7

• If the furnace is used in connection with a cooling unit, install

the furnace upstream or in parallel with the cooling unit coil.
Premature heat exchanger failure will result if the cooling
unit coil is placed ahead of the furnace.

• If the furnace is installed in a residential garage, position

the furnace so that the burners and ignition source are
located not less than 18 inches (457 mm) above the floor.
Protect the furnace from physical damage by vehicles.

• If the furnace is installed horizontally, the furnace access

doors must be vertical so that the burners fire horizontally
into the heat exchanger.  Do not install the unit with the
access doors on the “up/top” or “down/bottom” side of the
furnace.

• Do not connect this furnace to a chimney flue that serves a

separate appliance designed to burn solid fuel.

C

LEARANCES

 

AND

 A

CCESSIBILITY

Unobstructed front clearance of 24" 

for servicing

 is recommended.

TOP

B1-VENT

SINGLE

(PLENUM)

1"

6"

1"

3"

0"

1"

VENT

SIDES

FRONT

BACK

Top clearance for horizontal configuration - 1"

H

ORIZONTAL

 I

NSTALLATION

Line contact to framing is permitted when installed in the horizontal
configuration. Line contact is defined as the portion of the cabinet
that is formed by the intersection of the top and side.
ACCESSIBILITY CLEARANCE, WHERE GREATER, SHOULD
TAKE PRECEDENCE OVER MINIMUM FIRE PROTECTION
CLEARANCE.  A gas-fired furnace for installation in a residential
garage must be installed so that the ignition source and burners
are located not less than eighteen inches (18") above the floor and
is protected or located to prevent physical damage by vehicles.  A
gas furnace must not be installed directly on   carpeting, tile, or
other combustible materials other than wood flooring.

   

 

 

 

 

Vent Pipe Clearance to Combustibles -
6" using Single Wall Connector or 1" 
using B-1 vent.

Top - 1"

Side
Clearance - 1"

Back - 0"

Front Clearance - 3"

• Adequate combustion/ combustion air must be supplied to

the closet.

• Furnace must be 

completely

 sealed to floor or base.

Combustion/ ventilation air supply pipes must terminate 12"
from top of closet and 12" from floor of closet. DO NOT
remove solid base plate for bottom return.

• Return air ducts must be 

completely

 sealed to the furnace

and terminate outside the enclosure surfaces.

F

URNACE

 S

USPENSION

If suspending the furnace from rafters or joist, use 3/8" threaded
rod and 2”x2”x3/8” angle iron as shown below.  The length of rod
will depend on the application and the clearances necessary.

TILT  OUTWARD  TO  ALLOW  FOR

DOOR AND CIRCULATOR BLOWER

REMOVAL

3/8"  DIAMETER

 THREADED ROD

(6 PLACES)

PROVIDE  8"  MINMUM CLEARANCE BETWEEN

CENTER ROD  AND  FURNACE CABINET

TO ALLOW FOR CIRCULATOR BLOWER  REMOVAL 

ASSURE FURNACE IS LEVEL FROM

END TO END AND HAS A SLIGHT

FORWARD TILT WITH THE FRONT

OF THE FURNACE 0"-3/4" 

BELOW THE BACK OF THE FURNACE

POSITION AS CLOSE AS  POSSIBLE
TO BLOWER DECK TO ALLOW  FOR 

CIRCULATOR  BLOWER REMVOAL

HOLD DOWN

 NUTS

SUPPORT

NUTS

2"x2"x3/8"

ANGLE IRON

(3 PLACES)

Suspended Furnace

E

XISTING

 F

URNACE

 R

EMOVAL

NOTE:

 When an existing furnace is removed from a venting system

serving other appliances,

 

the venting system may be too large to

properly vent the remaining attached appliances.

The following vent testing procedure is reproduced from the

American National Standard/National Standard of Canada for
Gas-Fired Central Furnaces ANSI Z21.47b-2002, CSA-2.3b-2002
Section 1.23.1.

  The following steps shall be followed with each

appliance connected to the venting system placed in operation,
while any other appliances connected to the venting system are
not in operation:

a. Seal any unused openings in the venting system;
b. Inspect the venting system for proper size and horizontal

pitch, as required by the National Fuel Gas Code, ANSI
Z223.1 or the CAN/CSA B149 Installation Codes and these
instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies which
could cause an unsafe condition;

c. In so far as practical, close all building doors and windows

and all doors between the space in which the appliance(s)
connected to the venting system are located and other
spaces of the building. Turn on clothes dryers and any
appliance not connected to the venting system. Turn on any
exhaust fans, such as range hoods and bathroom exhausts,
so they shall operate at maximum speed. Do not operate a
summer exhaust fan. Close fireplace dampers;

d. Follow the lighting instructions. Place the appliance being

inspected in operation. Adjust thermostat so appliance shall
operate continuously;

e. Test for draft hood equipped appliance spillage at the draft

hood relief opening after 5 minutes of main burner operation.
Use the flame of a match or candle;

f. After it has been determined that each appliance connected

to the venting system properly vents when tested as outlined
above, return doors, windows, exhaust fans, fireplace
dampers and any other gas burning appliance to their
previous conditions of use;

g. If improper venting is observed during any of the above tests,

the venting system must be corrected.

Corrections must be in accordance with the latest edition of the
National Fuel Gas Code NFPA 54/ANSI Z223.1 and/or CAN/CSA
B149 Installation Codes.

Содержание GMV8

Страница 1: ...han when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of co...

Страница 2: ...HECK 3 CHIMNEY CROWN CONDITION 13 CHECK 4 DEBRIS IN CLEANOUT 13 CHECK 5 LINER CONDITION 13 CHECK 6 DILUTION AIR 13 CHECK 7 COMPLETE THE INSTALLATION 13 FIX 1 LINER TERMINATION 14 FIX 2 CHANGE VENTING...

Страница 3: ...MPERATURE RISE 25 CIRCULATOR BLOWER SPEED ADJUSTMENT 25 ADJUST BLOWER HEAT OFF DELAY 27 CIRCULATOR BLOWER FAN TIMING ADJUSTMENT 27 XIII OPERATIONAL CHECKS 27 BURNER FLAME 27 AUXILIARY LIMIT CONTROL 27...

Страница 4: ...ponent failures could result in heating system operational problems TO THE INSTALLER Before installing this unit please read this manual thoroughly to familiarize yourself with specific items which mu...

Страница 5: ...stalling the control on a furnace Return any old or new controls to their containers before touching any ungrounded object III PRODUCT APPLICATION This furnace is primarily designed for residential ho...

Страница 6: ...ents and glues antistatic fabric softeners for clothes dryers and masonry acid washing materials WARNING POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE EXPLOSION SMOKE SOOT CONDENSTAION...

Страница 7: ...ATOR BLOWER REMOVAL 3 8 DIAMETER THREADED ROD 6 PLACES PROVIDE 8 MINMUM CLEARANCE BETWEEN CENTER ROD AND FURNACE CABINET TO ALLOW FOR CIRCULATOR BLOWER REMOVAL ASSURE FURNACE IS LEVEL FROM END TO END...

Страница 8: ...an 50 cubic feet per 1 000 BTU per hour of the aggregate input rating of all appliances installed in that space Rooms communicating directly with the space in which the appliances are installed throug...

Страница 9: ...sure Inlet Air Ventilation louvers for unheated crawl space Alternate air inlet Ventilation louvers each end of attic Equipment Located in Confined Spaces All Air from Outdoors Inlet Air from Ventilat...

Страница 10: ...eration of installed gas utilization equipment VI CATEGORY I VENTING VERTICAL VENTING WARNING TO PREVENT POSSIBLE PERSONAL INJURY OR DEATH DUE TO ASPHYXIATION THIS FURNACE MUST BE CATEGORY I VENTED DO...

Страница 11: ...ng In most situations the existing masonry chimneys will require a properly sized metallic liner WARNING POSSIBILITY OF PROPERTY DAMAGE PERSONAL INJURY OR DEATH DAMAGING CONDENSATION CAN OCCUR INSIDE...

Страница 12: ...condition Check 5 Yes Yes No Reline Fix 4 Dilution air available Check 6 Complete the installation Check 7 CHECK 1 PROPER CHIMNEY TERMINATION A masonry chimney used as a vent for gas fired equipment...

Страница 13: ...seal Use caution when doing this as the cut edges of flexible liners may be sharp The surfaces of the liner must be physically sound If gaps or holes are present the metal liner must be removed and r...

Страница 14: ...F ELECTRICAL SHOCK WIRING TO THE UNIT MUST BE POLARIZED AND GROUNDED FIX 1 LINER TERMINATION Any cap or roof assembly used with a liner must be approved by the liner manufacturer for such use The line...

Страница 15: ...SK OF INJURY ELECTRICAL SHOCK OR DEATH THE FURNACE MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR IN THEIR ABSENCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC CODE WARNING EDGES...

Страница 16: ...m located on the blower compartment door for further details of 115 Volt and 24 Volt wiring SINGLE STAGE THERMOSTAT APPLICATION W G Y Single Stage Heating with Single Stage Cooling R B C G R W1 W2 O Y...

Страница 17: ...G R W1 W2 CR35 R122 R128 W3 DS7 R191 R85 DS3 R84 R22 DS4 DS5 TP1 TP2 DEHUMIDIFICATION LED YELLOW DEHUMIDIFICATION JUMPER WIRE CUT TO ENABLE W 14 FOSSIL FUEL APPLICATIONS This furnace can be used in co...

Страница 18: ...cause poor combustion and equipment failure When this furnace is installed at high altitude the appropriate High Altitude orifice kit must be applied The furnace is supplied with orifices sized for na...

Страница 19: ...ranges and pressure switch kits High Low 70 90 115 7 500 0 5 w c 0 3 w c NR Pressure Switch Changes Setting Furnace Input kBtu hr Altitude ft PROPANE GAS CONVERSION WARNING POSSIBLE PROPERTY DAMAGE P...

Страница 20: ...1 8 Pipe Plug To Measure Line Gas Pressure General Furnace Layout UPFLOW INSTALLATIONS When the gas piping enters through the right side of the furnace the installer must supply the following fitting...

Страница 21: ...50 330 770 1 500 2 400 3 700 1 500 3 400 60 300 700 1 300 2 200 3 300 1 300 3 100 80 260 610 1 200 1 900 2 900 1 200 2 600 100 220 540 1 000 1 700 2 600 1 000 2 300 125 200 490 900 1 400 2 300 900 2 1...

Страница 22: ...g to the low heat circulating speed from entering the furnace and if manually operated must be equipped with means to prevent operation of either unit unless the damper is in the full heat or cool pos...

Страница 23: ...acts open completing the call for heat Gas valve closes extinguishing flame Induced draft blower is de energized following a fifteen second post purge Humidifier terminals are de energized Circulator...

Страница 24: ...um 13 0 w c Inlet Gas Supply Pressure If supply pressure differs from table make the necessary adjustments to pressure regulator gas piping size etc and or consult with local gas utility 5 Turn OFF ga...

Страница 25: ...eed If the correct amount of temperature rise is not obtained it may be necessary to change the blower speed An incorrect temperature rise can cause condensing in or overheating of the heat exchanger...

Страница 26: ...he motor then ramps to 100 of the required airflow A 1 minute OFF delay at 100 of the cooling airflow OFF 100 CFM Cooling Demand 100 CFM 1 min 50 CFM OFF min Profile C ramps up to 82 of the full cooli...

Страница 27: ...econds after the call for cooling ends During normal heating operation the circulator fan will come on approximately 37 seconds after the gas valve opens ON OFF ON OFF ON OFF ON OFF 1 2 1 2 1 2 1 2 90...

Страница 28: ...and monitors heat exchanger compartment temperatures It is an automatic reset temperature sensor The limit guards against the overheating as a resulting of insufficient air passing over the heat excha...

Страница 29: ...means of filtering all of the return air The installer will supply filter s at the time of installation FILTER MAINTENANCE Improper filter maintenance is the most common cause of inadequate heating o...

Страница 30: ...t off electric power and gas supply to the furnace 2 Remove screws securing manifold to burner bracket Slightly pull manifold out and away from burner bracket Burners will drop Re secure manifold to b...

Страница 31: ...it Inspect pressure switch hose Repair if necessary Inspect flue for blockage proper length elbows and termination Correct pressure switch setpoint or contact motion Tighten or correct wiring connecti...

Страница 32: ...or proper sensor alignment Check inlet air piping for blockage proper length elbows and termination Compare current gas pressure to rating plate info Adjust as needed Turn power OFF prior to repair Tu...

Страница 33: ...RLY O N SO M E M O D ELS IN DU C T OR C O IL P R ES S U RE SW ITC H LO W FIR E Y L R D BK W H IN DU C E D B R G N D WH WH BK BR RD GN BU BR W H A U XILIA R Y LIM IT C O NT R OLS R D B U W H VAC 115 VA...

Страница 34: ...ct failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know There s No Bette...

Отзывы: