5
Model: GVH-C & GVH-F
Installation
2.
Installation
This section summarizes procedures necessary for proper equipment installation. To help avoid personal injury or
equipment damage, be sure to adhere to all of these recommended procedures.
Installation expense (materials & labor) is completely the Purchaser’s responsibility. Generally, it is advisable to
engage the services of a professional commercial kitchen equipment specialist, a licensed electrician, and/or a
qualified HVAC contractor to assist with the details of installation. Call
Giles Technical Suppor
t @ 800.554.4537, if
assistance is required.
The hood is factory assembled with piping, conduit, nozzles, detector link brackets, and exhaust fire damper. Upon
installation It must be connected to a,
customer provided,
fire suppression system specified by the UL listing, which
is the
Ansul® R-102 Wet Chemical system
.
The system. field installation/set-up, testing and final commissioning
shall be provided by the purchaser, and must be supplied by an authorized
Ansul Distributor/Dealer
.
1. No minimum clearance (0”) is required between the top of air diverter and ceiling, but it is adviseable to
provide some clearance (3 to 6”) to allow make moving the unit easier should the need arise. Area around the
diverter openings must not be obstructed.
2. The
GVH-C
hood is designed to sit on a counter-top space. Ensure that the intended site is structurally sound
and capable of supporting the hood’s weight plus that of appliances to be placed under it. See
Section 1.04.4,
Hood Weight
.
2.01
Location
IMPORTANT!!
Before installing the GILES Recirculating/Ventless Hood system ensure that, A). all necessary approvals from local
code authorities have been obtained, B). the appliances to be used with the hood are all within the hood’s listing
limitations, as outlined in
Section 2.04
, and C). the installation site complies with the specific requirements and
limitations outlined in the
GFSE Recirculating/Ventless Hood Approval Letter (HAL)
. The
HAL
is available for
review or download at www.gfse.com under the
SUPPORT
tab in
VENTLESS DOCUMENTS
.
To ensure satisfactory hood performance after installation, the intended site MUST comply with minimum
requirements for kitchen size (>600 sq ft), ceiling height, fresh outdoor air make-up, supplemental exhaust
ventilation, clearances, etc. as stipulated in Giles’ Hood Approval Letter.
•
MAXIMUM of 1 hood per 600 sq ft of commercial kitchen space.
•
Fresh outside air make-up must be equal to a MINIMUM of fifteen (15) complete room air exchanges per hour.
•
Giles makes no representations as to proper design or layout of an establishment in which the ventless hood
will be used. Further, Giles does not perform site inspections prior to installation of any of its units.
• When operating, the hood produces a sound level of approximately
65 dB
.
•
DO NOT ALTER, ADD ATTACHMENTS OR OTHERWISE MODIFY THIS EQUIPMENT.
•
Failure to comply with installation requirements as specified by the Giles Hood Approval Letter will void the
factory warranty.
Continued on Next Page
Содержание GVH-C
Страница 2: ......
Страница 4: ......
Страница 12: ...2 Model GVH C GVH F Introduction 1 04 Specifications 1 04 1 Overall Dimensions GVH C Counter Top Version ...
Страница 13: ...3 Model GVH C GVH F Introduction 1 04 1 Overall Dimensions GVH F Floor Stand Version ...
Страница 17: ...7 Model GVH C GVH F Installation 2 03 Clearance to Combustibles 2 03 1 GVH Counter Top Hood GVH C ...
Страница 18: ...8 Model GVH C GVH F Installation 2 03 2 GVH Floor Stand Hood GVH F ...
Страница 34: ...Model GVH C GVH F Overview 24 1 5 2 4 3 8 9 3 01 Control Panel 6 7 ...
Страница 36: ...26 Model GVH C GVH F Overview Optional Not Seen 3 02 Hood Front Filter Chamber 1 5 2 6 7 4 3 8 ...
Страница 49: ...39 Model GVH C GVH F Operation Filter Maintenance ...
Страница 56: ...46 Model GVH C GVH F Troubleshooting ...
Страница 60: ...50 Model GVH C GVH F Parts List Hidden Optional 7 03 Hood Front Filter Compartment 9 2 1 8 3 5 6 4 7 11 10 ...
Страница 64: ...54 Parts List Model GVH C GVH F 7 05 Under Hood Components 2 1 4 3 ...
Страница 66: ...56 Model GVH C GVH F Parts List ...
Страница 67: ......