Wireless dimming actuator, 4-gang
Parameters
Setting options, Basic setting
Explanations
Maximum brightness
75...100 %
Basic setting: 100 %
Specifies the maximum set-
table brightness.
Note: If parameters or scene
values are set to a level higher
than the maximum brightness,
then the system will dim to
maximum brightness.
Dimming adjustment time
1…60 s
Basic setting: 4 s
Time from minimum bright-
ness until reaching maximum
brightness (dimming speed).
Switch-on delay
0 s … 24 h
Basic setting: 0 s
The load switches on after a
delay. Repeated switch-on
commands restart the delay
time. If the load has not yet
been switched on due to the
delay when a switch-off com-
mand comes, then the load
will remain off.
Note: The set time apply to
operation using radio transmit-
ters. The device is switched
immediately when the Prog
button is pressed.
Switch-off delay
0 s … 24 h
Basic setting: 0 s
The load switches off after a
delay. Repeated switch-off
commands restart the delay
time. If the load has not yet
been switched off due to the
delay when a switch-on com-
mand comes, then the load
will remain on.
Note: The set time apply to
operation using radio transmit-
ters. The device is switched
immediately when the Prog
button is pressed.
Dim up ramp
0 s … 24 h
Basic setting: 0 s
Time between switch-on and
reaching switch-on brightness.
The light is switched on at
minimum brightness and then
dimmed to the switch-on
brightness.
Only applies to switch-on with
transmitters (short operation).
If scenes are recalled or
switching uses logic modules,
the switch-on brightness is ap-
proached using so-called soft
dimming (not configurable).
Dim down ramp
0 s … 24 h
Basic setting: 0 s
Time until reaching minimum
brightness. The light is
dimmed to minimum bright-
ness and then switched off.
Only applies to switch-off with
11 / 19
32578622
10867484