background image

26

3. Knowing the furnace model, locate the high stage cooling

air flow charts in the Product Data Book applicable to your
model* .  Look up the cooling air flow determined in step 2
and find the required cooling speed and adjustment setting.

Example:

A 70 kBtu furnace is to be installed with a 2.5
ton air conditioning system.  The air flow
needed is 1000 CFM. Using the cooling speed
chart for the 70 kBtu furnace, find the airflow
closest to 1000 CFM.  A cooling airflow of 990
CFM can be attained by setting the cooling
speed to “C” and the adjustment to “-” (minus).

NOTE:

  Continuous Fan Speed will be 56% of

high stage cooling.

4. Locate the blower speed selection DIP switches on the

integrated control module.  Select the desired “cooling”
speed tap by positioning switches 1 and 2 appropriately.
Select the desired “adjust” tap by positioning switches 3
and 4 appropriately.  Refer to the following figure for switch
positions and their corresponding taps.  Turn off power to
furnace for a minimum of 10 seconds, allowing motor to
reset and recognize new speed selection.  Turn on power
to furnace.  Verify CFM by counting the number of times the
green CFM LED blinks.

5. The multi-speed circulator blower also offers several custom

ON/OFF ramping profiles.  These ramping profiles may be
used to enhance cooling performance and increase comfort
level.  The ramping profiles are selected using DIP switches
5 and 6.  Refer to the following figure for switch positions
and their corresponding taps.  Refer to the bullet points below
for a description of each ramping profile.  Turn off power to
furnace for a minimum of 10 seconds, allowing motor to
reset and recognize the new profile selection.  Turn on power
to the furnace.  Verify profile selection by counting the green
CFM LED blinks and timing each step of the ramping profile

Profile A provides only an OFF delay of 1 minute at 100% of
the cooling demand airflow.

100% CFM  

1 min  

100% CFM  

Cooling 

Demand 

OFF OFF 

• Profile B ramps up to full cooling demand airflow by first

stepping up to 50% of the full demand for 30 seconds.  The
motor then ramps to 100% of the required airflow.  A 1 minute
OFF delay at 100% of the cooling airflow.

OFF 

100% CFM  

Cooling Demand  

100% C FM  

1 min   

50% CFM 

OFF 

½ min 

Profile C ramps up to 82% of the full cooling demand airflow
and operates there for approximately 7 ½ minutes. The motor
then steps up to the full demand airflow.  Profile C also has
a 1 minute/100% OFF delay.

 

100% CFM  

100% CFM  

1 min  

82% CFM 

Cooling Demand

 

7 ½ min 

OFF 

OFF 

Profile D ramps up to 50% of the demand for ½ minute,
then ramps to 82% of the full cooling demand airflow and
operates there for approximately 7 ½ minutes. The motor

then steps up to the full demand airflow.  Profile D has a 1/
2 minute at 50% airflow OFF delay.

 

100% CFM  

50% CFM   

½

 min  

82% CFM 

Cooling Demand 

7 ½ min 

OFF 

OFF 

50% CFM 

½ min 

Ramping Profiles 

(*indicates factory setting)

 

Ramping 

Profile 

Tap A

 

Ramping 

Profile 

Tap B 

Ramping 

Profile 

Tap C

 

Ramping 

Profile 

Tap D

 

 8    7    6    5    4     3   2    1 

 


F

 



F

 

 8    7    6    5    4     3   2    1 

 



F

 



F

 

 8    7    6    5    4     3   2    1 

 


F

 



F

 

 8    7    6    5    4     3   2    1 

 



F

 



F

 

*

6. Select the heating speed from the heating speed chart in

the Product Data Book applicable for your model*.  The
adjust setting (already established by the cooling speed
selection) determines which set of speeds are available.
The selected speed must provide a temperature rise within
the rise range listed with the particular model.

Example:

The 70 kBtu is set for 990 CFM on cooling,
the “ADJUST” is set to “-” (minus).  The four
heating speeds available are “A Minus”, “B
Minus”, “C Minus”, and “D Minus”.   “B Minus”
has a rise of 56

°

F for both stages which is

within the 30-60°F rise range for the 70 kBtu.
This setting will keep electrical consumption
to a minimum.  Set the “Heat” speed DIP
switches to “A”.

7. Select the desired “heating” speed tap by positioning

switches 7 and 8 appropriately.  Refer to figure above.  Turn
off power to furnace for a minimum of 10 seconds, allowing
motor to reset and recognize new speed selection.  Turn on
power to furnace.  Verify selected CFM by counting the green
CFM LED blinks.

In general lower heating speeds will: reduce electrical consumption,
lower operating sound levels of the blower, and increase the outlet
air temperature delivered to the home.   The speeds available allow
the blower performance to be optimized for the particular
homeowner’s needs.

Содержание GMV8

Страница 1: ...han when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of co...

Страница 2: ...HECK 3 CHIMNEY CROWN CONDITION 13 CHECK 4 DEBRIS IN CLEANOUT 13 CHECK 5 LINER CONDITION 13 CHECK 6 DILUTION AIR 13 CHECK 7 COMPLETE THE INSTALLATION 13 FIX 1 LINER TERMINATION 14 FIX 2 CHANGE VENTING...

Страница 3: ...MPERATURE RISE 25 CIRCULATOR BLOWER SPEED ADJUSTMENT 25 ADJUST BLOWER HEAT OFF DELAY 27 CIRCULATOR BLOWER FAN TIMING ADJUSTMENT 27 XIII OPERATIONAL CHECKS 27 BURNER FLAME 27 AUXILIARY LIMIT CONTROL 27...

Страница 4: ...ponent failures could result in heating system operational problems TO THE INSTALLER Before installing this unit please read this manual thoroughly to familiarize yourself with specific items which mu...

Страница 5: ...stalling the control on a furnace Return any old or new controls to their containers before touching any ungrounded object III PRODUCT APPLICATION This furnace is primarily designed for residential ho...

Страница 6: ...ents and glues antistatic fabric softeners for clothes dryers and masonry acid washing materials WARNING POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE EXPLOSION SMOKE SOOT CONDENSTAION...

Страница 7: ...ATOR BLOWER REMOVAL 3 8 DIAMETER THREADED ROD 6 PLACES PROVIDE 8 MINMUM CLEARANCE BETWEEN CENTER ROD AND FURNACE CABINET TO ALLOW FOR CIRCULATOR BLOWER REMOVAL ASSURE FURNACE IS LEVEL FROM END TO END...

Страница 8: ...an 50 cubic feet per 1 000 BTU per hour of the aggregate input rating of all appliances installed in that space Rooms communicating directly with the space in which the appliances are installed throug...

Страница 9: ...sure Inlet Air Ventilation louvers for unheated crawl space Alternate air inlet Ventilation louvers each end of attic Equipment Located in Confined Spaces All Air from Outdoors Inlet Air from Ventilat...

Страница 10: ...eration of installed gas utilization equipment VI CATEGORY I VENTING VERTICAL VENTING WARNING TO PREVENT POSSIBLE PERSONAL INJURY OR DEATH DUE TO ASPHYXIATION THIS FURNACE MUST BE CATEGORY I VENTED DO...

Страница 11: ...ng In most situations the existing masonry chimneys will require a properly sized metallic liner WARNING POSSIBILITY OF PROPERTY DAMAGE PERSONAL INJURY OR DEATH DAMAGING CONDENSATION CAN OCCUR INSIDE...

Страница 12: ...condition Check 5 Yes Yes No Reline Fix 4 Dilution air available Check 6 Complete the installation Check 7 CHECK 1 PROPER CHIMNEY TERMINATION A masonry chimney used as a vent for gas fired equipment...

Страница 13: ...seal Use caution when doing this as the cut edges of flexible liners may be sharp The surfaces of the liner must be physically sound If gaps or holes are present the metal liner must be removed and r...

Страница 14: ...F ELECTRICAL SHOCK WIRING TO THE UNIT MUST BE POLARIZED AND GROUNDED FIX 1 LINER TERMINATION Any cap or roof assembly used with a liner must be approved by the liner manufacturer for such use The line...

Страница 15: ...SK OF INJURY ELECTRICAL SHOCK OR DEATH THE FURNACE MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR IN THEIR ABSENCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC CODE WARNING EDGES...

Страница 16: ...m located on the blower compartment door for further details of 115 Volt and 24 Volt wiring SINGLE STAGE THERMOSTAT APPLICATION W G Y Single Stage Heating with Single Stage Cooling R B C G R W1 W2 O Y...

Страница 17: ...G R W1 W2 CR35 R122 R128 W3 DS7 R191 R85 DS3 R84 R22 DS4 DS5 TP1 TP2 DEHUMIDIFICATION LED YELLOW DEHUMIDIFICATION JUMPER WIRE CUT TO ENABLE W 14 FOSSIL FUEL APPLICATIONS This furnace can be used in co...

Страница 18: ...cause poor combustion and equipment failure When this furnace is installed at high altitude the appropriate High Altitude orifice kit must be applied The furnace is supplied with orifices sized for na...

Страница 19: ...ranges and pressure switch kits High Low 70 90 115 7 500 0 5 w c 0 3 w c NR Pressure Switch Changes Setting Furnace Input kBtu hr Altitude ft PROPANE GAS CONVERSION WARNING POSSIBLE PROPERTY DAMAGE P...

Страница 20: ...1 8 Pipe Plug To Measure Line Gas Pressure General Furnace Layout UPFLOW INSTALLATIONS When the gas piping enters through the right side of the furnace the installer must supply the following fitting...

Страница 21: ...50 330 770 1 500 2 400 3 700 1 500 3 400 60 300 700 1 300 2 200 3 300 1 300 3 100 80 260 610 1 200 1 900 2 900 1 200 2 600 100 220 540 1 000 1 700 2 600 1 000 2 300 125 200 490 900 1 400 2 300 900 2 1...

Страница 22: ...g to the low heat circulating speed from entering the furnace and if manually operated must be equipped with means to prevent operation of either unit unless the damper is in the full heat or cool pos...

Страница 23: ...acts open completing the call for heat Gas valve closes extinguishing flame Induced draft blower is de energized following a fifteen second post purge Humidifier terminals are de energized Circulator...

Страница 24: ...um 13 0 w c Inlet Gas Supply Pressure If supply pressure differs from table make the necessary adjustments to pressure regulator gas piping size etc and or consult with local gas utility 5 Turn OFF ga...

Страница 25: ...eed If the correct amount of temperature rise is not obtained it may be necessary to change the blower speed An incorrect temperature rise can cause condensing in or overheating of the heat exchanger...

Страница 26: ...he motor then ramps to 100 of the required airflow A 1 minute OFF delay at 100 of the cooling airflow OFF 100 CFM Cooling Demand 100 CFM 1 min 50 CFM OFF min Profile C ramps up to 82 of the full cooli...

Страница 27: ...econds after the call for cooling ends During normal heating operation the circulator fan will come on approximately 37 seconds after the gas valve opens ON OFF ON OFF ON OFF ON OFF 1 2 1 2 1 2 1 2 90...

Страница 28: ...and monitors heat exchanger compartment temperatures It is an automatic reset temperature sensor The limit guards against the overheating as a resulting of insufficient air passing over the heat excha...

Страница 29: ...means of filtering all of the return air The installer will supply filter s at the time of installation FILTER MAINTENANCE Improper filter maintenance is the most common cause of inadequate heating o...

Страница 30: ...t off electric power and gas supply to the furnace 2 Remove screws securing manifold to burner bracket Slightly pull manifold out and away from burner bracket Burners will drop Re secure manifold to b...

Страница 31: ...it Inspect pressure switch hose Repair if necessary Inspect flue for blockage proper length elbows and termination Correct pressure switch setpoint or contact motion Tighten or correct wiring connecti...

Страница 32: ...or proper sensor alignment Check inlet air piping for blockage proper length elbows and termination Compare current gas pressure to rating plate info Adjust as needed Turn power OFF prior to repair Tu...

Страница 33: ...RLY O N SO M E M O D ELS IN DU C T OR C O IL P R ES S U RE SW ITC H LO W FIR E Y L R D BK W H IN DU C E D B R G N D WH WH BK BR RD GN BU BR W H A U XILIA R Y LIM IT C O NT R OLS R D B U W H VAC 115 VA...

Страница 34: ...ct failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know There s No Bette...

Отзывы: