TROUBLESHOOTING CHART
Complaint
System
Operating
Pressures
POSSIBLE CAUSE
DOTS IN ANALYSIS
GUIDE INDICATE
"POSSIBLE CAUSE"
SYM
PT
OM
S
ystem will not star
t
Compr
e
ssor
will not star
t -
fan r
uns
C
o
mp. and C
ond. F
an w
ill not star
t
E
v
apor
ator
fan w
ill not star
t
C
ondenser
fan w
ill not star
t
C
o
mpressor runs - goes off on overload
Compr
e
ssor
cycles on over
load
S
ystem runs continuously
- little cooling/htg
Too cool and then too w
a
rm
N
o
t cool enough on w
a
rm days
C
e
rtain areas too cool, others too w
a
rm
Compr
e
ssor
is noisy
S
ystem runs - blow
s cold air in heating
Unit will not ter
m
inate defr
o
st
Unit will not defr
o
st
Low
suction pressure
Low
head pressure
H
igh suction pressure
H
igh head pressure
Test Method
Remedy
See Ser
v
ice Pr
o
ced
u
re R
e
f.
Power Failure
•
Test Voltage
S-1
Blown Fuse
•
• •
Inspect Fuse Size & Type
S-1
Unbalanced Power, 3PH
•
• •
Test Voltage
S-1
Loose Connection
•
•
•
Inspect Connection - Tighten
S-2, S-3
Shorted or Broken Wires
• • • • • •
Test Circuits With Ohmmeter
S-2, S-3
Open Fan Overload
• •
Test Continuity of Overload
S-17A
Faulty Thermostat
•
• •
•
Test Continuity of Thermostat & Wiring
S-3
Faulty Transformer
•
•
Check Control Circuit with Voltmeter
S-4
Shorted or Open Capacitor
•
• • • •
Test Capacitor
S-15
Internal Compressor Overload Open
•
♦
Test Continuity of Overload
S-17A
Shorted or Grounded Compressor
•
•
Test Motor Windings
S-17B
Compressor Stuck
•
• •
♦
Use Test Cord
S-17D
Faulty Compressor Contactor
•
• •
Test Continuity of Coil & Contacts
S-7, S-8
Faulty Fan Relay
•
Test Continuity of Coil And Contacts
S-7
Open Control Circuit
•
Test Control Circuit with Voltmeter
S-4
Low Voltage
•
• •
Test Voltage
S-1
Faulty Evap. Fan Motor
•
•
♦
Repair or Replace
S-16
Shorted or Grounded Fan Motor
•
•
Test Motor Windings
S-16
Improper Cooling Anticipator
•
•
Check Resistance of Anticipator
S-3B
Shortage of Refrigerant
• •
♦
• •
Test For Leaks, Add Refrigerant
S-101,103
Restricted Liquid Line
• •
• •
•
Remove Restriction, Replace Restricted Part
S-112
Open Element or Limit on Elec. Heater
♦
♦
Test Heater Element and Controls
S-26,S-27
Dirty Air Filter
•
• •
•
♦
Inspect Filter-Clean or Replace
Dirty Indoor Coil
•
• •
•
♦
Inspect Coil - Clean
Not enough air across Indoor Coil
•
• •
•
♦
Check Blower Speed, Duct Static Press, Filter
S-200
Too much air across Indoor Coil
♦
•
Reduce Blower Speed
S-200
Overcharge of Refrigerant
• •
•
♦
• •
Recover Part of Charge
S-113
Dirty Outdoor Coil
• •
•
♦
•
Inspect Coil - Clean
Noncondensibles
•
•
♦
•
Recover Charge, Evacuate, Recharge
S-114
Recirculation of Condensing Air
•
•
•
Remove Obstruction to Air Flow
Infiltration of Outdoor Air
•
• •
Check Windows, Doors, Vent Fans, Etc.
Improperly Located Thermostat
•
•
Relocate Thermostat
Air Flow Unbalanced
•
•
Readjust Air Volume Dampers
System Undersized
•
•
Refigure Cooling Load
Broken Internal Parts
•
♦
Replace Compressor
S-115
Broken Valves
•
•
• •
Test Compressor Efficiency
S-104
Inefficient Compressor
•
♦
• •
Test Compressor Efficiency
S-104
Wrong Type Expansion Valve
• • •
•
• •
♦
Replace Valve
S-110
Expansion Device Restricted
• • •
•
• •
•
Remove Restriction or Replace Expansion Device
S-110
Oversized Expansion Valve
•
•
Replace Valve
Undersized Expansion Valve
• • •
•
•
Replace Valve
Expansion Valve Bulb Loose
•
•
Tighten Bulb Bracket
S-105
Inoperative Expansion Valve
•
•
•
Check Valve Operation
S-110
Loose Hold-down Bolts
•
Tighten Bolts
Faulty Reversing Valve
•
♦ ♦ ♦
♦ ♦ ♦
Replace Valve or Solenoid
S-21, 122
Faulty Defrost Control
•
♦ ♦ ♦ ♦ ♦
♦
Test Control
S-24
Faulty Defrost Thermostat
♦ ♦ ♦ ♦ ♦ ♦ ♦
Test Defrost Thermostat
S-25
Flowrator Not Seating Properly
•
• •
Check Flowrator & Seat or Replace Flowrator
S-111
•
Cooling or Heating Cycle (Heat Pump)
♦
COOLING/HP ANALYSIS CHART
No Cooling
Unsatisfactory Cooling/Heating
Heating Cycle Only (Heat Pump)
Содержание ASH Series
Страница 76: ...5 W D H PRODUCT DIMENSIONS Model Dimensions W x D x H GSH101203AC 35 x 35 x 41 ...
Страница 210: ...CONTROL COVER CONTROL BOX 4 RP 364A www goodmanmfg com www amana hac com ...
Страница 212: ...COMPRESSOR TUBING ASSEMBLY 6 RP 364A www goodmanmfg com www amana hac com ...
Страница 214: ...COIL CABINET TOP SIDE PANELS 8 RP 364A www goodmanmfg com www amana hac com ...
Страница 219: ...Control Cover Control Box 4 RP 436G www goodmanmfg com www amana hac com ...
Страница 221: ...Basepan Compressor Coil Assembly 6 RP 436G www goodmanmfg com www amana hac com ...
Страница 223: ...Tubing Assembly 8 RP 436G www goodmanmfg com www amana hac com ...
Страница 225: ...Cabinet Top Side Panels 10 RP 436G www goodmanmfg com www amana hac com ...
Страница 230: ...Control Cover Control Box 4 RP 356D ...
Страница 232: ...Tubing Assembly 6 RP 356D ...
Страница 234: ...Cabinet Top Side Panels Cond Coil 8 RP 356D ...
Страница 239: ...Control Cover Control Box 4 RP 392E www amana hac com ...
Страница 241: ...Coil Compressor Tubing 6 RP 392E www amana hac com ...
Страница 243: ...Cabinet Top Side Panels 8 RP 392E www amana hac com ...
Страница 248: ...Control Cover Control Box 4 RP 569A www goodmanmfg com www amana hac com ...
Страница 250: ...Cabinet Top Side Panels Cond Coil 6 RP 569A www goodmanmfg com www amana hac com ...
Страница 252: ...Tubing Assembly 8 RP 569A www goodmanmfg com www amana hac com ...