background image

8

4. Turn the fan switch to the “ON” position. The blower

should operate after a 10 second delay.

5. Turn the fan switch to “Auto” position. The blower should

stop after a 60 second delay.

6. Slowly lower the cooling temperature until the unit starts.

The compressor, blower and fan should now be operating.
Allow the unit to run 10 minutes, make sure cool air is
being supplied by the unit.

7. Turn the temperature setting to the highest

position, stopping the unit. The indoor
blower will continue to run for 60 seconds.

8. Turn the thermostat system switch to “OFF”

and disconnect all power when servicing the
unit.

Heat Pump Start-Up Procedure

9. Check the cooling mode for the heat pump

in the same manner as above. The reversing
valve is energized when the thermostat is
placed in the cooling position. A clicking sound
should be noticeable from the reversing
valve.  By lowering the temperature setting
to call for cooling, the contractor is
energized.  The compressor, blower and fan
should then be running.  After the cooling
mode is checked out, turn the thermostat
system switch to “OFF

”.

10. Turn the thermostat system switch to “HEAT”

and fan switch to “AUTO

”.

11. Slowly raise the heating temperature setting.

When the heating first stage makes contact,

stop raising the temperature setting.. The

compressor, blower and fan should now be

running with the reversing valve in the de-

energized (heating) position. After giving the

unit time to settle out, make sure the unit

is supplying heated air.

12. If the out door ambient is above 80°F, the

unit may trip on its high pressure cut out

when on heating. The compressor should

stop.  The heating cycle must be thoroughly

checked, so postpone the test to another day

when conditions are more suitable but-DO

NOT FAIL TO TEST.
If the out door ambient is low and the unit

operates properly on the heating cycle, you

may check the pressure cutout operation by

blocking off the indoor return air until the

unit trips.

13. If unit operates properly in the heating cycle,

raise the temperature setting until the heating second stage makes contact. Supplemental resistance heat, if installed

should now come on. Make sure it operates properly.

NOTE:  If outdoor thermostats are installed the outdoor ambient must be below the set point of these thermostats

for the heaters to operate. It may be necessary to jumper these thermostats to check heater operation if

outdoor ambient is mild.

14.  For thermostats with emergency heat switch, return to step 11. The emergency heat switch is located at the bottom

of the thermostat. Move the switch to emergency heat. The heat pump will stop, the blower will continue to run, all

heaters will come on and the thermostat emergency heat light will come on.

15. If checking the unit in the wintertime, when the outdoor coil is cold enough to actuate the defrost control, observe at

least one defrost cycle to make sure the unit defrosts completely.

WARNING

HIGH

 

VOLTAGE

!

D

ISCONNECT 

ALL

 POWER BEFORE SERVICING OR INSTALLING

THIS UNIT. 

M

ULTIPLE POWER SOURCES MAY BE PRESENT. FAILU

TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY O

DEATH.

RE

R

E

V

A

P

O

R

A

T

O

R

CO OLING

SER VIC E VALVE

SERV IC E PO RT

R EVERSING  V AL VE

C

O

N

D

E

N

S

E

R

SER VIC E POR T

CO MPR ESS OR

SERV IC E POR T

AC C UM U LATO R

EX PA NSION  DEVIC E

CH ECK  VALVE 

OR IF IC E

SE RVIC E

VA LV E

C H EC K  VAL VE  

OR IF ICE

INDO OR

CO IL

D IST RIBU TOR

OU TDO OR

COIL

E

V

A

P

O

R

A

T

O

R

HEATING

SERV IC E VALVE

SE RV IC E PO RT

RE VE RSING  V ALVE

C

O

N

D

E

N

S

E

R

CO MPR ESSOR

SERV IC E POR T

AC C UM UL ATO R

CH ECK  VALVE 

OR IF ICE

SER VIC E

VALVE

CH ECK  VALVE 

OR IFIC E

IN DO OR

CO IL

DISTR IBU TOR

OU TD OOR

C OIL

D IST RIBU TOR

HEAT PUMP REFRIGERANT CIRCUIt - FIGURE 7

Содержание GPC15 SEER

Страница 1: ...licable to your model for information regarding accessories NOTE Please contact your distributor or our website for the applicable Specifications Sheets referred to in this manual IMPORTANT This produ...

Страница 2: ...MENT SPECIFIED IN THIS MANUAL WITHOUT PROPER TRAINING MAY RESULT IN PRODUCT DAMAGE PROPERTY DAMAGE PERSONAL INJURY OR DEATH T O THE INSTALLER Carefully read all instructions for the installation prior...

Страница 3: ...Failure to heed safety information increases the risk of serious personal injury or death property damage and or product damage WARNING TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DEATH DO NOT USE THI...

Страница 4: ...EASE CONTACT THE LOCAL OFFICE OF THE EPA National Codes This product is designed and manufactured to permit installation in accordance with National Codes It is the installer s responsibility to insta...

Страница 5: ...k should be fabricated by the installing contractor in accordance with local codes Industry manuals may be used as a guide when sizing and designing the duct system such as NESCA National Environmenta...

Страница 6: ...ded for easy and convenient access to the filters for periodic inspection and cleaning Filters must have adequate face area for the rated quantity of the unit See air delivery tables Figure 4 for reco...

Страница 7: ...unit is located on the electrical box cover If any of the original wire supplied with the appliance must be replaced the wire gauge and insulation must be the same as the original wiring Transformer...

Страница 8: ...day when conditions are more suitable but DO NOT FAIL TO TEST If the out door ambient is low and the unit operates properly on the heating cycle you may check the pressure cutout operation by blockin...

Страница 9: ...used to prevent full electric heater operation at varying outdoor ambient 0 F to 45 F They are normally open above their set points and closed below to permit staging of indoor supplement heater oper...

Страница 10: ...unit s defrost period SUGGESTED FIELD TESTING TROUBLESHOOTING 1 Run unit in the heating mode room thermostat calling for heat 2 Check unit for proper charge Note Bands of frost on the condenser coil i...

Страница 11: ...on Temperature from tables or pressure gauge saturated temperature scale R 410A 2 Read suction line temperature 3 Use the following formula SUPERHEAT SUCTION LINE TEMP SAT SUCTION TEMP EXPANSION VALVE...

Страница 12: ...tion for the specific installation Permanently mark the unit s nameplate with the model being installed High and low voltage connections are detailed in the heat kit instructions Indoor Blower motor s...

Страница 13: ...tubing Poor contact may not terminate the unit s defrost cycle quickly enough to prevent the unit from cutting out on high discharge pressure Malfunctioning Reversing Valve This may be due to 1 Soleno...

Страница 14: ...09 122 134 147 159 172 184 CFM 1123 1068 1014 959 905 850 796 741 Watts 123 136 148 161 173 186 198 211 CFM 1462 1409 1357 1305 1252 1200 1147 1095 Watts 241 253 266 278 291 303 315 328 CFM 1005 961 9...

Страница 15: ...767 1732 1669 1618 Watts 498 521 516 534 385 567 571 574 CFM 1130 1080 1020 968 993 887 826 762 Watts 125 139 150 161 175 186 190 207 CFM 1712 1655 1587 1541 1486 1444 1393 1340 Watts 337 348 358 375...

Страница 16: ...ssor stuck grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still open replace the compressor c Low voltage connection c At compressor terminals voltage...

Страница 17: ...evaporator coil The safest way to clean the evaporator coil is to sim ply flush the coil with water This cleaning practice remains as the recommended cleaning method for both copper tube and aluminum...

Страница 18: ...ance around the unit for safety service maintenance and proper unit operation Verify proper weatherproofing of all ductwork roof curbs and electrical connections Check that the flue screen is in place...

Страница 19: ...t 1 Compressor Amps Circuit 2 Compressor Amps Blower Amps Condenser Fan Amps ELECTRICAL Total External Static Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cool...

Страница 20: ...20 Goodman Manufacturing Company L P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com 2015 2016 Goodman Manufacturing Company L P...

Отзывы: