background image

24

G

AS

 S

UPPLY

 P

RESSURE

 M

EASUREMENT

CAUTION

T

O PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE INLET

GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE

WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING.

W

HITE

-R

ODGERS

 36G54 G

AS

 V

ALVE

The line pressure supplied to the gas valve must be within the
range specified below.  The supply pressure can be measured at
the gas valve inlet pressure boss or at a hose fitting installed in the
gas piping drip leg.  The supply pressure must be measured with
the burners operating.  To measure the gas supply pressure, use
the following procedure.

On/Off Switch

Inlet

Pressure Boss

High Fire

Coil Terminal (HI)

Low Fire

Regulator Adjust

Manometer

Manometer

Hose

A

High Fire Regulator

Adjust

Regulator

Vent

Common

Terminal (C)

Coaxial Coil

Terminal (M)

Outlet

Pressure Boss

Open to

Atmosphere

White-Rodgers Model 36G54 Connected to Manometer

1. Turn OFF gas to furnace at the manual gas shutoff valve

external to the furnace.

2. Connect a calibrated water manometer (or appropriate gas

pressure gauge) at either the gas valve inlet pressure boss
or the gas piping drip leg.

Gas Line

Gas
Shutoff
Valve

Gas Line 
To Furnace

Drip Leg Cap 
With Fitting

Manometer Hose

Manometer

Open To
Atmosphere

Measuring Inlet Gas Pressure (Alt. Method)

NOTE:

 If measuring gas pressure at the drip leg, a field supplied

hose barb fitting must be installed prior to making the hose
connection. If using the inlet pressure boss on the gas valve,
then use the 36G Valve Pressure Check Kit, Goodman Part No.
0151K00000S.

3. Turn ON the gas supply and operate the furnace and all

other gas consuming appliances on the same gas supply
line.

4. Measure furnace gas supply pressure with burners firing.

Supply pressure must be within the range specified in the

Inlet Gas Supply Pressure

 table.

Natural Gas

Minimum: 5.0" w.c.

Maximum:10.0" w.c.

Propane Gas Minimum: 11.0" w.c.

Maximum:13.0" w.c.

Inlet Gas Supply Pressure

If supply pressure differs from table, make the necessary
adjustments to pressure regulator, gas piping size, etc., and/or
consult with local gas utility.

5. Turn OFF gas to furnace at the manual shutoff valve and

disconnect manometer.  Reinstall plug before turning on gas
to furnace.

6. Turn OFF any unnecessary gas appliances stated in step

3.

G

AS

 M

ANIFOLD

 P

RESSURE

 M

EASUREMENT

 

AND

 A

DJUSTMENT

CAUTION

T

O PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE GAS

MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE. 

O

NLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING THE GAS VALVE

PRESSURE REGULATOR.

Only small variations in gas pressure should be made by adjusting
the gas valve pressure regulator.  The manifold pressure must be
measured with the burners operating.  To measure and adjust the
manifold pressure, use the following procedure.

1. Turn OFF gas to furnace at the manual gas shutoff valve

external to the furnace.

2. Turn off all electrical power to the system.
3. Back outlet pressure test screw (inlet/outlet pressure boss)

out one turn (counterclockwise, not more than one turn).

4. Attach a hose and manometer to the outlet pressure boss

of the valve.

5. Turn ON the gas supply.
6. Turn on power and energize main (M) solenoid. Do not

energize the HI solenoid.

7. Measure gas manifold pressure with burners firing.  Adjust

manifold pressure using the 

Manifold Gas Pressure

 table

shown below.

8. Remove regulator cover screw from the low (LO) outlet

pressure regulator adjust tower and turn screw clockwise to
increase pressure, or counterclockwise to decrease
pressure.

9. Energize main (M) solenoid as well as the HI terminal.
10. Remove regulator cover screw from the HI outlet pressure

regulator adjust tower and turn screw clockwise to increase
pressure, or counterclockwise to decrease pressure.

11. Turn off all electrical power and gas supply to the system.
12. Remove manometer hose from outlet pressure boss.
13. Turn outlet pressure test screw in to seal pressure port

(clockwise, 7 in-lb minimum).

14. Turn on electrical power and gas supply to the system.

Содержание GMV8

Страница 1: ...han when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of co...

Страница 2: ...HECK 3 CHIMNEY CROWN CONDITION 13 CHECK 4 DEBRIS IN CLEANOUT 13 CHECK 5 LINER CONDITION 13 CHECK 6 DILUTION AIR 13 CHECK 7 COMPLETE THE INSTALLATION 13 FIX 1 LINER TERMINATION 14 FIX 2 CHANGE VENTING...

Страница 3: ...MPERATURE RISE 25 CIRCULATOR BLOWER SPEED ADJUSTMENT 25 ADJUST BLOWER HEAT OFF DELAY 27 CIRCULATOR BLOWER FAN TIMING ADJUSTMENT 27 XIII OPERATIONAL CHECKS 27 BURNER FLAME 27 AUXILIARY LIMIT CONTROL 27...

Страница 4: ...ponent failures could result in heating system operational problems TO THE INSTALLER Before installing this unit please read this manual thoroughly to familiarize yourself with specific items which mu...

Страница 5: ...stalling the control on a furnace Return any old or new controls to their containers before touching any ungrounded object III PRODUCT APPLICATION This furnace is primarily designed for residential ho...

Страница 6: ...ents and glues antistatic fabric softeners for clothes dryers and masonry acid washing materials WARNING POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE EXPLOSION SMOKE SOOT CONDENSTAION...

Страница 7: ...ATOR BLOWER REMOVAL 3 8 DIAMETER THREADED ROD 6 PLACES PROVIDE 8 MINMUM CLEARANCE BETWEEN CENTER ROD AND FURNACE CABINET TO ALLOW FOR CIRCULATOR BLOWER REMOVAL ASSURE FURNACE IS LEVEL FROM END TO END...

Страница 8: ...an 50 cubic feet per 1 000 BTU per hour of the aggregate input rating of all appliances installed in that space Rooms communicating directly with the space in which the appliances are installed throug...

Страница 9: ...sure Inlet Air Ventilation louvers for unheated crawl space Alternate air inlet Ventilation louvers each end of attic Equipment Located in Confined Spaces All Air from Outdoors Inlet Air from Ventilat...

Страница 10: ...eration of installed gas utilization equipment VI CATEGORY I VENTING VERTICAL VENTING WARNING TO PREVENT POSSIBLE PERSONAL INJURY OR DEATH DUE TO ASPHYXIATION THIS FURNACE MUST BE CATEGORY I VENTED DO...

Страница 11: ...ng In most situations the existing masonry chimneys will require a properly sized metallic liner WARNING POSSIBILITY OF PROPERTY DAMAGE PERSONAL INJURY OR DEATH DAMAGING CONDENSATION CAN OCCUR INSIDE...

Страница 12: ...condition Check 5 Yes Yes No Reline Fix 4 Dilution air available Check 6 Complete the installation Check 7 CHECK 1 PROPER CHIMNEY TERMINATION A masonry chimney used as a vent for gas fired equipment...

Страница 13: ...seal Use caution when doing this as the cut edges of flexible liners may be sharp The surfaces of the liner must be physically sound If gaps or holes are present the metal liner must be removed and r...

Страница 14: ...F ELECTRICAL SHOCK WIRING TO THE UNIT MUST BE POLARIZED AND GROUNDED FIX 1 LINER TERMINATION Any cap or roof assembly used with a liner must be approved by the liner manufacturer for such use The line...

Страница 15: ...SK OF INJURY ELECTRICAL SHOCK OR DEATH THE FURNACE MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR IN THEIR ABSENCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC CODE WARNING EDGES...

Страница 16: ...m located on the blower compartment door for further details of 115 Volt and 24 Volt wiring SINGLE STAGE THERMOSTAT APPLICATION W G Y Single Stage Heating with Single Stage Cooling R B C G R W1 W2 O Y...

Страница 17: ...G R W1 W2 CR35 R122 R128 W3 DS7 R191 R85 DS3 R84 R22 DS4 DS5 TP1 TP2 DEHUMIDIFICATION LED YELLOW DEHUMIDIFICATION JUMPER WIRE CUT TO ENABLE W 14 FOSSIL FUEL APPLICATIONS This furnace can be used in co...

Страница 18: ...cause poor combustion and equipment failure When this furnace is installed at high altitude the appropriate High Altitude orifice kit must be applied The furnace is supplied with orifices sized for na...

Страница 19: ...ranges and pressure switch kits High Low 70 90 115 7 500 0 5 w c 0 3 w c NR Pressure Switch Changes Setting Furnace Input kBtu hr Altitude ft PROPANE GAS CONVERSION WARNING POSSIBLE PROPERTY DAMAGE P...

Страница 20: ...1 8 Pipe Plug To Measure Line Gas Pressure General Furnace Layout UPFLOW INSTALLATIONS When the gas piping enters through the right side of the furnace the installer must supply the following fitting...

Страница 21: ...50 330 770 1 500 2 400 3 700 1 500 3 400 60 300 700 1 300 2 200 3 300 1 300 3 100 80 260 610 1 200 1 900 2 900 1 200 2 600 100 220 540 1 000 1 700 2 600 1 000 2 300 125 200 490 900 1 400 2 300 900 2 1...

Страница 22: ...g to the low heat circulating speed from entering the furnace and if manually operated must be equipped with means to prevent operation of either unit unless the damper is in the full heat or cool pos...

Страница 23: ...acts open completing the call for heat Gas valve closes extinguishing flame Induced draft blower is de energized following a fifteen second post purge Humidifier terminals are de energized Circulator...

Страница 24: ...um 13 0 w c Inlet Gas Supply Pressure If supply pressure differs from table make the necessary adjustments to pressure regulator gas piping size etc and or consult with local gas utility 5 Turn OFF ga...

Страница 25: ...eed If the correct amount of temperature rise is not obtained it may be necessary to change the blower speed An incorrect temperature rise can cause condensing in or overheating of the heat exchanger...

Страница 26: ...he motor then ramps to 100 of the required airflow A 1 minute OFF delay at 100 of the cooling airflow OFF 100 CFM Cooling Demand 100 CFM 1 min 50 CFM OFF min Profile C ramps up to 82 of the full cooli...

Страница 27: ...econds after the call for cooling ends During normal heating operation the circulator fan will come on approximately 37 seconds after the gas valve opens ON OFF ON OFF ON OFF ON OFF 1 2 1 2 1 2 1 2 90...

Страница 28: ...and monitors heat exchanger compartment temperatures It is an automatic reset temperature sensor The limit guards against the overheating as a resulting of insufficient air passing over the heat excha...

Страница 29: ...means of filtering all of the return air The installer will supply filter s at the time of installation FILTER MAINTENANCE Improper filter maintenance is the most common cause of inadequate heating o...

Страница 30: ...t off electric power and gas supply to the furnace 2 Remove screws securing manifold to burner bracket Slightly pull manifold out and away from burner bracket Burners will drop Re secure manifold to b...

Страница 31: ...it Inspect pressure switch hose Repair if necessary Inspect flue for blockage proper length elbows and termination Correct pressure switch setpoint or contact motion Tighten or correct wiring connecti...

Страница 32: ...or proper sensor alignment Check inlet air piping for blockage proper length elbows and termination Compare current gas pressure to rating plate info Adjust as needed Turn power OFF prior to repair Tu...

Страница 33: ...RLY O N SO M E M O D ELS IN DU C T OR C O IL P R ES S U RE SW ITC H LO W FIR E Y L R D BK W H IN DU C E D B R G N D WH WH BK BR RD GN BU BR W H A U XILIA R Y LIM IT C O NT R OLS R D B U W H VAC 115 VA...

Страница 34: ...ct failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know There s No Bette...

Отзывы: