Model: GVH-C & GVH-F
Operation & Filter Maintenance
If the
baffle filter
or
charcoal filter
become clogged, or there are other restrictions that reduce airflow through the
hood to a level below the minimum required for effective capture of cooking vapors, a
steady tone alarm
sounds
and the
[CHARCOAL OR BAFFLE FILTER CLOGGED]
light will turn
ON
. The
amber
[APPLIANCE POWERED]
light turns
OFF
and power to the under-hood
appliances turns
OFF
until the condition is corrected.
• Hood fan continues running.
• Clean the baffle filter; see
Section 4.03.1, Baffle Filter Cleaning.
• Replace charcoal filter with fresh new filter;
4.03.3, Charcoal Filter
Maintenance
.
• Inspect the hood plenum to ensure there are no other obstructions.
• Check the hood exhaust outlet and be sure that nothing is obstructing
exhaust airflow.
4.02.4.2
Charcoal or Baffle Filter Clogged
Three LED indicator lights on the control panel display the operational status of the E.A.C. filter system.
[ON]
Indicates that the E.A.C. cell is installed, powered and operating. Only light
ON
when the system is operating normally.
[WASH]
This light turns
ON
to indicate:
• Filter cell is not installed or is mis-aligned.
• Collection fins contain excessive amount of captured grease residue.
• Poor contact with filter cell contact plate inside hood.
• Ionizer wire, or wires, completely missing.
When
[WASH]
light is
ON
, an alarm condition exists and air cleaning is
not occurring. After approximately two (2) minutes, an
intermittent
(beeping) alarm tone
will begin sounding and shortly thereafter, power
to the under-hood appliances is shutdown and
[APPLIANCE POWERED]
light turns
OFF
.
[WASH} light is NOT intented to be a signal for routine cleaning of the cell, DO NOT use as such.
Typically, the collection cell must be cleaned DAILY to ensure optimum performance. See Section 4.03.2,
EAC Filter Cell Cleaning
.
[CHECK]
This light will turn
ON
to indicate:
• Ionizer wires are broken and shorting out against the cell frame.
• Cell is damaged and is shorting out to ground.
• Collection fins are shorting out because excessive moisture has formed on them.
When
[CHECK]
light is
ON,
the hood will continue to run and the under-hood appliances remain powered,
however the system is no longer operating to clean the air .
DO NOT CONTINUE OPERATIONS WHEN
THIS CONDITION EXIST ... STOP AND INSPECT!
The following actions may clear the alarm condition:
1. Turn
OFF
hood
Power Switch
.
2. Remove the E.A.C. cell and clean as described in
Section 4.03.2
.
4.02.4.3
E.A.C. Filter Status & Alarm
Continued on Next Page
Содержание GVH-C
Страница 2: ......
Страница 4: ......
Страница 12: ...2 Model GVH C GVH F Introduction 1 04 Specifications 1 04 1 Overall Dimensions GVH C Counter Top Version ...
Страница 13: ...3 Model GVH C GVH F Introduction 1 04 1 Overall Dimensions GVH F Floor Stand Version ...
Страница 17: ...7 Model GVH C GVH F Installation 2 03 Clearance to Combustibles 2 03 1 GVH Counter Top Hood GVH C ...
Страница 18: ...8 Model GVH C GVH F Installation 2 03 2 GVH Floor Stand Hood GVH F ...
Страница 34: ...Model GVH C GVH F Overview 24 1 5 2 4 3 8 9 3 01 Control Panel 6 7 ...
Страница 36: ...26 Model GVH C GVH F Overview Optional Not Seen 3 02 Hood Front Filter Chamber 1 5 2 6 7 4 3 8 ...
Страница 49: ...39 Model GVH C GVH F Operation Filter Maintenance ...
Страница 56: ...46 Model GVH C GVH F Troubleshooting ...
Страница 60: ...50 Model GVH C GVH F Parts List Hidden Optional 7 03 Hood Front Filter Compartment 9 2 1 8 3 5 6 4 7 11 10 ...
Страница 64: ...54 Parts List Model GVH C GVH F 7 05 Under Hood Components 2 1 4 3 ...
Страница 66: ...56 Model GVH C GVH F Parts List ...
Страница 67: ......