Wireless dimming actuator, 4-gang

Parameters

Setting options, Basic setting

Explanations

transmitters (short operation).
If scenes are recalled or
switching uses logic modules,
the system switches off dir-
ectly.

Run-on time

0 s … 24 h
Basic setting: 0 s

As soon as a run-on time has
been entered, the actuator will
no longer remain on perman-
ently, but only for the length of
the run-on time. The run-on
time is restarted if actuation is
repeated. This parameter is
directly connected to the
"Manual switch-off of run-on
time" parameter. 
Note: The set time apply to
operation using radio transmit-
ters. The device is switched
immediately when the Prog
button is pressed.

Manual switch-off of the run-
on time

On, Off
Basic setting: Off

Allows manual switch-off of a
running run-on time. If the
parameter is switched off,
then a switch-off command
will also switch the actuator
on. Only visible if a run-on
time was set.

Operating hours

0...65535
Basic setting: Current value

The time is counted during
which the load is physically
switched on.
This parameter can be reset
to "0", for example after ex-
changing the load.
The Reset button is used to
reset the counter to "0". The
device must be programmed
to apply the change.

Extended channel settings

Parameters

Setting options, Basic setting

Explanations

Operating mode

Normal operation
Continuous on
Continuous off
Basic setting: Normal Opera-
tion

see Device and channels

Manual commissioning

On, Off
Basic setting: On

Blocks manual commissioning
for the device channel. 
Note: In the "Off" setting, the
device cannot be reset to the
factory setting.

Local Operation

On, Off
Basic setting: On

Blocks the output for operation
using the Prog button.

12 / 19

32578622

10867484

01.10.2019

Содержание 5431 00

Страница 1: ...58 2 6 may be used Fire hazard Operation exclusively with the power supplies listed under accessories These instructions are an integral part of the product and must remain with the end customer 2 Int...

Страница 2: ...on with Prog button Switching the light Press Prog button briefly The light switches on or off at the saved switch on brightness Status LED A1 A4 4 lights up output is switched on Status LED A1 A4 4 o...

Страница 3: ...DIN rail Output terminals must be at the top Connect bus line Figure 1 Connection diagram of bus line Labelling Colour Connection DC GY dark grey Power supply DC RD red Power supply Bus WH white Data...

Страница 4: ...pere circuit breaker When connecting transformers observe the data of the transformer manufac turer Our dimmers take into account the different electronic characteristics of most LED lamps found on th...

Страница 5: ...in parallel CAUTION Risk of destruction of outputs switched in parallel if the device is set incorrectly Dimmer and loads may be destroyed In the case of parallel switched outputs check the device se...

Страница 6: ...leading edge phase control or trailing edge phase control Connec tion of incandescent lamps HV halogen lamps electronic transformers with halogen or LED lamps or dimmable induct ive transformers with...

Страница 7: ...sioning described here Connecting output to radio transmitters Load is switched off Press button Prog 3 for longer than 4 seconds The status LED 4 flashes after 4 seconds The output is in programming...

Страница 8: ...econds After 20 seconds the status LED flashes faster Release Prog button and press briefly once again within 10 seconds The status LED flashes more slowly for approx 5 seconds The output is reset to...

Страница 9: ...nd HV LED typ 3 50 W Ohmic and compact fl lamp typ 3 50 W Power boosters See power booster instructions Total length power cable per channel 100 m Fitting width 144 mm 8 module Bus connection Rated vo...

Страница 10: ...er The parameter is only changed over for the display in the commissioning inter face The actual setting must be made on the device Advanced device settings Parameters Setting options Basic setting Ex...

Страница 11: ...button is pressed Switch off delay 0 s 24 h Basic setting 0 s The load switches off after a delay Repeated switch off commands restart the delay time If the load has not yet been switched off due to t...

Страница 12: ...a running run on time If the parameter is switched off then a switch off command will also switch the actuator on Only visible if a run on time was set Operating hours 0 65535 Basic setting Current va...

Страница 13: ...g for phase dimmable HV LED or compact fluores cent lamps that can be dimmed according to the lead ing edge phase control prin ciple LED trailing edge phase con trol Setting for phase dimmable HV LED...

Страница 14: ...ff If the switch off warning is act ive then during switch off the system dims to minimum brightness within 30 seconds and only then switches off If the parameter Dim down ramp is configured as longer...

Страница 15: ...he output on activating the wind alarm Deactivate wind alarm bright ness value 0 100 Basic setting 0 Defines the behaviour of the output on deactivating the wind alarm Only visible when the priority f...

Страница 16: ...t yet active as a light controller has not yet been implemen ted Hotel function On Off Basic setting Off If the hotel function is activ ated the system will dim to 20 brightness when a switch off comm...

Страница 17: ...second Cause 1 Operating mode switch 2 was set to another dimming principle The dimming principle was accidentally adjusted Reset the original dimming principle on the operating mode switch see sectio...

Страница 18: ...voltage Output cannot be operated load is off all status LEDs 4 flash 3 times each at intervals of 1 second Cause The configuration of the outputs was adjusted with the Mod switch 5 Configuration was...

Страница 19: ...GmbH Co KG Elektro Installations Systeme Industriegebiet Mermbach Dahlienstra e 42477 Radevormwald Postfach 12 20 42461 Radevormwald Deutschland Tel 49 0 21 95 602 0 Fax 49 0 21 95 602 191 www gira de...

Отзывы: