background image

4

Torch heat required to braze tubes of various sizes
is proportional to the size of the tube. Tubes of
smaller size require less heat to bring the tube to
brazing temperature before adding brazing alloy.
Applying too much heat to any tube can melt the
tube. Service personnel must use the appropriate
heat level for the size of the tube being brazed. NOTE:
The use of a heat shield when brazing is
recommended to avoid burning the serial plate or
the finish on the unit.

1. The ends of the refrigerant lines must be cut square,

deburred, cleaned, and be round and free from nicks or
dents.  Any other condition increases the chance of a
refrigerant leak.

2.  “Sweep” the refrigerant line with nitrogen or inert gas

during brazing to prevent the formation of copper-oxide
inside the refrigerant lines.  The POE oils used in R-
410A applications will clean any copper-oxide present
from the inside of the refrigerant lines and spread it
throughout the system. This may cause a blockage or
failure of the metering device.

3. After brazing, quench the joints with water or a wet cloth

to prevent overheating of the service valve.

4. Ensure the filter drier paint finish is intact after brazing.

If the paint of the steel filter drier has been burned or
chipped, repaint or treat with a rust preventative.  This is
especially important on suction line filter driers which
are continually wet when the unit is operating.

NOTE: 

 Be careful not to kink or dent refrigerant lines.  Kinked

or dented lines will cause poor performance or compressor
damage.

Do NOT make final refrigerant line connection until plugs
are removed from refrigerant tubing.

NOTE: 

 Before brazing, verify indoor piston size by checking

the piston kit chart packaged with indoor unit.

L

EAK

 T

ESTING

 (N

ITROGEN

 

OR

 N

ITROGEN

-T

RACED

)

T

O

 

AVOID

 

THE

 

RISK

 

OF

 

FIRE

 

OR

 

EXPLOSION

,

 

NEVER

 

USE

 

OXYGEN

,

 

HIGH

 

PRESSURE

 

AIR

 

OR

 

FLAMMABLE

 

GASES

 

FOR

 

LEAK

 

TESTING

 

OF

 

A

 

REFRIGERATION

 

SYSTEM

.

WARNING

T

O

 

AVOID

 

POSSIBLE

 

EXPLOSION

,

 

THE

 

LINE

 

FROM

 

THE

 

NITROGEN

 

CYLINDER

 

MUST

 

INCLUDE

 

A

 

PRESSURE

 

REGULATOR

 

AND

 

A

 

PRESSURE

 

RELIEF

 

VALVE

.

 

T

HE

 

PRESSURE

 

RELIEF

 

VALVE

 

MUST

 

BE

 

SET

 

TO

 

OPEN

 

AT

 

NO

 

MORE

 

THAN

 

150

 

PSIG

.

WARNING

Pressure test the system using dry nitrogen and soapy water
to locate leaks.  If you wish to use a leak detector, charge the
system to 10 psi using the appropriate refrigerant then use
nitrogen to finish charging the system to working pressure then
apply the detector to suspect areas. If leaks are found, repair
them. After repair, repeat the pressure test. If no leaks exist,
proceed to system evacuation.

S

YSTEM

 E

VACUATION

Condensing unit liquid and suction valves are closed to contain
the charge within the unit.  The unit is shipped with the valve
stems closed and caps installed.  

Do not open valves until

the system is evacuated.

REFRIGERANT

 

UNDER

 

PRESSURE!

F

AILURE

 

TO

 

FOLLOW

 

PROPER

 

PROCEDURES

 

MAY

 

CAUSE

 

PROPERTY

 

DAMAGE

,

 

PERSONAL

 

INJURY

 

OR

 

DEATH

.

WARNING

NOTE:

Scroll compressors should never be used to evacuate

or pump down a heat pump or air conditioning system.

P

ROLONGED

 

OPERATION

 

AT

 

SUCTION

 

PRESSURES

 

LESS

 

THAN

 

20

 

PSIG

 

FOR

 

MORE

 

THAN

 

5

 

SECONDS

 

WILL

 

RESULT

 

IN

 

OVERHEATING

 

OF

 

THE

 

SCROLLS

 

AND

 

PERMANENT

 

DAMAGE

 

TO

 

THE

 

SCROLL

 

TIPS

,

 

DRIVE

 

BEARINGS

 

AND

 

INTERNAL

 

SEAL

.

CAUTION

1. Connect the vacuum pump with 250 micron capability

to the service valves.

2. Evacuate the system to 250 microns or less using

suction 

and

 liquid service valves.  Using both valves is

necessary as some compressors create a mechanical
seal separating the sides of the system.

3. Close pump valve and hold vacuum for 10 minutes.

Typically pressure will rise during this period.

If the pressure rises to 1000 microns or less and remains
steady the system is considered leak-free; proceed to
startup.

If pressure rises above 1000 microns but holds steady
below 2000 microns, moisture and/or noncondensibles
may be present or the system may have a small leak.
Return to step 2: If the same result is encountered check
for leaks as previously indicated and repair as necessary
then repeat evacuation.

If pressure rises above 2000 microns, a leak is present.
Check for leaks as previously indicated and repair as
necessary then repeat evacuation.

Содержание CONDENSING UNITAIR CONDITIONING

Страница 1: ...four and a minimum of two IMPORTANT SAFETY INSTRUCTIONS The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards It is the owner s and instal...

Страница 2: ...pads or springs can be installed between the con densing unit legs or frame and the roof mounting assembly to reduce noise vibration SAFE REFRIGERANT HANDLING While these items will not cover every co...

Страница 3: ...red Insulation must be installed in a manner which protects tubing from damage and contamination Where possible drain as much residual compressor oil from existing systems lines and traps pay close at...

Страница 4: ...ITROGEN CYLINDER MUST INCLUDE A PRESSURE REGULATOR AND A PRESSURE RELIEF VALVE THE PRESSURE RELIEF VALVE MUST BE SET TO OPEN AT NO MORE THAN 150 PSIG WARNING Pressure test the system using dry nitroge...

Страница 5: ...protection devices are approved for use Time delay fuses HACR type circuit breakers These devices have sufficient time delay to permit the motor compressor to start and accelerate its load HIGH VOLTA...

Страница 6: ...charge has bled into the system open the liquid service valve The service valve cap is the secondary seal for the valves and must be properly tightened to prevent leaks Make sure cap is clean and appl...

Страница 7: ...and superheat are high adjust TXV valve to 7 to 9 F superheat then check subcooling d If subcooling is high and superheat is low adjust TXV valve to 7 to 9 F superheat and remove charge to lower the...

Страница 8: ...another In a traditional system the thermostat sends commands to the indoor and outdoor units via analog 24 VAC signals It is a one way communication path in that the indoor and outdoor units typical...

Страница 9: ...mostat CT Compatible Air Handler Furnace Modular Blower Integrated Control Module CT Compatible AC HP Integrated Control Module 1 2 R C System Wiring Using Four Wires TWO WIRE OUTDOOR FOUR WIRE INDOOR...

Страница 10: ...displayed in the scrolling display area while the data is being retrieved The first sub menu is then displayed See tables below for listing of air conditioner submenus Touch the or _ to step through t...

Страница 11: ...ecent AC HP fault For display only Fault 6 FAULT 6 Least recent AC HP fault For display only Clear Fault History CLEAR NO or YES Selecting YES clears the fault history NOTE Consecutively repeated faul...

Страница 12: ...bmenu Item Indication for Display Only not User Modifiable Mode MODE Displays the current air conditioner or heat pump operating mode CFM CFM Displays the airflow for the current operating mode STATUS...

Страница 13: ...s dc Data 2 should be approximately 2 2 volts dc The voltage difference between data 1 and data 2 should be approximately 0 6 volts dc Verify that the bus TERM dipswitches are in the ON position 1 2 O...

Страница 14: ...are securely twisted together prior to inserting into terminal block Verify installation type legacy traditional or communicating Check data 1 data 2 voltages Rapid Flashing Normal network traffic Co...

Страница 15: ...rcuit Test Control Circuit with Voltmeter Low Voltage Test Voltage Faulty Evaporator Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Re...

Страница 16: ...e indicated code 6 Flashes ON OFF OFF x Board miss operation INTERNAL FAULT EE x Compressor relay contacts welded x Replace control x Turn power OFF prior to repair x Replace with correct replacement...

Страница 17: ...emory card x Error code will be cleared once data is loaded Applies only to fully communicating system using ComfortNet thermostat x Air conditioner heat pump fails to operate x Air conditioner heat p...

Страница 18: ...indoor blower motor repair replace as needed x Check indoor thermostat setting x Turn power OFF prior to repair x Fault will clear after 30 consecutive normal cycles x Fault may be cleared by cycling...

Страница 19: ...tdoor fan motor capacitor replace as needed x Turn power OFF prior to repair x Replace with correct replacement part s x Compressor and outdoor fan are off x Low pressure switch trip 3 times within sa...

Страница 20: ...ompressor repair replace as needed x Check compressor wiring repair replace as needed x Turn power OFF prior to repair x Fault will clear after 1 normal cycle x Fault may be cleared by cycling 24VAC t...

Страница 21: ...all x Open Run Circuit Lockout OPEN RUN LOCK 07 x Compressor run winding is open x Compressor not properly wired to control x Faulty compressor wiring x Check compressor repair replace as needed x Che...

Страница 22: ...Check transformer replace if needed x Turn power OFF prior to repair x Fault will clear if secondary voltage rises above 21VAC x Replace with correct replacement part s x Compressor is off x Integrat...

Страница 23: ...23 THISPAGELEFTINTENTIONALLYBLANK...

Страница 24: ...rant Loss of refrigerant can cause poor operation and or severe equipment damage Do not use a condensing unit cover to protect the outdoor unit during the winter unless you first discuss it with your...

Отзывы: