SELECTING INSTALLATION SITE
When selecting the installation position, pay
attention to the outer wall of the building, the units
needs to be positioned esthetical correct in the
building façade. For example: the units should be
installed at the same height as the windows and at equal distances
from windows.
The outside or room-side air inlet/outlet opening is recommended
at a minimum distance of 150 to 200 mm from adjacent façade
components and room corners!
Fox up ventilation units should be installed at a height of 1.6 to 1.8
m above the finished floor level, and the room-side air inlet/outlet
opening must not be covered by furniture or curtains.
6.
INSTALLATION OF WALL DUCT
EPS pipe wall duct
Inner ø 153, outer ø 198 mm, built-in gradient to outside (condensate drainage)
Wall ducts are available in two different lengths for Fox up ventilation units:
• Pipe length 500 mm:
Fox up shell set 500 mm, item no. 1145210 or 1145212
• Pipe length 1000 mm:
Fox up shell set 1000 mm, item no. 1145211 or 1145213
The delivery units
Fox up-GP-Design
and
Fox up-EP-Design
are supplied as standard with 500 mm wall ducts, the wall ducts are manu-
factured with a built-in gradient to the outside for condensate drainage (observe marking of outside, see fig. above).
Содержание Fox-Up
Страница 26: ...R 24 Maintenance work carriedoutby 8 MAINTENANCEREPORT FILTERCLEANING Maintenancereport...
Страница 28: ...R 26...
Страница 52: ...R 50 Wartungsarbeiten ausgef hrtdurch 8 WARTUNGSPROTOKOLL FILTERREINIGUNG Wartungsprotokoll...
Страница 54: ...R 52...
Страница 78: ...R 76 Onderhoudswerk uitgevoerddoor 8 ONDERHOUDSVERSLAG FILTERREINIGING Onderhoudsverslag...
Страница 80: ...R 78...
Страница 104: ...R 102 Travaux de maintenance Effectu spar 8 ONDERHOUDSVERSLAG FILTERREINIGING Rapportdemaintenance...
Страница 106: ...R 104...
Страница 107: ...R www glt de www ventilairgroup com...