background image

8

ADDITIONAL NOTES:

1. There are (4) LEDs on the PCB. See the 

Troubleshooting

Tables

 at the end of this manual

 

for definitions of the

LED status.

2. When system is at Standby mode, press “TEST” push

button to turn on both compressor and outdoor fan for
five (5) seconds.

3. Press “RECALL” push-button to retrieve the six most

recent faults.  The control must be in Standby Mode (no
thermostat inputs) to use the feature.  Depress the push-
button for approximately two seconds and less than five
seconds.  The LEDs will then display the six most recent
faults beginning with the most recent fault and
decrementing to the least recent fault.  The faults may
be cleared by depressing the button for greater than five
seconds.  Consecutively repeated faults are displayed
a maximum of three times.  Refer to the fault code
definitions at the end of this manual for more details.

4. “TERM” dipswitch is used for communications bus

configuration. Leave the settings to the factory default
position.

5. “LEARN” push button is used in communication mode

to  support device recognition on start-up. As the
communication system supports automatic identification
of both indoor unit and outdoor unit, this button is not
used for a normal start-up.

C

OMFORT

N

ET

™ S

YSTEM

O

VERVIEW

The ComfortNet system (or CT system) is a system that in-
cludes a ComfortNet compatible air handler/furnace/modular
blower and air conditioner or heat pump with a CTK0*AA ther-
mostat.  Any other system configurations are considered in-
valid ComfortNet systems and must be connected as a tradi-
tion (or legacy) system.  The table below compares the valid
CT systems.

CT compatib le

Air Handler/Furnace/Modular 

Blower

CT compatib le

Air Conditioner

Full CT system

b enefits & features

CT compatib le

Air Handler/Furnace/Modular 

Blower

CT compatib le

Heat Pump

Full CT system

b enefits & features

A ComfortNet heating/air conditioning system differs from a
legacy/traditional system in the manner in which the indoor
unit, outdoor unit and thermostat interact with one another.  In
a traditional system, the thermostat sends commands to the
indoor and outdoor units via analog 24 VAC signals.  It is a
one-way communication path in that the indoor and outdoor
units typically do not return information to the thermostat.

On the other hand, the indoor unit, outdoor unit, and thermo-
stat comprising a ComfortNet system “communicate” digitally
with one another.  It is now a two-way communications path.
The thermostat still sends commands to the indoor and out-
door units.  However, the thermostat may also request and
receive information from both the indoor and outdoor units.  This
information may be displayed on the CT thermostat.  The in-
door and outdoor units also interact with one another.  The
outdoor unit may send commands to or request information
from the indoor unit.  This two-way digital communications
between the thermostat and subsystems (indoor/outdoor unit)
and between subsystems is the key to unlocking the benefits
and features of the ComfortNet system.

Two-way digital communications is accomplished using only
two wires.  The thermostat and subsystem controls are pow-
ered with 24 VAC  Thus, a maximum of 4 wires between the
equipment and thermostat is all that is required to operate the
system.

A

IRFLOW

 C

ONSIDERATIONS

Airflow demands are managed differently in a fully communi-
cating system than they are in a legacy wired system.  The
system operating mode (as determined by the thermostat)
determines which unit calculates the system airflow demand.
If the indoor unit is responsible for determining the airflow de-
mand, it calculates the demand and sends it to the ECM motor.
If the outdoor unit or thermostat is responsible for determining
the demand, it calculates the demand and transmits the de-
mand along with a fan request to the indoor unit.  The indoor
unit then sends the demand to the ECM motor.  The following
table  lists the various ComfortNet™ systems, the operating
mode, and airflow demand source.

Sys te m

Sys te m  

Ope r ating M ode

Air flow  De m and 

Sour ce

Cooling

A ir Conditioner

Heating

A ir Handler

Continuous Fan

Thermostat

Cooling

A ir Conditioner

Heating

Furnace

Continuous Fan

Thermostat

A ir Condi 

A ir Handler

A ir Condi 

Furnace

Содержание CONDENSING UNITAIR CONDITIONING

Страница 1: ...four and a minimum of two IMPORTANT SAFETY INSTRUCTIONS The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards It is the owner s and instal...

Страница 2: ...pads or springs can be installed between the con densing unit legs or frame and the roof mounting assembly to reduce noise vibration SAFE REFRIGERANT HANDLING While these items will not cover every co...

Страница 3: ...red Insulation must be installed in a manner which protects tubing from damage and contamination Where possible drain as much residual compressor oil from existing systems lines and traps pay close at...

Страница 4: ...ITROGEN CYLINDER MUST INCLUDE A PRESSURE REGULATOR AND A PRESSURE RELIEF VALVE THE PRESSURE RELIEF VALVE MUST BE SET TO OPEN AT NO MORE THAN 150 PSIG WARNING Pressure test the system using dry nitroge...

Страница 5: ...protection devices are approved for use Time delay fuses HACR type circuit breakers These devices have sufficient time delay to permit the motor compressor to start and accelerate its load HIGH VOLTA...

Страница 6: ...charge has bled into the system open the liquid service valve The service valve cap is the secondary seal for the valves and must be properly tightened to prevent leaks Make sure cap is clean and appl...

Страница 7: ...and superheat are high adjust TXV valve to 7 to 9 F superheat then check subcooling d If subcooling is high and superheat is low adjust TXV valve to 7 to 9 F superheat and remove charge to lower the...

Страница 8: ...another In a traditional system the thermostat sends commands to the indoor and outdoor units via analog 24 VAC signals It is a one way communication path in that the indoor and outdoor units typical...

Страница 9: ...mostat CT Compatible Air Handler Furnace Modular Blower Integrated Control Module CT Compatible AC HP Integrated Control Module 1 2 R C System Wiring Using Four Wires TWO WIRE OUTDOOR FOUR WIRE INDOOR...

Страница 10: ...displayed in the scrolling display area while the data is being retrieved The first sub menu is then displayed See tables below for listing of air conditioner submenus Touch the or _ to step through t...

Страница 11: ...ecent AC HP fault For display only Fault 6 FAULT 6 Least recent AC HP fault For display only Clear Fault History CLEAR NO or YES Selecting YES clears the fault history NOTE Consecutively repeated faul...

Страница 12: ...bmenu Item Indication for Display Only not User Modifiable Mode MODE Displays the current air conditioner or heat pump operating mode CFM CFM Displays the airflow for the current operating mode STATUS...

Страница 13: ...s dc Data 2 should be approximately 2 2 volts dc The voltage difference between data 1 and data 2 should be approximately 0 6 volts dc Verify that the bus TERM dipswitches are in the ON position 1 2 O...

Страница 14: ...are securely twisted together prior to inserting into terminal block Verify installation type legacy traditional or communicating Check data 1 data 2 voltages Rapid Flashing Normal network traffic Co...

Страница 15: ...rcuit Test Control Circuit with Voltmeter Low Voltage Test Voltage Faulty Evaporator Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Re...

Страница 16: ...e indicated code 6 Flashes ON OFF OFF x Board miss operation INTERNAL FAULT EE x Compressor relay contacts welded x Replace control x Turn power OFF prior to repair x Replace with correct replacement...

Страница 17: ...emory card x Error code will be cleared once data is loaded Applies only to fully communicating system using ComfortNet thermostat x Air conditioner heat pump fails to operate x Air conditioner heat p...

Страница 18: ...indoor blower motor repair replace as needed x Check indoor thermostat setting x Turn power OFF prior to repair x Fault will clear after 30 consecutive normal cycles x Fault may be cleared by cycling...

Страница 19: ...tdoor fan motor capacitor replace as needed x Turn power OFF prior to repair x Replace with correct replacement part s x Compressor and outdoor fan are off x Low pressure switch trip 3 times within sa...

Страница 20: ...ompressor repair replace as needed x Check compressor wiring repair replace as needed x Turn power OFF prior to repair x Fault will clear after 1 normal cycle x Fault may be cleared by cycling 24VAC t...

Страница 21: ...all x Open Run Circuit Lockout OPEN RUN LOCK 07 x Compressor run winding is open x Compressor not properly wired to control x Faulty compressor wiring x Check compressor repair replace as needed x Che...

Страница 22: ...Check transformer replace if needed x Turn power OFF prior to repair x Fault will clear if secondary voltage rises above 21VAC x Replace with correct replacement part s x Compressor is off x Integrat...

Страница 23: ...23 THISPAGELEFTINTENTIONALLYBLANK...

Страница 24: ...rant Loss of refrigerant can cause poor operation and or severe equipment damage Do not use a condensing unit cover to protect the outdoor unit during the winter unless you first discuss it with your...

Отзывы: