background image

11

ADJUSTING SPEED TAP FOR INDOOR BLOWER MOTOR

EEM Motor

The blower motor speed for the EEM motor is controlled by three 24V low voltage leads: green, yellow, and white.  The
green lead sets the speed for fan-only mode. The yellow lead sets the speed for cooling and heat pump heating mode (if
applicable).  The white lead sets the speed for electric heat mode (emergency heat and second stage heat, if applicable).
The leads are factory connected as follows: Green to T1, Yellow to T2, and White to T3. T1 is the low speed setting and
is dedicated to fan-only mode.  T2 is medium speed cooling and T3 is medium speed heating. T4 is high speed cooling
and T5 is high speed heating.  To adjust the blower speed, move the yellow and/or white wires to T4 and T5.

NOTE:

 If more than one lead is energized at the same time,

the motor will use the higher speed setting.

NOTE: 

 GPC15 and GPH16 units are rated for a maximum

E.S.P. of 0.8 except when using a 20kw electric heater. (The
maximum static for 20 kW electric heat is 0.5 E.S.P.)  When
these units are installed in the 0.5 - 0.8 E.S.P. range, the
white lead (electric heat) must be moved to T5 for proper
operation of the electric heaters.

See CFM vs ESP tables in this manual.

 

Refrigerant Charge Check (Units with Fixed Orifice Devices)

After completing airflow measurements and adjustments the
unit’s refrigerant charge must be checked.  All package units
with fixed orifice devices are charged using the super heat
method at the compressor suction line.  After superheat is
adjusted it is recommended to check unit sub-cooling at the
condenser coil liquid line out. For charge adjustments, see
superheat and subcooling charts shown for each model.

  

 

SUPERHEAT CAN BE DETERMINED AS FOLLOWS:

1. Read suction pressure.  Determine Saturated Suction

Temperature from tables or pressure gauge saturated
temperature scale (R-410A).

2. Read suction line temperature.
3. Use the following formula:

SUPERHEAT = SUCTION LINE TEMP - SAT. SUCTION TEMP.

EXPANSION VALVE (TXV) SYSTEM

SINGLE SPEED APPLICATION
(GPH1624-42)

1. Purge gauge lines. Connect service gauge manifold to

access fittings. Run system at least 10 minutes to allow
pressure to stabilize.

2. Temporarily install thermometer on liquid (small) line near

liquid line access fitting with adequate contact and insulate
for best possible reading.

3. Check subcooling and superheat. Systems with TXV

application should have a subcooling and superheat within
the range listed on the chart.

a. If subcooling and superheat are low, 

adjust

 TXV  then

check subcooling.

b. If subcooling is low and superheat is high, 

add 

charge

to raise subcooling then check superheat.

c. If subcooling and superheat are high, 

adjust

 TXV valve then check subcooling.

d. If subcooling is high and superheat is low, 

adjust 

TXV valve superheat and 

remove 

charge to lower the subcooling.

The TXV should 

NOT

 be adjusted at light load conditions 55º to 60ºF, under such conditions only the subcooling can be

evaluated. This is because suction pressure is dependent on indoor air flow, and wet bulb temperature.

SUCTION

PRESSURE

SATURATED

SUCTION 

TEMPERATURE

ºF

LIQUID

PRESSURE

SATURATED

LIQUID 

TEMPERATURE

ºF

PSIG  

R-410A  

PSIG  

R-410A  

50

1

200

70

52

3

210

73

54

4

220

76

56

6

225

78

58

7

235

80

60

8

245

83

62

10

255

85

64

11

265

88

66

13

275

90

68

14

285

92

70

15

295

95

72

16

305

97

74

17

325

101

76

19

355

108

78

20

375

112

80

21

405

118

85

24

415

119

90

26

425

121

95

29

435

123

100

31

445

125

110

36

475

130

120

41

500

134

130

45

525

138

140

49

550

142

150

53

575

145

160

56

600

149

170

60

625

152

SATURATED

SUCTION PRESSURE

 TEM PERATURE CHART

SATURATED

LIQUID PRESSURE

 TEM PERATURE CHART

TABLE  5

Suction Pressure

Liquid Pressure

Temperature (R-410A)

Temperature (R-410A)

 

SUBCOOLING = SAT. LINE TEMP - LIQUID LINE TEMP.

Содержание GPC15 SEER

Страница 1: ...licable to your model for information regarding accessories NOTE Please contact your distributor or our website for the applicable Specifications Sheets referred to in this manual IMPORTANT This produ...

Страница 2: ...MENT SPECIFIED IN THIS MANUAL WITHOUT PROPER TRAINING MAY RESULT IN PRODUCT DAMAGE PROPERTY DAMAGE PERSONAL INJURY OR DEATH T O THE INSTALLER Carefully read all instructions for the installation prior...

Страница 3: ...Failure to heed safety information increases the risk of serious personal injury or death property damage and or product damage WARNING TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DEATH DO NOT USE THI...

Страница 4: ...EASE CONTACT THE LOCAL OFFICE OF THE EPA National Codes This product is designed and manufactured to permit installation in accordance with National Codes It is the installer s responsibility to insta...

Страница 5: ...k should be fabricated by the installing contractor in accordance with local codes Industry manuals may be used as a guide when sizing and designing the duct system such as NESCA National Environmenta...

Страница 6: ...ded for easy and convenient access to the filters for periodic inspection and cleaning Filters must have adequate face area for the rated quantity of the unit See air delivery tables Figure 4 for reco...

Страница 7: ...unit is located on the electrical box cover If any of the original wire supplied with the appliance must be replaced the wire gauge and insulation must be the same as the original wiring Transformer...

Страница 8: ...day when conditions are more suitable but DO NOT FAIL TO TEST If the out door ambient is low and the unit operates properly on the heating cycle you may check the pressure cutout operation by blockin...

Страница 9: ...used to prevent full electric heater operation at varying outdoor ambient 0 F to 45 F They are normally open above their set points and closed below to permit staging of indoor supplement heater oper...

Страница 10: ...unit s defrost period SUGGESTED FIELD TESTING TROUBLESHOOTING 1 Run unit in the heating mode room thermostat calling for heat 2 Check unit for proper charge Note Bands of frost on the condenser coil i...

Страница 11: ...on Temperature from tables or pressure gauge saturated temperature scale R 410A 2 Read suction line temperature 3 Use the following formula SUPERHEAT SUCTION LINE TEMP SAT SUCTION TEMP EXPANSION VALVE...

Страница 12: ...tion for the specific installation Permanently mark the unit s nameplate with the model being installed High and low voltage connections are detailed in the heat kit instructions Indoor Blower motor s...

Страница 13: ...tubing Poor contact may not terminate the unit s defrost cycle quickly enough to prevent the unit from cutting out on high discharge pressure Malfunctioning Reversing Valve This may be due to 1 Soleno...

Страница 14: ...09 122 134 147 159 172 184 CFM 1123 1068 1014 959 905 850 796 741 Watts 123 136 148 161 173 186 198 211 CFM 1462 1409 1357 1305 1252 1200 1147 1095 Watts 241 253 266 278 291 303 315 328 CFM 1005 961 9...

Страница 15: ...767 1732 1669 1618 Watts 498 521 516 534 385 567 571 574 CFM 1130 1080 1020 968 993 887 826 762 Watts 125 139 150 161 175 186 190 207 CFM 1712 1655 1587 1541 1486 1444 1393 1340 Watts 337 348 358 375...

Страница 16: ...ssor stuck grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still open replace the compressor c Low voltage connection c At compressor terminals voltage...

Страница 17: ...evaporator coil The safest way to clean the evaporator coil is to sim ply flush the coil with water This cleaning practice remains as the recommended cleaning method for both copper tube and aluminum...

Страница 18: ...ance around the unit for safety service maintenance and proper unit operation Verify proper weatherproofing of all ductwork roof curbs and electrical connections Check that the flue screen is in place...

Страница 19: ...t 1 Compressor Amps Circuit 2 Compressor Amps Blower Amps Condenser Fan Amps ELECTRICAL Total External Static Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cool...

Страница 20: ...20 Goodman Manufacturing Company L P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com 2015 2016 Goodman Manufacturing Company L P...

Отзывы: