background image

16

TROUBLESHOOTING CHART

WARNING

HIGH VOLTAGE!
D

ISCONNECT

 ALL 

POWER

 

BEFORE

 

SERVICING

 

OR

 

INSTALLING

 

THIS

 

UNIT

.  M

ULTIPLE

 

POWER

SOURCES

 

MAY

 

BE

 

PRESENT

. F

AILURE

 

TO

 

DO

 

SO

 

MAY

 

CAUSE

 

PROPERTY

 

DAMAGE

PERSONAL

INJURY

 

OR

 

DEATH

.

SYMPTOM

High head - low suction

a. Restriction in liquid line or flowrator a. Remove or replace with proper size flowrator.

High head - high or normal suction a. Dirty condenser coil

a. Clean coil

b. Overcharged

b. Correct System charge

c. Condenser fan not running

c. Repair or Replace

a.  Incorrect flowrator

a. Replace with correct flowrator

b. Defective compressor valves

b. Replace compressor

c. Flowrator not seating properly

c. Check for debris under flowrator or deformed 

flowrator. Remove debris or replace flowrator.

a. Power off or loose electrical 

connection

a. Check for unit voltage at contactor in unit

b. Thermostat out of calibration set too  b. Reset
c. Defective contactor

c. Check for 24 volts at contactor coil replace if 

contacts are open

d. Blown fuses or tripped breaker

d. Replace fuse or reset breaker Check wiring - 

replace transformer

e. Transformer defective

f. High or low pressure control open 

(Optional)

f. Reset high pressure control or check unit charge

High pressure control opens at 610 psig
Low pressure control opens at 22 psig

g. Compressor overload contacts open

g. Replace compressor

NOTE: Wait at least 2 hours for overload to
reset

Condenser fan runs,
compressor doesn't

a. Loose connection

a. Check for unit voltage at compressor check & 

tighten all connections

b. Compressor stuck, grounded or open 

winding

 

open internal overload

b. Wait at least 2 hours for overload to reset 

If still open, replace the compressor.

c. Low voltage connection

c. At compressor terminals, voltage must be within 

10 % of nameplate volts when unit is operating

d. Capacitor weak, open, or shorted

d.  Check capacitor. If defective, replace.

Low suction - cool compressor

a.

a.

Iced evaporator coil

a. Defective overload protector

a. Replace - check for correct voltage

b. Unit cycling on low pressure control b. Check refrigerant charge and / or airflow
c. High pressure switch cuts out

c. Check airflow (Indoor & outdoor)

a.

a. Increase speed of blower or reduce restriction 

replace air filters

a. Excessive load

a. Recheck load calculation

b. Defective compressor

b. Replace

c. Reversing valve not seating properly. c. Replace
a. Improperly sized unit

a. Recalculate load

b. Improper airflow

b. Check - should be approximately 400 CFM per ton

c. Incorrect refrigerant charge.

c. Charge per procedure attached to unit service 

panel

d. Incorrect voltage 

d. At compressor terminals, voltage must be within 

10% of nameplate volts when unit is
operating

Evaporator coil freezing or frosting a. Low airflow

a. Check - should be approximately 400 CFM per ton, 

dirty air filters, all duct outlets open

b. Low refrigerant charge

b. Properly charge unit

c. Operating unit in cooling mode below 

65°F outdoor temperature

c. Install or check low ambient control, should be 

open below 65°F outdoor temperature

Compressor short cycles

Registers sweat

Low airflow

High suction pressure

Insufficient cooling

POSSIBLE CAUSE

REMEDY

Low head - high suction

Unit will not run

Low indoor airflow

Increase speed of blower or reduce restriction - 
replace air filters

Содержание GPC15 SEER

Страница 1: ...licable to your model for information regarding accessories NOTE Please contact your distributor or our website for the applicable Specifications Sheets referred to in this manual IMPORTANT This produ...

Страница 2: ...MENT SPECIFIED IN THIS MANUAL WITHOUT PROPER TRAINING MAY RESULT IN PRODUCT DAMAGE PROPERTY DAMAGE PERSONAL INJURY OR DEATH T O THE INSTALLER Carefully read all instructions for the installation prior...

Страница 3: ...Failure to heed safety information increases the risk of serious personal injury or death property damage and or product damage WARNING TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DEATH DO NOT USE THI...

Страница 4: ...EASE CONTACT THE LOCAL OFFICE OF THE EPA National Codes This product is designed and manufactured to permit installation in accordance with National Codes It is the installer s responsibility to insta...

Страница 5: ...k should be fabricated by the installing contractor in accordance with local codes Industry manuals may be used as a guide when sizing and designing the duct system such as NESCA National Environmenta...

Страница 6: ...ded for easy and convenient access to the filters for periodic inspection and cleaning Filters must have adequate face area for the rated quantity of the unit See air delivery tables Figure 4 for reco...

Страница 7: ...unit is located on the electrical box cover If any of the original wire supplied with the appliance must be replaced the wire gauge and insulation must be the same as the original wiring Transformer...

Страница 8: ...day when conditions are more suitable but DO NOT FAIL TO TEST If the out door ambient is low and the unit operates properly on the heating cycle you may check the pressure cutout operation by blockin...

Страница 9: ...used to prevent full electric heater operation at varying outdoor ambient 0 F to 45 F They are normally open above their set points and closed below to permit staging of indoor supplement heater oper...

Страница 10: ...unit s defrost period SUGGESTED FIELD TESTING TROUBLESHOOTING 1 Run unit in the heating mode room thermostat calling for heat 2 Check unit for proper charge Note Bands of frost on the condenser coil i...

Страница 11: ...on Temperature from tables or pressure gauge saturated temperature scale R 410A 2 Read suction line temperature 3 Use the following formula SUPERHEAT SUCTION LINE TEMP SAT SUCTION TEMP EXPANSION VALVE...

Страница 12: ...tion for the specific installation Permanently mark the unit s nameplate with the model being installed High and low voltage connections are detailed in the heat kit instructions Indoor Blower motor s...

Страница 13: ...tubing Poor contact may not terminate the unit s defrost cycle quickly enough to prevent the unit from cutting out on high discharge pressure Malfunctioning Reversing Valve This may be due to 1 Soleno...

Страница 14: ...09 122 134 147 159 172 184 CFM 1123 1068 1014 959 905 850 796 741 Watts 123 136 148 161 173 186 198 211 CFM 1462 1409 1357 1305 1252 1200 1147 1095 Watts 241 253 266 278 291 303 315 328 CFM 1005 961 9...

Страница 15: ...767 1732 1669 1618 Watts 498 521 516 534 385 567 571 574 CFM 1130 1080 1020 968 993 887 826 762 Watts 125 139 150 161 175 186 190 207 CFM 1712 1655 1587 1541 1486 1444 1393 1340 Watts 337 348 358 375...

Страница 16: ...ssor stuck grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still open replace the compressor c Low voltage connection c At compressor terminals voltage...

Страница 17: ...evaporator coil The safest way to clean the evaporator coil is to sim ply flush the coil with water This cleaning practice remains as the recommended cleaning method for both copper tube and aluminum...

Страница 18: ...ance around the unit for safety service maintenance and proper unit operation Verify proper weatherproofing of all ductwork roof curbs and electrical connections Check that the flue screen is in place...

Страница 19: ...t 1 Compressor Amps Circuit 2 Compressor Amps Blower Amps Condenser Fan Amps ELECTRICAL Total External Static Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cool...

Страница 20: ...20 Goodman Manufacturing Company L P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com 2015 2016 Goodman Manufacturing Company L P...

Отзывы: