HD50CR
- 38 -
V1.0
Address Type
Coil description
62
b
Enabling of the buzzer “Latch” function for the quantity #4:
0= disabled, 1=enabled
63
b
Enabling of the buzzer “Latch” function for the quantity #5:
0= disabled, 1=enabled
64
b
Enabling of the buzzer “Latch” function for the quantity #6:
0= disabled, 1=enabled
65
b
Enabling of the buzzer “Latch” function for the quantity #7:
0= disabled, 1=enabled
71
b
Type of calibration used: 0=factory, 1=user
72
b
Set 1 to carry out the zero calibration of the differential pressure. Bit ze-
roing is automatic.
73
b
Enabling of the auto-calibration of the zero of the differential pressure:
0=disabled, 1=enabled
Input Registers - Read-only parameters
Address Type
Input Register description
Measured values and status of measurement alarms
2
SW R
ELATIVE
H
UMIDITY
in % (x10).
3
B
Relative humidity alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
4
SW D
EW
P
OINT
in the set measurement unit (x10).
5
B
Dew Point alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
10
SW A
BSOLUTE
H
UMIDITY
in g/m
3
(x10).
11
B
Absolute humidity alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
12
SW W
ET
B
ULB TEMPERATURE
in the set measurement unit (x10).
13
B
Wet bulb temperature alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
84
SW D
IFFERENTIAL
P
RESSURE
in the set measurement unit (the multiplier de-
pends on the set unit).
85
B
Differential pressure alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
174
SW T
EMPERATURE
with 4-wire Pt100 sensor of the T/RH combined probe in the
set measurement unit (x100).
175
B
Alarm for temperature with 4-wire Pt100 sensor of the T/RH combined
probe: 0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
Measurement units and resolution
5004
W
D
EW POINT
measurement unit: 0=°C, 1=°F.
5012
W
W
ET BULB TEMPERATURE
measurement unit: 0=°C, 1=°F.
5084
W
D
IFFERENTIAL PRESSURE
measurement unit: see the table of indexes
5085
SW D
IFFERENTIAL PRESSURE
resolution:
…, -2=100, -1=10, 0=1, 1=0.1, 2=0.01, …
5174
W
Unit of measurement for
TEMPERATURE
with 4-wire Pt100 sensor of the
T/RH combined probe: 0=°C, 1=°F.
Содержание Delta OHM HD50CR
Страница 44: ...HD50CR 44 V1 0 Dimensions mm...
Страница 49: ...HD50CR 49 V1 0 NOTES...
Страница 50: ...HD50CR 50 V1 0 NOTES...
Страница 51: ......