Wireless dimming actuator, 4-gang
Parameters
Setting options, Basic setting
Explanations
Brightness on voltage return
0...100 %
Basic setting: 100 %
Brightness value, set by the
output after voltage return
(mains voltage). The para-
meter "Behaviour after voltage
return" must be set to "Con-
figured position".
Note: If the value is above the
set maximum brightness or
below the minimum bright-
ness, then the system will
switch to the appropriate limit
value.
Behaviour after the end of the
disabling function
On
Off
no change
Last value
Basic setting: No change
Behaviour of the output when
a block is removed.
Manual saving of the scene
values
On, Off
Basic setting: On
Disables the saving of the cur-
rent brightness value as scene
value in an actuator for a com-
mand via a transmitter.
Switch-off warning
On, Off
Basic setting: Off
If the switch-off warning is act-
ive, then, during switch-off, the
system dims to minimum
brightness within 30 seconds
and only then switches off. If
the parameter "Dim down
ramp" is configured as longer
than 30 s, then the length of
the dim down ramp is applied.
If, during the dim down opera-
tion, another command is
given, e.g. switch on or scene
recall, then the switch-off
warning stops and the com-
mand is executed. A switch-off
command restarts the time for
the switch-off warning.
Note: The set time apply to
operation using radio transmit-
ters. The device is switched
immediately when the Prog
button is pressed.
Priority, lock-out protection
0...4
Basic setting: 1
Specifies the priority for recall-
ing and removing a scene of
type Lock-out protection for
the channel.
Note: 1 is the highest priority
and 4 the lowest. 0 means no
priority.
Activate lock-out protection
brightness value
0…100 %
Basic setting: 0 %
Defines the behaviour of the
output on activating the lock-
out protection.