background image

7

Run the remote on low stage cooling for 10 minutes until refrig-
erant pressures stabilize. Use the following guidelines and meth-
ods to check unit operation and ensure that the refrigerant
charge is within limits. Charge the unit on low stage.

1. Purge gauge lines. Connect service gauge manifold to

base-valve service ports.

2. Temporarily install a thermometer on the liquid line at

the liquid line service valve and 4-6" from the compressor
on the suction line. Ensure the thermometer makes
adequate contact and is insulated for best possible
readings. Use liquid line temperature to determine sub-
cooling and vapor temperature to determine superheat.

3. Check subcooling and superheat. Systems with TXV

application should have a subcooling of 5 to 7ºF and
superheat of 7 to 9 ºF.

a.

If subcooling and superheat are low, 

adjust

 TXV to 7

to 9 ºF superheat, then check subcooling.

NOTE: 

 To adjust superheat, turn the valve stem

clockwise to increase and counter clockwise to de-
crease.

b.

If subcooling is low and superheat is high, 

add 

charge

to raise subcooling to 5 to 7 ºF then check super-
heat.

c.

If subcooling and superheat are high, 

adjust

 TXV

valve to 7 to 9 ºF superheat, then check subcooling.

d.

If subcooling is high and superheat is low, 

adjust

TXV valve to 7 to 9 ºF superheat and 

remove 

charge

to lower the subcooling to 5 to 7 ºF.

NOTE:

  Do 

NOT 

adjust the charge based on suction

pressure unless there is a gross undercharge.

4. Disconnect manifold set, installation is complete.

NOTE: 

Check the Schrader ports for leaks and tighten valve

cores if necessary. Install caps finger-tight.

SUPERHEAT FORMULA =

SUCT. LINE TEMP. - SAT. SUCT. TEMP.

LIQUID  PRESSURE

PSIG  

R-22  

R-410A  

200

101

70

210

105

73

220

108

76

225

110

78

235

113

80

245

116

83

255

119

85

265

121

88

275

124

90

285

127

92

295

130

95

305

133

97

325

137

101

355

144

108

375

148

112

405

155

118

415

157

119

425

n/a

121

435

n/a

123

445

n/a

125

475

n/a

130

500

n/a

134

525

n/a

138

550

n/a

142

575

n/a

145

600

n/a

149

625

n/a

152

SATURATED LIQUID PR ESSU RE

 TEMPER ATU RE  CHART

SATURATED  LIQUID 

TEMPERATURE ºF

SUCTION PRESSURE

PSIG  

R-22  

R-410A  

50

26

1

52

28

3

54

29

4

56

31

6

58

32

7

60

34

8

62

35

10

64

37

11

66

38

13

68

40

14

70

41

15

72

42

16

74

44

17

76

45

19

78

46

20

80

48

21

85

50

24

90

53

26

95

56

29

100

59

31

110

64

36

120

69

41

130

73

45

140

78

49

150

83

53

160

86

56

170

90

60

SATURATED SUCTION PRESSURE

 TEMPERATURE CHART

SATURATED SUCTION 

TEMPERATURE ºF

Содержание CONDENSING UNITAIR CONDITIONING

Страница 1: ...four and a minimum of two IMPORTANT SAFETY INSTRUCTIONS The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards It is the owner s and instal...

Страница 2: ...pads or springs can be installed between the con densing unit legs or frame and the roof mounting assembly to reduce noise vibration SAFE REFRIGERANT HANDLING While these items will not cover every co...

Страница 3: ...red Insulation must be installed in a manner which protects tubing from damage and contamination Where possible drain as much residual compressor oil from existing systems lines and traps pay close at...

Страница 4: ...ITROGEN CYLINDER MUST INCLUDE A PRESSURE REGULATOR AND A PRESSURE RELIEF VALVE THE PRESSURE RELIEF VALVE MUST BE SET TO OPEN AT NO MORE THAN 150 PSIG WARNING Pressure test the system using dry nitroge...

Страница 5: ...protection devices are approved for use Time delay fuses HACR type circuit breakers These devices have sufficient time delay to permit the motor compressor to start and accelerate its load HIGH VOLTA...

Страница 6: ...charge has bled into the system open the liquid service valve The service valve cap is the secondary seal for the valves and must be properly tightened to prevent leaks Make sure cap is clean and appl...

Страница 7: ...and superheat are high adjust TXV valve to 7 to 9 F superheat then check subcooling d If subcooling is high and superheat is low adjust TXV valve to 7 to 9 F superheat and remove charge to lower the...

Страница 8: ...another In a traditional system the thermostat sends commands to the indoor and outdoor units via analog 24 VAC signals It is a one way communication path in that the indoor and outdoor units typical...

Страница 9: ...mostat CT Compatible Air Handler Furnace Modular Blower Integrated Control Module CT Compatible AC HP Integrated Control Module 1 2 R C System Wiring Using Four Wires TWO WIRE OUTDOOR FOUR WIRE INDOOR...

Страница 10: ...displayed in the scrolling display area while the data is being retrieved The first sub menu is then displayed See tables below for listing of air conditioner submenus Touch the or _ to step through t...

Страница 11: ...ecent AC HP fault For display only Fault 6 FAULT 6 Least recent AC HP fault For display only Clear Fault History CLEAR NO or YES Selecting YES clears the fault history NOTE Consecutively repeated faul...

Страница 12: ...bmenu Item Indication for Display Only not User Modifiable Mode MODE Displays the current air conditioner or heat pump operating mode CFM CFM Displays the airflow for the current operating mode STATUS...

Страница 13: ...s dc Data 2 should be approximately 2 2 volts dc The voltage difference between data 1 and data 2 should be approximately 0 6 volts dc Verify that the bus TERM dipswitches are in the ON position 1 2 O...

Страница 14: ...are securely twisted together prior to inserting into terminal block Verify installation type legacy traditional or communicating Check data 1 data 2 voltages Rapid Flashing Normal network traffic Co...

Страница 15: ...rcuit Test Control Circuit with Voltmeter Low Voltage Test Voltage Faulty Evaporator Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Re...

Страница 16: ...e indicated code 6 Flashes ON OFF OFF x Board miss operation INTERNAL FAULT EE x Compressor relay contacts welded x Replace control x Turn power OFF prior to repair x Replace with correct replacement...

Страница 17: ...emory card x Error code will be cleared once data is loaded Applies only to fully communicating system using ComfortNet thermostat x Air conditioner heat pump fails to operate x Air conditioner heat p...

Страница 18: ...indoor blower motor repair replace as needed x Check indoor thermostat setting x Turn power OFF prior to repair x Fault will clear after 30 consecutive normal cycles x Fault may be cleared by cycling...

Страница 19: ...tdoor fan motor capacitor replace as needed x Turn power OFF prior to repair x Replace with correct replacement part s x Compressor and outdoor fan are off x Low pressure switch trip 3 times within sa...

Страница 20: ...ompressor repair replace as needed x Check compressor wiring repair replace as needed x Turn power OFF prior to repair x Fault will clear after 1 normal cycle x Fault may be cleared by cycling 24VAC t...

Страница 21: ...all x Open Run Circuit Lockout OPEN RUN LOCK 07 x Compressor run winding is open x Compressor not properly wired to control x Faulty compressor wiring x Check compressor repair replace as needed x Che...

Страница 22: ...Check transformer replace if needed x Turn power OFF prior to repair x Fault will clear if secondary voltage rises above 21VAC x Replace with correct replacement part s x Compressor is off x Integrat...

Страница 23: ...23 THISPAGELEFTINTENTIONALLYBLANK...

Страница 24: ...rant Loss of refrigerant can cause poor operation and or severe equipment damage Do not use a condensing unit cover to protect the outdoor unit during the winter unless you first discuss it with your...

Отзывы: