HD50CR
- 34 -
V1.0
F805: sending interval of the of data via e-mail {Real time / 15 min / 30 min / 1 hour /
2 hours / 4 hours / 8 hours / 12 hours / 1 day / 2 days / 4 days / 1 week,
default=15 min}
F806: format of the data sent via e-mail {LOG=format for the database and displaying
with the Monitor function of the web server, CSV=format for Excel
®
, de-
fault=LOG}
F807: enable the sending of data via FTP {On/OFF, default=OFF}
F808: sending interval of the of data via FTP {Real time / 15 min / 30 min / 1 hour / 2
hours / 4 hours / 8 hours / 12 hours / 1 day / 2 days / 4 days / 1 week, de-
fault=15 min}
F809: format of the data sent via FTP {LOG=format for the database and displaying
with the Monitor function of the web server, CSV=format for Excel
®
, de-
fault=LOG}
F810: enable the sending of data to the Cloud {On/OFF, default=OFF}
F811: sending interval of the of data to the Cloud {Real time / 15 min / 30 min / 1 hour
/ 2 hours / 4 hours / 8 hours / 12 hours / 1 day / 2 days / 4 days / 1 week,
default=15 min}
F812: enable the sending of data to the PC in which the server function of the
HDServer1 software is active {On/OFF, default=OFF}
F813: sending interval of the of data to the PC in which the server function of the
HDServer1 software is active {Real time / 15 min / 30 min / 1 hour / 2
hours / 4 hours / 8 hours / 12 hours / 1 day / 2 days / 4 days / 1 week, de-
fault=15 min}
F900 submenu (MODBUS MENU)
Modbus settings.
F901: Modbus address {1…247, default=1}
F902: RS485 baud rate in kbps {9.6 / 19.2 / 38.4 / 57.6 / 115.2, default=19.2}
F903: RS485 communication mode {8N1 / 8N2 / 8E1 / 8E2 / 8O1 / 8O2, default=8E1}
F904: waiting of 3.5 characters after transmission with Modbus protocol {nO=violate
protocol and go in receiving mode right after transmission / YES=respect pro-
tocol and wait 3.5 characters after transmission, default=nO}
F905: enabling of the password for changing the configuration via Modbus {On/OFF,
default=OFF}
FA00 submenu (CLK MENU)
Clock settings.
FA01: year
FA02: month
FA03: day
FA04: hour
FA05: minutes
FA06: enabling of the automatic synchronization of the internal clock with a reference
server {On/OFF, default=OFF}
FA07: time zone {default=0}