10
200 PSIG
Maximum
5 to 15 PSIG
(20 PSIG Max.)
Continuous
11" W.C.
Second Stage
Regulator
First Stage
Regulator
Typical Propane Gas Piping
Sizing Between First and Second Stage Regulator
Maximum Propane Capacities listed are based on 1 PSIG Pressure Drop at 10
PSIG Setting. Capacities in 1,000 BTU/HR
3/8"
1/2"
5/8"
3/4"
7/8"
1/2"
3/4"
30
309
700
1,303
2,205
3,394
1,843
3,854
40
265
599
1,115
1,887
2,904
1,577
3,298
50
235
531
988
1,672
2,574
1,398
2,923
60
213
481
896
1,515
2,332
1,267
2,649
70
196
446
824
1,394
2,146
1,165
2,437
80
182
412
767
1,297
1,996
1,084
2,267
90
171
386
719
1,217
1,873
1,017
2,127
100
161
365
679
1,149
1,769
961
2,009
150
130
293
546
923
1,421
772
1,613
200
111
251
467
790
1,216
660
1,381
250
90
222
414
700
1,078
585
1,224
300
89
201
378
634
976
530
1,109
350
82
185
345
584
898
488
1,020
400
76
172
321
543
836
454
949
To convert to Capacities at 15 PSIG Settings -- Multiply by 1.130
To convert to Capacities at 5 PSIG Settings -- Multiply by 0.879
PIPE OR
TUBING
LENGTH,
FEET
NOMINAL PIPE SIZE,
SCHEDULE 40
TUBING SIZE, O.D., TYPE L
Sizing Between Single or Second Stage Regulator and Appliance*
Maximum Propane Capacities Listed are Based on 1/2" W.C. Pressure Drop at
11" W.C. Setting. Capacities in 1,000 BTU/HR
3/8"
1/2"
5/8"
3/4"
7/8"
1/2"
3/4"
1"
1-1/4"
1-1/2"
10
49
110
206
348
539
291
608
1,146
2,353
3,525
20
34
76
141
239
368
200
418
788
1,617
2,423
30
27
61
114
192
296
161
336
632
1,299
1,946
40
23
52
97
164
253
137
284
541
1,111
1,665
50
20
46
86
146
224
122
255
480
985
1,476
60
19
42
78
132
203
110
231
436
892
1,337
80
16
36
67
113
174
94
198
372
764
1,144
100
14
32
59
100
154
84
175
330
677
1,014
125
12
28
52
89
137
74
155
292
600
899
150
11
26
48
80
124
67
141
265
544
815
200
10
22
41
69
106
58
120
227
465
697
250
9
19
36
61
94
51
107
201
412
618
300
8
18
33
55
85
46
97
182
374
560
350
7
16
30
51
78
43
89
167
344
515
400
7
15
28
47
73
40
83
156
320
479
*DATA IN ACCORDANCE WITH NFPA PAMPHLET NO. 54
NOMINAL PIPE SIZE,
SCHEDULE 40
TUBING SIZE, O.D., TYPE L
PIPE OR
TUBING
LENGTH,
FEET
Propane Gas Pipe Sizing
ELECTRICAL WIRING
NOTE:
All wiring should be made in accordance with the
National Electrical Code.
Consult your local Power Company to determine the
availability of sufficient power to operate the unit. Check
the voltage, frequency, and phase at the power supply
to ensure it corresponds to the unit’s RATED VOLTAGE
REQUIREMENT.
In accordance with the N.E.C. or local codes, install a
branch circuit fused disconnect near the unit. Determine
wire sizes and overcurrent protection from the unit
nameplate ampacity and in accordance with the Minimum
Fuse Size or the N.E.C. The wiring should never be
sized smaller than is recommended by either of these two
sources.
Fuses smaller than that recommended on the rating plate
could result in unnecessary fuse failure or service calls.
The use of protective devices of larger size than indicated
could result in extensive damage to the equipment.
The manufacturer bears no responsibility for damage
caused to equipment as result of the use of larger than is
recommended size protective devices.
For unit protection, use a fuse or hacr circuit breaker that
is in excess of the circuit ampacity, but less than or equal
to the maximum overcurrent protection device. DO NOT
EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE
SHOWN ON UNIT DATA PLATE.
All line voltage connections must be made through
weatherproof fittings. All exterior power supply and ground
wiring must be in approved weatherproof conduit. Low
voltage wiring from the unit control panel to the thermostat
requires coded cable. See below for ground level and
rooftop wiring.
DO NOT use gas piping, or conduit as an electrical ground.
A dedicated ground wire must be run from the unit to the
electrical panel.
All units have undergone a run test prior to packaging for
shipment. This equipment has been started at minimum
rated voltage and checked for satisfactory operation. Do
not attempt to operate this unit if the voltage is not within
the minimum and maximum voltages shown on nameplate.
All exterior wiring must be within approved weatherproof
conduit. The unit must be permanently grounded in
accordance with local codes, or in absence of local codes,
with N.E.C. ANSI/ NFPA NO. 70-1984 or latest edition by
using ground lug in the control box.
Fuses or HACR type circuit breakers may be used where
codes permit.
IMPORTANT NOTE:
Some single phase units are
Содержание 209319576
Страница 34: ...34 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 35: ...35 THIS PAGE IS INTENTIONALLY LEFT BLANK...