background image

19

3. 

If the outdoor ambient is above 80°F, the unit may trip 

on its high-pressure cutout when in heating mode. The 

compressor should stop. The heating cycle must be 

thoroughly checked, so postpone the test to another 

day when conditions are more suitable but- DO NOT 

FAIL TO TEST.

4. 

If the outdoor ambient is low and the unit operates 

properly in the heating cycle, you may check the 

pressure cutout operation by blocking off the indoor 

return air until the unit trips. If unit operates properly 

in the heating cycle, raise the temperature setting 

until the heating second stage makes contact. 

Supplemental resistance heat, if installed should now 

come on. Make sure it operates properly.

NOTE:

 If outdoor thermostats are installed the outdoor 

ambient must be below the set point of these thermostats 

for the heaters to operate. It may be necessary to jumper 

these thermostats to check heater operation if outdoor 

ambient is mild.

5. 

For thermostats with emergency heat switch, The 

emergency heat switch is located at the bottom of 

the thermostat. Move the switch to emergency heat. 

The heat pump will stop, the blower will continue to 

run, the gas heating sequence will begin and the 

thermostat emergency heat light will come on.

6. 

If checking the unit in the wintertime, when the outdoor 

coil is cold enough to actuate the defrost control, 

observe at least one defrost cycle to make sure the 

unit defrosts completely.

SUGGESTED FIELD TESTING 

TROUBLESHOOTING

Testing Defrost Control

NOTE: 

PCBDM133 defrost controls have a three (3) minute 

compressor off cycle delay. 

NOTE: 

The PCBDM133 defrost controls are shipped from 

the factory with the compressor delay option selected. This 

will de-energize the compressor contactor for 30 seconds 

on defrost initiation and defrost termination. If the jumper 

is set to Normal, the compressor will continue to run during 

defrost initiation and defrost termination. The control will 

also ignore the low-pressure switch connected to R-PS1 

and PS2 for 5 minutes upon defrost initiation and 5 minutes 

after defrost termination.

To check the defrost control for proper sequencing, proceed 

as follows: With power ON; unit not running.

1. 

Jumper defrost thermostat by placing a jumper wire 

across the terminals “DFT” and “R”/” R-DFT” at defrost 

control board.

2. 

Remove jumper from timer pins and jump across test 

pins on defrost control board. 

NOTE: 

Do not use screwdriver or field supplied jumper to 

test the control.

3. 

Set thermostat to call for heating. System should go 

into defrost within 21 seconds.

4. 

 Immediately remove jumper from test pins.

5. 

Using VOM check for voltage across terminals “C & 

O”. Meter should read 24 volts.

6. 

Using VOM check for voltage across fan terminals 

DF1 and DF2 on the board. Should read line voltage 

(208-230 VAC) indicating the relay is open in the 

defrost mode.

7.  Using VOM check for voltage across “W”/”W2” & “C” 

terminals on the board. Should read 24 volts.

8.  If not as above, replace control board.

9. 

Set thermostat to off position and disconnect power. 

Remove jumper from defrost thermostat and replace 

timer jumper to the desired defrost time.

NOTE:

 Remove jumper across defrost thermostat before 

returning system to service.

PCBDM133 Defrost Control PCB

Testing Defrost Thermostat

1. 

Install a thermocouple type temperature test lead on 

the tube adjacent to the defrost control. Insulate the 

lead point of contact. 

2. 

Check the temperature at which the control closes its 

contacts by lowering the temperature of the control. It 

should close at approximately 30°F. 

3. 

Check the temperature at which the control opens its 

contacts by raising the temperature of the control. It 

should open at approximately 60°F. 

4. 

If not as above, replace control.

Temperature Rise Check 
Check the temperature rise through the unit by placing 

thermometers in supply and return air registers as close 

to the unit as possible. Thermometers must not be able to 

sample temperature directly from the unit heat exchangers, 

or false readings could be obtained.

1. 

All registers must be open; all duct dampers must be 

in their final (fully or partially open) position and the 

unit operated for 15 minutes before taking readings.

2. 

The temperature rise must be within the range 

specified on the rating plate

Содержание 209319576

Страница 1: ...the product safely and to educate the customer on its safe use 19001 Kermier Rd Waller TX 77484 www goodmanmfg com or www amana hac com 2022 Daikin Comfort Technologies Manufacturing L P IOG 3028 06 2...

Страница 2: ...t 27 Cooling heat pump Timing Chart 27 UNIT DEMENSIONS 28 WIRING DIAGRAMs 29 BLOWER PERFORMANCE DATA 31 START UP CHECKLIST 33 TO THE INSTALLER Before installing this unit please read this manual to fa...

Страница 3: ...amage personal injury or loss of life AVERTISSEMENT RISQUE D INCENDIE OU D EXPLOSION Si les consignes de s curit ne sont pas suivies la lettre cela peut entra ner la mort de graves blessures ou des do...

Страница 4: ...moyen des essais d crits ci dessus les portes les fen tres les ventilateurs les registres de foyer et tous les autres appareils de combustion aliment s au gaz doivent tre remis dans leur tat initial l...

Страница 5: ...ite please select the residential or commercial products menu and then select the submenu for the type of product to be installed such as air conditioners or heat pumps to access a list of product pag...

Страница 6: ...and industrial processes may also be sources of chlorine fluorine compounds To avoid possible illness or death of the building occupants do NOT locate outside air intake device economizer manual fres...

Страница 7: ...ry guidelines The duct work must be placed into the roof curb before mounting the package unit Curb insulation cant strips flashing and general roofing material are furnished by the contractor Roof Cu...

Страница 8: ...unit nameplate Refer to Installation Manual provided with High Altitude kit for altitude adjustments Use HA03 for installations above 2000 NOTE Up to 2 000 feet no changes are required above 2 000 fee...

Страница 9: ...ait for five minutes until all gas has been dissipated in the air Be certain there is no open flame in the vicinity during air bleeding procedure The unit is placed in operation by closing the main el...

Страница 10: ...accordance with the National Electrical Code Consult your local Power Company to determine the availability of sufficient power to operate the unit Check the voltage frequency and phase at the power...

Страница 11: ...as will not ignite until the control thermostat calls for a 2nd stage of heat Low Voltage Wiring Heat Pumps Connect 24V wires from the thermostat to the corresponding wires in the control box using No...

Страница 12: ...er to the Unit Dimension illustration in the appendix For down discharge applications the ductwork should be attached to the roof curb prior to installing the unit Ductwork dimensions are shown in the...

Страница 13: ...e The flowrator distributors also act as check valves to allow for the reverse of refrigerant flow When the heat pump is on the heating cycle the outdoor coil is functioning as an evaporator The tempe...

Страница 14: ...and energy rates Optional Outdoor Thermostat OTDFPKG 01 The outdoor thermostat is an optional accessory that can be set from 0 45 F and is set inside a birdhouse enclosure This enclosure will be moun...

Страница 15: ...econds if the SmartShift defrost technology delay feature is selected on the defrost board At this time the reversing valve shifts from heat to cool position and condenser fans shut off The inducer mo...

Страница 16: ...ed with an electronic ignition device to automatically light the main burners It also has a power vent blower to exhaust combustion products On new installations or if a major component has been repla...

Страница 17: ...mmon Terminal C White Rodgers Model 36G54 Connected to Manometer Mode 10 0 White Rodgers Model 36G54 Connected to Manometer Gas inlet pressure must be checked and adjusted in accordance to the type of...

Страница 18: ...all power when servicing the unit Heating 1 Turn the thermostat system switch to HEAT and fan switch to AUTO 2 Slowly raise the heating temperature setting When the heating first stage makes contact s...

Страница 19: ...itiation and 5 minutes after defrost termination To check the defrost control for proper sequencing proceed as follows With power ON unit not running 1 Jumper defrost thermostat by placing a jumper wi...

Страница 20: ...ower Speed Adjustments WARNING TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK REMOVE ELECTRICAL POWER FROM THE UNIT BEFORE CHANGING SPEED TAPS ON THE BLOWER MOTOR Refer to the wiring diagram...

Страница 21: ...l ing only SUBCOOLING FORMULA SATURATED LIQUID LINE TEMPERATURE LIQUID LINE TEMPERATURE EXAMPLE a Liquid Line Pressure 417 PSI b Corresponding Temp 120 F c Thermometer on Liquid line 109 F To obtain t...

Страница 22: ...o the unit 2 Place the room thermostat selector switch in the COOL position or AUTO if available and if automatic changeover from cooling to heating is desired 3 Set the room thermostat to the desired...

Страница 23: ...tomatically reset once the temperature falls below a preset level Auxiliary Secondary Limit A dirty filter excessive duct static insufficient air flow a faulty limit or a failed circulator blower can...

Страница 24: ...lations with extended periods of direct sunlight Clean Outside Coil Qualified Servicer Only The coil with the outside air flowing over it should be inspected annually and cleaned as frequently as nece...

Страница 25: ...nce each year Turn the unit on at the thermostat Wait a few minutes since any dislodged dust will alter the normal flame appearance Flames should be predominantly blue and directed into the tubes They...

Страница 26: ...RESSURE SWITCH 3 FLASHES 2 FLASHES 4 FLASHES 5 FLASHES FALSE FLAME DETECTED OPEN LIMIT SWITCH WITHOUT INDUCER ON PRESSURE SWITCH OPEN CHECK FOR SHORTS IN FLAME SENSOR WIRING NORMAL FLAME PRESENT DIAGN...

Страница 27: ...3 Flashes Pressure Switch Stuck Closed 4 Flashes Thermal Protection Device Open 5 Flashes Flame Detected with Gas Valve Closed 6 Flashes Short Cycle Compressor Delay Cooling Only 7 Flashes Limit Open...

Страница 28: ...del Unit Dimensions Inches Chassis Size Height w d a b A GPDM3 24 36 47 51 32 34 1 2 Medium A GPDM3 42 48 47 51 40 42 1 2 Large Model Duct Openings Supply Return W H W H A GPDM3 24 36 16 16 16 16 A GP...

Страница 29: ...CER L2 PARK 24VAC COM 5 4 3 2 1 1 2 3 5 6 7 8 9 EM N G L T5 T4 T3 T2 T1 C 1 2 6 4 1 FS LS M C H1 RS VM ALS PS GV IGN H C F LO HEAT 6 3 1 2 4 5 OR BL PU YL OR BR OR P1 PIN 3 P1 PIN 5 P1 PIN 9 P1 PIN 2...

Страница 30: ...ED AS AN ALTERNATE CONFIGURATION LINE VOLTAGE OPTIONAL HIGH VOLTAGE HIGH VOLTAGE FIELD WIRING LOW VOLTAGE LOW VOLTAGE BK BLACK WIRE CODE PK PINK OR ORANGE GR GREEN BR BROWN BL BLUE RD RED WH WHITE YL...

Страница 31: ...1285 331 0 4 886 173 51 1164 302 52 908 158 1118 260 1249 333 0 5 835 182 54 1131 314 53 857 166 1071 268 1211 345 0 6 781 188 58 1086 319 55 784 175 1023 275 1168 348 0 7 731 200 62 1038 319 58 732...

Страница 32: ...PDM34210041A Rise Range 35 65 E S P T1 1ST Stage Heating Speed T2 2 nd Stage Heating Speed T3 Cooling Speed T4 Cooling Speed T5 Cooling Speed CFM WATTS RISE CFM WATTS RISE CFM WATTS CFM WATTS CFM WATT...

Страница 33: ...LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Circuit Pressure Suct...

Страница 34: ...34 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Страница 35: ...35 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Страница 36: ...rademark of Maytag Corporation or its related companies and is used under license All rights reserved NOTE SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE Qualit...

Отзывы: