16
Model: GVH-C & GVH-F
Installation
HOOD POWER
APPLIANCE POWER AND
CONTACTOR COIL SIGNAL
TO SHUNT TRIP DEVICE
G
G A1 A2 A3
L1 L2 L3
H
1
H
2
C
1
LN
C
2
AN
G
C
3
G
H
USE LIQUID-TIGHT
CONDUIT AND
FITTINGS WHEN
RECEPTACLE IS NOT
INSTALLED
120V to 480V APPLIANCE POWER SEPARATE FROM 208-240 V HOOD POWER (USING REMOTE SHUNT TRIP
CONTACTOR SUPPLIED BY LICENSED ELECTRICIAN). Contactor must be a UL Listed, definite purpose, AC resistive,
air heating type, suitable for the appliance load. The Installation and connections shall be in accordance with the
National Electric Code NFPA 70.
2.05.2.4
120 to 480V Appliance Power, Separate Circuit from 208-240V Hood Power
Using Remote Shunt Trip Device
Содержание GVH-C
Страница 2: ......
Страница 4: ......
Страница 12: ...2 Model GVH C GVH F Introduction 1 04 Specifications 1 04 1 Overall Dimensions GVH C Counter Top Version ...
Страница 13: ...3 Model GVH C GVH F Introduction 1 04 1 Overall Dimensions GVH F Floor Stand Version ...
Страница 17: ...7 Model GVH C GVH F Installation 2 03 Clearance to Combustibles 2 03 1 GVH Counter Top Hood GVH C ...
Страница 18: ...8 Model GVH C GVH F Installation 2 03 2 GVH Floor Stand Hood GVH F ...
Страница 34: ...Model GVH C GVH F Overview 24 1 5 2 4 3 8 9 3 01 Control Panel 6 7 ...
Страница 36: ...26 Model GVH C GVH F Overview Optional Not Seen 3 02 Hood Front Filter Chamber 1 5 2 6 7 4 3 8 ...
Страница 49: ...39 Model GVH C GVH F Operation Filter Maintenance ...
Страница 56: ...46 Model GVH C GVH F Troubleshooting ...
Страница 60: ...50 Model GVH C GVH F Parts List Hidden Optional 7 03 Hood Front Filter Compartment 9 2 1 8 3 5 6 4 7 11 10 ...
Страница 64: ...54 Parts List Model GVH C GVH F 7 05 Under Hood Components 2 1 4 3 ...
Страница 66: ...56 Model GVH C GVH F Parts List ...
Страница 67: ......