Wireless dimming actuator, 4-gang

Short-circuit protection is not based on a conventional fuse, no metallic separation of the
operational current.

Cause 5: load failure.

Check load, replace lamp. For inductive transformers, check primary fuse and replace if
necessary.

Cause 6: mains voltage on the dimmer has failed.

Check mains voltage. After the return of the mains voltage, the dimmer executes the com-
mand that was last received.

Lamps flicker or buzz, proper dimming not possible, device buzzes

Cause: Incorrect operating mode set.

Check connected lamps. Correct the set operating mode.

LED lamp is dimly lit when dimmer is switched off

Cause: LED lamp is not optimally suited for this dimmer.

Use a compensation module, see accessories.
Use another type of LED lamp or an LED lamp of another manufacturer.

Output cannot be operated, load is off, all status LEDs are off.

Cause: Bus voltage has failed.

Check bus voltage.

Output cannot be operated, load is off, all status LEDs (4) flash 3 times each at intervals of 1
second

Cause: The configuration of the outputs was adjusted with the Mod. switch (5).

Configuration was accidentally adjusted: Check installation. Reset Mod. switch to the ori-
ginal configuration. Switch bus voltage off and on again, the dimmer assumes the setting
(see section 5.1. Mounting and Electrical Connection).
Configuration was intentionally adjusted: Check installation. Switch bus voltage off and on
again, the dimmer assumes the new setting.

8

Accessories

Power supply 12 V DC / 2 A DRA

Order no. 5319 00

Wireless receiver module

Order no. 5452 00

eNet Server

Order no. 5301 00

Compensation module LED

Order no. 2375 00

9

Warranty

The warranty is provided in accordance with statutory requirements via the specialist trade.
Please submit or send faulty devices postage paid together with an error description to your re-
sponsible salesperson (specialist trade/installation company/electrical specialist trade). They will
forward the devices to the Gira Service Center.

18 / 19

32578622

10867484

01.10.2019

Содержание 5431 00

Страница 1: ...58 2 6 may be used Fire hazard Operation exclusively with the power supplies listed under accessories These instructions are an integral part of the product and must remain with the end customer 2 Int...

Страница 2: ...on with Prog button Switching the light Press Prog button briefly The light switches on or off at the saved switch on brightness Status LED A1 A4 4 lights up output is switched on Status LED A1 A4 4 o...

Страница 3: ...DIN rail Output terminals must be at the top Connect bus line Figure 1 Connection diagram of bus line Labelling Colour Connection DC GY dark grey Power supply DC RD red Power supply Bus WH white Data...

Страница 4: ...pere circuit breaker When connecting transformers observe the data of the transformer manufac turer Our dimmers take into account the different electronic characteristics of most LED lamps found on th...

Страница 5: ...in parallel CAUTION Risk of destruction of outputs switched in parallel if the device is set incorrectly Dimmer and loads may be destroyed In the case of parallel switched outputs check the device se...

Страница 6: ...leading edge phase control or trailing edge phase control Connec tion of incandescent lamps HV halogen lamps electronic transformers with halogen or LED lamps or dimmable induct ive transformers with...

Страница 7: ...sioning described here Connecting output to radio transmitters Load is switched off Press button Prog 3 for longer than 4 seconds The status LED 4 flashes after 4 seconds The output is in programming...

Страница 8: ...econds After 20 seconds the status LED flashes faster Release Prog button and press briefly once again within 10 seconds The status LED flashes more slowly for approx 5 seconds The output is reset to...

Страница 9: ...nd HV LED typ 3 50 W Ohmic and compact fl lamp typ 3 50 W Power boosters See power booster instructions Total length power cable per channel 100 m Fitting width 144 mm 8 module Bus connection Rated vo...

Страница 10: ...er The parameter is only changed over for the display in the commissioning inter face The actual setting must be made on the device Advanced device settings Parameters Setting options Basic setting Ex...

Страница 11: ...button is pressed Switch off delay 0 s 24 h Basic setting 0 s The load switches off after a delay Repeated switch off commands restart the delay time If the load has not yet been switched off due to t...

Страница 12: ...a running run on time If the parameter is switched off then a switch off command will also switch the actuator on Only visible if a run on time was set Operating hours 0 65535 Basic setting Current va...

Страница 13: ...g for phase dimmable HV LED or compact fluores cent lamps that can be dimmed according to the lead ing edge phase control prin ciple LED trailing edge phase con trol Setting for phase dimmable HV LED...

Страница 14: ...ff If the switch off warning is act ive then during switch off the system dims to minimum brightness within 30 seconds and only then switches off If the parameter Dim down ramp is configured as longer...

Страница 15: ...he output on activating the wind alarm Deactivate wind alarm bright ness value 0 100 Basic setting 0 Defines the behaviour of the output on deactivating the wind alarm Only visible when the priority f...

Страница 16: ...t yet active as a light controller has not yet been implemen ted Hotel function On Off Basic setting Off If the hotel function is activ ated the system will dim to 20 brightness when a switch off comm...

Страница 17: ...second Cause 1 Operating mode switch 2 was set to another dimming principle The dimming principle was accidentally adjusted Reset the original dimming principle on the operating mode switch see sectio...

Страница 18: ...voltage Output cannot be operated load is off all status LEDs 4 flash 3 times each at intervals of 1 second Cause The configuration of the outputs was adjusted with the Mod switch 5 Configuration was...

Страница 19: ...GmbH Co KG Elektro Installations Systeme Industriegebiet Mermbach Dahlienstra e 42477 Radevormwald Postfach 12 20 42461 Radevormwald Deutschland Tel 49 0 21 95 602 0 Fax 49 0 21 95 602 191 www gira de...

Отзывы: