SERVICING
41
DIPSWITCH FUNCTIONS
The MBE air handler motor has an electronic control that
contains an eight (8) position dip switch. The function of
these dipswitches are shown in
Table 1.
D ipsw itch N um ber
Function
1
2
3
N /A
4
Indoor Therm ostat
5
6
7
8
Cooling & Heat Pum p CFM
CFM Trim Adjust
Electric H eat
Table 1
CFM DELIVERY
Tables 2, 2A
and
3, 3A
show the CFM output for dipswitch
combinations 1-2, 5-6 and 7-8.
Model
Switch 1
Switch 2
CFM
OFF
OFF
1,200
ON
OFF
1,000
OFF
ON
800
ON
ON
600
OFF
OFF
1,600
ON
OFF
1,400
OFF
ON
1,200
ON
ON
1,000
OFF
OFF
2,000
ON
OFF
1,800
OFF
ON
1,600
ON
ON
1,200
MBE1200
MBE1600
MBE2000
Electric Heat Operation
Table 2
Model
Switch 5
Switch 6
CFM
OFF
OFF
1,200
ON
OFF
1,000
OFF
ON
800
ON
ON
600
OFF
OFF
1,600
ON
OFF
1,400
OFF
ON
1,200
ON
ON
1,000
OFF
OFF
1,600
ON
OFF
1,400
OFF
ON
1,200
ON
ON
1,000
Cooling/Heat Pump Operation
MBE2000
MBE1200
MBE1600
Table 2A
Dipswitch 1/2 & 7/8
AEPF 1830
Heating
Element
(kw)
1
2
7
8
UP TO 10
OFF
OFF
OFF
OFF
1100
1210
UP TO 10
ON
OFF
OFF
OFF
890
935
5
OFF
ON
OFF
OFF
700
770
AEPF3036 / 3137 / 4260
Heating
Element
(kw)
1
2
7
8
UP TO 20
OFF
OFF
OFF
OFF
2050
2150
UP TO 20
ON
OFF
OFF
OFF
1750
1835
UP TO 15
OFF
ON
OFF
OFF
1600
1680
UP TO 10
ON
ON
OFF
OFF
1200
1260
UP TO 10
ON
ON
OFF
ON
1020
1070
Heat Pump
With Backup
Switch
Position
Switch
Position
Switch
Position
Switch
Position
Emergency
Backup
Heat Pump
With Backup
Emergency
Backup
Table 3
Dipswitch 5/6 & 7/8
AEPF 1830
5
6
7
8
Cooling
Heat Pump
OFF
OFF
OFF
OFF
1100
1100
ON
OFF
OFF
OFF
800
800
OFF
ON
OFF
OFF
600
600
5
6
7
8
Cooling
Heat Pump
OFF
OFF
OFF
OFF
1800
1800
ON
OFF
OFF
OFF
1580
1580
OFF
ON
OFF
OFF
1480
1480
ON
ON
OFF
OFF
1200
1200
ON
ON
OFF
ON
1020
1020
Switch
Position
Switch
Position
Indoor Airflow
Switch
Position
Switch
Position
Indoor Airflow
AEPF3036 / 3137 / 4260
Table 3A
THERMOSTAT “FAN ONLY” MODE
During Fan Only Operations, the CFM output is 30% of the
cooling setting.
CFM TRIM ADJUST
Minor adjustments can be made through the dip switch
combination of 7-8.
Table 4
shows the switch position for
this feature.
NOTE:
The airflow will not make the decreasing adjustment
in Electric Heat mode.
C FM
S w it c h 7
S w it c h 8
+ 1 0 %
O N
O F F
- 1 5 %
O F F
O N
Table 4
Содержание ASH Series
Страница 76: ...5 W D H PRODUCT DIMENSIONS Model Dimensions W x D x H GSH101203AC 35 x 35 x 41 ...
Страница 210: ...CONTROL COVER CONTROL BOX 4 RP 364A www goodmanmfg com www amana hac com ...
Страница 212: ...COMPRESSOR TUBING ASSEMBLY 6 RP 364A www goodmanmfg com www amana hac com ...
Страница 214: ...COIL CABINET TOP SIDE PANELS 8 RP 364A www goodmanmfg com www amana hac com ...
Страница 219: ...Control Cover Control Box 4 RP 436G www goodmanmfg com www amana hac com ...
Страница 221: ...Basepan Compressor Coil Assembly 6 RP 436G www goodmanmfg com www amana hac com ...
Страница 223: ...Tubing Assembly 8 RP 436G www goodmanmfg com www amana hac com ...
Страница 225: ...Cabinet Top Side Panels 10 RP 436G www goodmanmfg com www amana hac com ...
Страница 230: ...Control Cover Control Box 4 RP 356D ...
Страница 232: ...Tubing Assembly 6 RP 356D ...
Страница 234: ...Cabinet Top Side Panels Cond Coil 8 RP 356D ...
Страница 239: ...Control Cover Control Box 4 RP 392E www amana hac com ...
Страница 241: ...Coil Compressor Tubing 6 RP 392E www amana hac com ...
Страница 243: ...Cabinet Top Side Panels 8 RP 392E www amana hac com ...
Страница 248: ...Control Cover Control Box 4 RP 569A www goodmanmfg com www amana hac com ...
Страница 250: ...Cabinet Top Side Panels Cond Coil 6 RP 569A www goodmanmfg com www amana hac com ...
Страница 252: ...Tubing Assembly 8 RP 569A www goodmanmfg com www amana hac com ...