F700 submenu (AN OUT MENU)
Setting of the analog outputs.
F710: analog output 1
F711: 0-20 mA / 4-20 mA selection for the current output {default=4-20 mA}
F712: 0-5 V / 0-10 V selection for the voltage output {default=0-10 V}
F713: value of the quantity associated with the analog output corresponding to 0/4
mA and 0 V {default=-125 Pa}
F714: value of the quantity associated with the analog output corresponding to 20
mA and 5/10 V {d125 Pa}
F715: analog output test mode. The current output goes to the value entered. Set
OFF to exit the test mode.
F716: analog output test mode. The voltage output goes to the value entered. Set
OFF to exit the test mode.
F720: analog output 2
F721: 0-20 mA / 4-20 mA selection for the current output {default=4-20 mA}
F722: 0-5 V / 0-10 V selection for the voltage output {default=0-10 V}
F723: value of the quantity associated with the analog output corresponding to 0/4
mA and 0 V {default=0.0 °C}
F724: value of the quantity associated with the analog output corresponding to 20
mA and 5/10 V {default=100.0 °C}
F725: analog output test mode. The current output goes to the value entered. Set
OFF to exit the test mode.
F726: analog output test mode. The voltage output goes to the value entered. Set
OFF to exit the test mode.
F730: analog output 3
F731: 0-20 mA / 4-20 mA selection for the current output {default=4-20 mA}
F732: 0-5 V / 0-10 V selection for the voltage output {default=0-10 V}
F733: value of the quantity associated with the analog output corresponding to 0/4
mA and 0 V {default=0.0 %RH}
F734: value of the quantity associated with the analog output corresponding to 20
mA and 5/10 V {default=100.0 %RH}
F735: analog output test mode. The current output goes to the value entered. Set
OFF to exit the test mode.
F736: analog output test mode. The voltage output goes to the value entered. Set
OFF to exit the test mode.
F800 submenu (LAN MENU)
LAN/WLAN settings.
F801: WLAN/LAN module reset {YES/nO}. if the WLAN/LAN module configura-
tion is changed, the new settings are not immediately activated, but
only after the reset of the module. To immediately activate the new
settings, set this parameter to YES.
F802: set the default configuration of the WLAN/LAN module {YES/nO, default=nO}
F803: enable the sending of alarm e-mail {On/OFF, default=On}
F804: enable the sending of data via e-mail {On/OFF, default=OFF}