background image

9

For example, assume the system is an air conditioner matched
with an air handler.  With a call for low stage cooling, the air
conditioner will calculate the system’s low stage cooling air-
flow demand.  The air conditioner will then send a fan request
along with the low stage cooling airflow demand to the air
handler.  Once received, the air handler will send the low stage
cooling airflow demand to the ECM motor.  The ECM motor
then delivers the low stage cooling airflow.  The table below
lists the nominal high and low stage airflow for the ComfortNet
air conditioners.

M ode l

High

Low

*SXC160241

800

600

*SXC160361

1200

800

*SXC160481

1550

1100

*SXC160601

1800

1400

*SXC180361

1250

850

*SXC180481

1750

1210

*SXC180601

1750

1210

CTK0* W

IRING

NOTE:

Refer to 

Electrical Connections - High Voltage

Connections

 for 208/230 volt line connections to the air

conditioner.

NOTE:

A removable plug connector is provided with the control

to make thermostat wire connections.  This plug may be
removed, wire connections made to the plug, and replaced.  It
is  strongly recommended that multiple wires into a single
terminal be twisted together prior to inserting into the plug
connector.  Failure to do so may result in intermittent operation.

Typical 18 AWG thermostat wire may be used to wire the sys-
tem components.  However, communications reliability may
be improved by using a high quality, shielded, twisted pair cable
for the data transmission lines.  In either case, 100 feet is the
maximum length of wire between indoor unit and outdoor unit,
or between indoor unit and thermostat.

F

OUR

-W

IRE

 I

NDOOR

 

AND

 O

UTDOOR

 W

IRING

Typical wiring will consist of four wires between the indoor unit
and outdoor unit and between the indoor unit and thermostat.
The required wires are: (a) data lines, 1 and 2; (b) thermostat
“R” (24 VAC hot) and “C” (24 VAC common).

1

2

R

C

1

2

R

C

CTK0*
Thermostat

CT Compatible
Air Handler/Furnace/Modular Blower
Integrated Control Module

CT Compatible AC/HP
Integrated Control Module

1

2

R

C

System Wiring Using Four-Wires

T

WO

-W

IRE

 O

UTDOOR

, F

OUR

-W

IRE

 I

NDOOR

 W

IRING

Two wires only may be utilized between the indoor and outdoor
units.  For this wiring scheme, only the data lines, 1 and 2, are
required between the indoor and outdoor units.  A 40 VA, 208/
230 VAC to 24 VAC transformer must be installed in the out-
door unit to provide 24 VAC power to the outdoor unit’s elec-
tronic control.  The transformer is included with the CTK0* kit.
See kit instructions for mounting and wiring instructions.  Four
wires are required between the indoor unit and thermostat.

NOTE:

Use of the CTK0* transformer is recommended if

installing a dual fuel system.  Failure to use the transformer in
the outdoor unit could result in over loading of the furnace
transformer.

1

2

R

C

1

2

R

C

CTK0*
Thermostat

CT Compatible Air 
Handler/Furnace/Modular
Blower Integrated 
Control Module

CT Compatible
AC/HP Integrated
Control Module

40VA Transformer (included in
            CTK0* kit)

208/230 VAC

24 VAC

1

2

R

C

System Wiring using Two-Wires between Furnace and AC/HP

and Four-Wires between Furnace and Thermostat

C

OMFORT

N

ET

™ S

YSTEM

 A

DVANCED

 F

EATURES

The ComfortNet system permits access to additional system
information, advanced setup features, and advanced diagnos-
tic/troubleshooting features.  These advanced features are or-
ganized into a menu structure.  The menus are accessed and
navigated as described below.

A

CCESSING

 

AND

 N

AVIGATING

 

THE

 A

DVANCED

 F

EATURES

 M

ENUS

The advanced system features are accessed using the
ComfortNet thermostat.  These advanced features are accessed
as follows:

On the CT thermostat Home Screen Display, touch
the 

Menu

 key to display additional key choices.

Touch and hold the 

Installer Config

 key for

approximately three seconds to enter the Thermostat
Options Configuration menu.

Touch and hold the 

Installer Config

 key again for

approximately three seconds to enter the Advanced
Installer Configuration menu.

Содержание CONDENSING UNITAIR CONDITIONING

Страница 1: ...four and a minimum of two IMPORTANT SAFETY INSTRUCTIONS The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards It is the owner s and instal...

Страница 2: ...pads or springs can be installed between the con densing unit legs or frame and the roof mounting assembly to reduce noise vibration SAFE REFRIGERANT HANDLING While these items will not cover every co...

Страница 3: ...red Insulation must be installed in a manner which protects tubing from damage and contamination Where possible drain as much residual compressor oil from existing systems lines and traps pay close at...

Страница 4: ...ITROGEN CYLINDER MUST INCLUDE A PRESSURE REGULATOR AND A PRESSURE RELIEF VALVE THE PRESSURE RELIEF VALVE MUST BE SET TO OPEN AT NO MORE THAN 150 PSIG WARNING Pressure test the system using dry nitroge...

Страница 5: ...protection devices are approved for use Time delay fuses HACR type circuit breakers These devices have sufficient time delay to permit the motor compressor to start and accelerate its load HIGH VOLTA...

Страница 6: ...charge has bled into the system open the liquid service valve The service valve cap is the secondary seal for the valves and must be properly tightened to prevent leaks Make sure cap is clean and appl...

Страница 7: ...and superheat are high adjust TXV valve to 7 to 9 F superheat then check subcooling d If subcooling is high and superheat is low adjust TXV valve to 7 to 9 F superheat and remove charge to lower the...

Страница 8: ...another In a traditional system the thermostat sends commands to the indoor and outdoor units via analog 24 VAC signals It is a one way communication path in that the indoor and outdoor units typical...

Страница 9: ...mostat CT Compatible Air Handler Furnace Modular Blower Integrated Control Module CT Compatible AC HP Integrated Control Module 1 2 R C System Wiring Using Four Wires TWO WIRE OUTDOOR FOUR WIRE INDOOR...

Страница 10: ...displayed in the scrolling display area while the data is being retrieved The first sub menu is then displayed See tables below for listing of air conditioner submenus Touch the or _ to step through t...

Страница 11: ...ecent AC HP fault For display only Fault 6 FAULT 6 Least recent AC HP fault For display only Clear Fault History CLEAR NO or YES Selecting YES clears the fault history NOTE Consecutively repeated faul...

Страница 12: ...bmenu Item Indication for Display Only not User Modifiable Mode MODE Displays the current air conditioner or heat pump operating mode CFM CFM Displays the airflow for the current operating mode STATUS...

Страница 13: ...s dc Data 2 should be approximately 2 2 volts dc The voltage difference between data 1 and data 2 should be approximately 0 6 volts dc Verify that the bus TERM dipswitches are in the ON position 1 2 O...

Страница 14: ...are securely twisted together prior to inserting into terminal block Verify installation type legacy traditional or communicating Check data 1 data 2 voltages Rapid Flashing Normal network traffic Co...

Страница 15: ...rcuit Test Control Circuit with Voltmeter Low Voltage Test Voltage Faulty Evaporator Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Re...

Страница 16: ...e indicated code 6 Flashes ON OFF OFF x Board miss operation INTERNAL FAULT EE x Compressor relay contacts welded x Replace control x Turn power OFF prior to repair x Replace with correct replacement...

Страница 17: ...emory card x Error code will be cleared once data is loaded Applies only to fully communicating system using ComfortNet thermostat x Air conditioner heat pump fails to operate x Air conditioner heat p...

Страница 18: ...indoor blower motor repair replace as needed x Check indoor thermostat setting x Turn power OFF prior to repair x Fault will clear after 30 consecutive normal cycles x Fault may be cleared by cycling...

Страница 19: ...tdoor fan motor capacitor replace as needed x Turn power OFF prior to repair x Replace with correct replacement part s x Compressor and outdoor fan are off x Low pressure switch trip 3 times within sa...

Страница 20: ...ompressor repair replace as needed x Check compressor wiring repair replace as needed x Turn power OFF prior to repair x Fault will clear after 1 normal cycle x Fault may be cleared by cycling 24VAC t...

Страница 21: ...all x Open Run Circuit Lockout OPEN RUN LOCK 07 x Compressor run winding is open x Compressor not properly wired to control x Faulty compressor wiring x Check compressor repair replace as needed x Che...

Страница 22: ...Check transformer replace if needed x Turn power OFF prior to repair x Fault will clear if secondary voltage rises above 21VAC x Replace with correct replacement part s x Compressor is off x Integrat...

Страница 23: ...23 THISPAGELEFTINTENTIONALLYBLANK...

Страница 24: ...rant Loss of refrigerant can cause poor operation and or severe equipment damage Do not use a condensing unit cover to protect the outdoor unit during the winter unless you first discuss it with your...

Отзывы: