1524H41 6

 

°

---

GPC1530H41 8°

---

GPC1536H41 12°

---

GPC1542H41 7°

---

GPC1548H41 10°

---

GPC1560H41 12°

12°

GPC15

Design superheat @ 95 °F

outdoor ambient temperature  

Model #

Superheat

± 2°F

Subcooling

± 2°F

GPH1624H41

15°

GPH1630H41

15°

GPH1636H41

10°

13°

GPH1642H41

12°

13°

GPH1648H41

15°

15°

GPH1660H41

12°

12°

GPH16

Design superheat @ 95 °F

outdoor ambient temperature  

5

8

10

15

20

GPC1524/GPH1624H41**

T3

T3

T3

T5

NA

GPC1530/GPH1630H41**

T3

T3

T3

T5

NA

GPC1536/GPH1636H41**

T3

T3

T3

T5

NA

GPC1542/GPH1642H41**

T3

T3

T3

T3

T5

GPC1548/GPH1648H41**

T3

T3

T3

T3

T3

GPC1648/GPH1660H41**

T3

T3

T3

T3

T3

5

8

10

15

20

GPC1524/GPH1624H41**

T5

T5

T5

T5

NA

GPC1530/GPH1630H41**

T5

T5

T5

T5

NA

GPC1536/GPH1636H41**

T5

T5

T5

T5

NA

GPC1542/GPH1642H41**

T5

T5

T5

T5

NA

GPC1548/GPH1648H41**

T5

T5

T5

T5

NA

GPC1560/GPH1660H41**

T5

T5

T5

T5

NA

T4 - High Speed Cooling;  T5 -  High Speed Heating

Unit Model Number

GPC15/GPH16(24-60) Models (0 - 0.5 E.S.P.)

Unit Model Number

Electric Heat KW

T1 - Fan Only;  T2 - Normal Speed Cooling

T3 - Normal Speed Heating

Electric Heat KW

T1 - Fan Only;  T2 - Normal Speed Cooling

T3 - Normal Speed Heating

T4 - High Speed Cooling;  T5 -  High Speed Heating

GPC15/GPH16(24-60) Models (0 - 0.5 E.S.P.)

Содержание GPC15 SEER

Страница 1: ...licable to your model for information regarding accessories NOTE Please contact your distributor or our website for the applicable Specifications Sheets referred to in this manual IMPORTANT This produ...

Страница 2: ...MENT SPECIFIED IN THIS MANUAL WITHOUT PROPER TRAINING MAY RESULT IN PRODUCT DAMAGE PROPERTY DAMAGE PERSONAL INJURY OR DEATH T O THE INSTALLER Carefully read all instructions for the installation prior...

Страница 3: ...Failure to heed safety information increases the risk of serious personal injury or death property damage and or product damage WARNING TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DEATH DO NOT USE THI...

Страница 4: ...EASE CONTACT THE LOCAL OFFICE OF THE EPA National Codes This product is designed and manufactured to permit installation in accordance with National Codes It is the installer s responsibility to insta...

Страница 5: ...k should be fabricated by the installing contractor in accordance with local codes Industry manuals may be used as a guide when sizing and designing the duct system such as NESCA National Environmenta...

Страница 6: ...ded for easy and convenient access to the filters for periodic inspection and cleaning Filters must have adequate face area for the rated quantity of the unit See air delivery tables Figure 4 for reco...

Страница 7: ...unit is located on the electrical box cover If any of the original wire supplied with the appliance must be replaced the wire gauge and insulation must be the same as the original wiring Transformer...

Страница 8: ...day when conditions are more suitable but DO NOT FAIL TO TEST If the out door ambient is low and the unit operates properly on the heating cycle you may check the pressure cutout operation by blockin...

Страница 9: ...used to prevent full electric heater operation at varying outdoor ambient 0 F to 45 F They are normally open above their set points and closed below to permit staging of indoor supplement heater oper...

Страница 10: ...unit s defrost period SUGGESTED FIELD TESTING TROUBLESHOOTING 1 Run unit in the heating mode room thermostat calling for heat 2 Check unit for proper charge Note Bands of frost on the condenser coil i...

Страница 11: ...on Temperature from tables or pressure gauge saturated temperature scale R 410A 2 Read suction line temperature 3 Use the following formula SUPERHEAT SUCTION LINE TEMP SAT SUCTION TEMP EXPANSION VALVE...

Страница 12: ...tion for the specific installation Permanently mark the unit s nameplate with the model being installed High and low voltage connections are detailed in the heat kit instructions Indoor Blower motor s...

Страница 13: ...tubing Poor contact may not terminate the unit s defrost cycle quickly enough to prevent the unit from cutting out on high discharge pressure Malfunctioning Reversing Valve This may be due to 1 Soleno...

Страница 14: ...09 122 134 147 159 172 184 CFM 1123 1068 1014 959 905 850 796 741 Watts 123 136 148 161 173 186 198 211 CFM 1462 1409 1357 1305 1252 1200 1147 1095 Watts 241 253 266 278 291 303 315 328 CFM 1005 961 9...

Страница 15: ...767 1732 1669 1618 Watts 498 521 516 534 385 567 571 574 CFM 1130 1080 1020 968 993 887 826 762 Watts 125 139 150 161 175 186 190 207 CFM 1712 1655 1587 1541 1486 1444 1393 1340 Watts 337 348 358 375...

Страница 16: ...ssor stuck grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still open replace the compressor c Low voltage connection c At compressor terminals voltage...

Страница 17: ...evaporator coil The safest way to clean the evaporator coil is to sim ply flush the coil with water This cleaning practice remains as the recommended cleaning method for both copper tube and aluminum...

Страница 18: ...ance around the unit for safety service maintenance and proper unit operation Verify proper weatherproofing of all ductwork roof curbs and electrical connections Check that the flue screen is in place...

Страница 19: ...t 1 Compressor Amps Circuit 2 Compressor Amps Blower Amps Condenser Fan Amps ELECTRICAL Total External Static Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cool...

Страница 20: ...20 Goodman Manufacturing Company L P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com 2015 2016 Goodman Manufacturing Company L P...

Отзывы: