12
NOTE:
Do
NOT
adjust charge based on suction pressure unless there is a gross
undercharge.
4. Disconnect manifold set. Installation is complete.
TWO
SPEED APPLICATION (GPH1648 / GPC1560)
Run the unit on low stage cooling for 10 minutes until refrigerant pressures stabi-
lize. Follow the guidelines and methods below to check unit operation and ensure
that the refrigerant charge is within limits. Charge the unit on low stage.
1. Purge gauge lines. Connect service gauge manifold to access fittings. Run
system at least 10 minutes to allow pressure to stabilize.
2. Temporarily install thermometer on liquid (small) line near liquid line access
fitting with adequate contact and insulate for best possible reading.
3. Check subcooling and superheat. Two stage systems running on low stage
with TXV application should have a subcooling and superheat within the
range listed on the chart.
a. If subcooling and superheat are low,
adjust
TXV superheat, then check
subcooling.
NOTE:
To adjust superheat, turn the valve stem clockwise to increase and
counter clockwise to decrease.
b. If subcooling is low and superheat is high,
add
charge to raise subcooling
then check superheat.
c. If subcooling and superheat are high,
adjust
TXV valve superheat, then
check subcooling.
d. If subcooling is high and superheat is low,
adjust
TXV valve superheat and
remove
charge to lower the subcooling.
NOTE:
Do
NOT
adjust the charge based on suction pressure unless there is
a gross undercharge.
4. Disconnect manifold set, installation is complete.
ELECTRIC HEAT INSTALLATION & ADJUSTMENT
This series of electric cooling and heat pump package
equipment is designed to accept a field installed electric heat
kit. The unit is equipped to easily install the HKR/HKP Series
Electric Heat Kit. Full Installation Instructions are included
in this kit. Please use this document for guidance in field
equipping the package unit with electric heat.
Choose the heat kit that fits the application for the specific
installation. Permanently mark the unit’s nameplate with the
model being installed. High and low voltage connections are
detailed in the heat kit instructions.
Indoor Blower motor speed tap selection may need to be
modified to accommodate normal continuous operation to
prevent a nuisance trip.
See tables at right.
MAINTENANCE
The Self Contained Package Air Conditioner and Heat Pump
should operate for many years without excessive service calls
if the unit is installed properly. However it is recommended
that the homeowner inspect the unit before a seasonal start
up. The coils should be free of debris so adequate airflow is
achieved. The return and supply registers should be free of
any obstructions. The filters should be cleaned or replaced.
These few steps will help to keep the product up time to a
maximum. The Troubleshooting Chart (on page 16) should
help in identifying problems if the unit does not operate
properly.
TABLE 7A & 7B
TABLE 6A & 6B
Model #
Superheat
± 2°F
Subcooling
± 2°F
GPC1524H41 6
°
---
GPC1530H41 8°
---
GPC1536H41 12°
---
GPC1542H41 7°
---
GPC1548H41 10°
---
GPC1560H41 12°
12°
GPC15
Design superheat @ 95 °F
outdoor ambient temperature
Model #
Superheat
± 2°F
Subcooling
± 2°F
GPH1624H41
15°
7°
GPH1630H41
15°
7°
GPH1636H41
10°
13°
GPH1642H41
12°
13°
GPH1648H41
15°
15°
GPH1660H41
12°
12°
GPH16
Design superheat @ 95 °F
outdoor ambient temperature
5
8
10
15
20
GPC1524/GPH1624H41**
T3
T3
T3
T5
NA
GPC1530/GPH1630H41**
T3
T3
T3
T5
NA
GPC1536/GPH1636H41**
T3
T3
T3
T5
NA
GPC1542/GPH1642H41**
T3
T3
T3
T3
T5
GPC1548/GPH1648H41**
T3
T3
T3
T3
T3
GPC1648/GPH1660H41**
T3
T3
T3
T3
T3
5
8
10
15
20
GPC1524/GPH1624H41**
T5
T5
T5
T5
NA
GPC1530/GPH1630H41**
T5
T5
T5
T5
NA
GPC1536/GPH1636H41**
T5
T5
T5
T5
NA
GPC1542/GPH1642H41**
T5
T5
T5
T5
NA
GPC1548/GPH1648H41**
T5
T5
T5
T5
NA
GPC1560/GPH1660H41**
T5
T5
T5
T5
NA
T4 - High Speed Cooling; T5 - High Speed Heating
Unit Model Number
GPC15/GPH16(24-60) Models (0 - 0.5 E.S.P.)
Unit Model Number
Electric Heat KW
T1 - Fan Only; T2 - Normal Speed Cooling
T3 - Normal Speed Heating
Electric Heat KW
T1 - Fan Only; T2 - Normal Speed Cooling
T3 - Normal Speed Heating
T4 - High Speed Cooling; T5 - High Speed Heating
GPC15/GPH16(24-60) Models (0 - 0.5 E.S.P.)