26
-
CHECK
DIAGNOSTIC
LED - RED
CHECK FUSE(S)
CHECK INPUT POWER
-
GAS PRESSURE
GAS FLOW
OFF
ON
1 FLASH
IGNITION FAILURE
NORMAL OPERATION
NO POWER OR
INTERNAL CONTROL
FAULT
STATUS
CHECK
3 MIN COMP. SHORT
CYCLE DELAY
COMPR. SHORT CYCLE DELAY
6 FLASHES
CHECK FOR SHORTS IN
FLAME SENSOR WIRING
CHECK GAS VALVE
CHECK ROLLOUT LIMIT SW.
CHECK AUXILIARY LIMIT SW.
CHECK MAIN LIMIT SWITCH
CHECK WIRING FOR SHORTS
CHECK PRESSURE SWITCH
PRESSURE SWITCH CLOSED
CHECK VENT MOTOR
CHECK TUBING
FLAME SENSOR
GAS VALVE
CHECK PRESSURE SWITCH
3 FLASHES
2 FLASHES
4 FLASHES
5 FLASHES
FALSE FLAME DETECTED
OPEN LIMIT SWITCH
WITHOUT INDUCER ON
PRESSURE SWITCH OPEN
CHECK FOR SHORTS IN
FLAME SENSOR WIRING
-
NORMAL FLAME PRESENT
DIAGNOSTIC
LED - AMBER
-
GAS PRESSURE
FLAME SENSOR
GAS VALVE
GAS FLOW
CHECK GAS VALVE
ON
OFF
1 FLASH
2 FLASHES
FALSE FLAME DETECTED
LOW FLAME SIGNAL
NO FLAME PRESENT
STATUS
CHECK
NOTE:
Fault Recall
The ignition control stores the last 5 faults in memory with the most recent fault indicated first. To retrieve the faults, de
-
press the fault recall button for 2 seconds while in the stand-by mode. To clear the fault memory, depress fault button for 5
seconds but not more than 10 seconds.
TROUBLESHOOTING
APPENDIX