HEATING PERFORMANCE DATA
PERFORMANCE TEST
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:
If conditions vary from this, results will change as follows:
1.
As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low and
high side pressures and power will not change.
2.
As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will
occur in low and high side pressures and power.
A properly operating unit should be within plus or minus
2 degrees
of the subcooling value shown in the Heat Pump
Specifications.
A properly operating unit should be within plus or minus
3 degrees
of the typical (Delta T) value shown.
A properly operating unit should be within plus or minus
7 PSIG
of the
HI PR
shown.
A properly operating unit should be within plus or minus
3 PSIG
of the
LO PR
shown.
A properly operating unit should be within plus or minus
3 Amps
of the typical value shown.
EXPANDED PERFORMANCE DATA
MODEL: GSH13060-4A* / ARUF61-00*-1* / ARUF48601A*
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
69.8
66.0
62.2
58.1
55.5
53.8
50.0
46.1
43.6
40.3
37.1
35.0
33.7
30.2
26.8
23.4
20.0
16.3
Delta T
35.9
34.0
32.0
29.9
28.5
27.7
25.7
23.7
22.4
20.7
19.1
18.0
17.3
15.6
13.8
12.0
10.3
8.4
KW
5.12
5.02
4.92
4.83
4.77
4.73
4.63
4.54
4.66
4.56
4.45
4.39
4.35
4.25
4.15
4.05
3.94
3.84
AMPS
3.7
3.6
3.5
3.5
3.5
3.4
3.4
3.4
3.3
3.3
3.3
3.3
3.3
3.2
3.2
3.2
3.1
3.1
COP
3.99
3.85
3.70
3.52
3.41
3.33
3.15
2.97
2.74
2.59
2.43
2.33
2.27
2.08
1.89
1.69
1.48
1.25
EER
13.6
13.2
12.6
12.0
11.6
11.4
10.8
10.2
9.4
8.8
8.3
8.0
7.7
7.1
6.5
5.8
5.1
4.3
HI PR
197
189
181
173
169
166
160
153
147
140
135
131
129
124
119
115
110
107
LO PR
72
67
63
58
54
52
48
43
39
35
30
28
27
23
20
17
15
11
High pressure is measured at the suction service valve ( the larger valve).
AMPS = Outdoor unit amps (comp.+fan)
Low pressure is measured at the gauge port connection.
KW = Total system power
Calculations are based on nominal CFM and 70 °F indoor dry bulb.
*Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temperature.
GSH13
Содержание ASH Series
Страница 76: ...5 W D H PRODUCT DIMENSIONS Model Dimensions W x D x H GSH101203AC 35 x 35 x 41 ...
Страница 210: ...CONTROL COVER CONTROL BOX 4 RP 364A www goodmanmfg com www amana hac com ...
Страница 212: ...COMPRESSOR TUBING ASSEMBLY 6 RP 364A www goodmanmfg com www amana hac com ...
Страница 214: ...COIL CABINET TOP SIDE PANELS 8 RP 364A www goodmanmfg com www amana hac com ...
Страница 219: ...Control Cover Control Box 4 RP 436G www goodmanmfg com www amana hac com ...
Страница 221: ...Basepan Compressor Coil Assembly 6 RP 436G www goodmanmfg com www amana hac com ...
Страница 223: ...Tubing Assembly 8 RP 436G www goodmanmfg com www amana hac com ...
Страница 225: ...Cabinet Top Side Panels 10 RP 436G www goodmanmfg com www amana hac com ...
Страница 230: ...Control Cover Control Box 4 RP 356D ...
Страница 232: ...Tubing Assembly 6 RP 356D ...
Страница 234: ...Cabinet Top Side Panels Cond Coil 8 RP 356D ...
Страница 239: ...Control Cover Control Box 4 RP 392E www amana hac com ...
Страница 241: ...Coil Compressor Tubing 6 RP 392E www amana hac com ...
Страница 243: ...Cabinet Top Side Panels 8 RP 392E www amana hac com ...
Страница 248: ...Control Cover Control Box 4 RP 569A www goodmanmfg com www amana hac com ...
Страница 250: ...Cabinet Top Side Panels Cond Coil 6 RP 569A www goodmanmfg com www amana hac com ...
Страница 252: ...Tubing Assembly 8 RP 569A www goodmanmfg com www amana hac com ...