background image

 

HD50CR

 

-   3   - 

V1.0

 

1

 

INTRODUCTION 

HD50CR is a relative or differential low pressure transmitter and data logger designed 

for wall flush-mounting. Measuring range ±125 Pa. 
A silicon piezoresistive sensor with high accuracy and temperature compensation is 

used, which allows excellent linearity, repeatability and stability over the time. The 

auto-zeroing feature allows stable measurements over the time without the need to 

recalibrate. 
An input for an optional relative humidity and temperature combined probe is provid-

ed. The absolute humidity, the Dew Point and the wet bulb temperature are calculat-

ed. 
Three  0…5/10 V and  0/4…20 mA analog outputs and a digital RS485 output with 

“Slave” Modbus-RTU protocol for connecting the instrument to a network of sensors 

are available. 
The electroluminescent display has an inattinic red protection. The front keyboard al-

lows scrolling the real time measurements and configuring the instrument. 
The instrument can be connected to a local network via the Ethernet interface (op-

tionally Wi-Fi, on request). The simultaneous operation of two communication proto-

cols (proprietary and Modbus TCP/IP) is possible. The instrument manages up to 10 

“TCP/IP Client” simultaneously. If the local network is connected to Internet, the data 

can be regularly sent to an FTP address, to the Cloud and via e-mail
Equipped with a USB port with mini-USB connector for the direct connection to a PC. 
For each detected quantity, two alarm thresholds can be set by the user. Exceeding a 

threshold is signaled acoustically, by means of the internal buzzer, visually, by lighting 

the alarm LEDs on the front panel (only for the three measurements associated with 

the analog outputs), and remotely, by sending alarm e-mails. An alarm hysteresis and 

a delay in the generation of the alarm can be configured for each detected quantity. 
Thanks to the integrated web server, you can configure the instrument and view the 

real time measurements from any PC, tablet or smartphone connected to the same lo-

cal network of the instrument by simply using a web browser. 
The PC software HD35AP-S allows configuring the instrument, viewing the real time 

measurements,  downloading  and viewing the data into  a database.  The  HD35AP-S 

software allows connecting one instrument at a time. If there are several HD50CR in-

struments in the local network, the PC software HDServer1 allows detecting automati-

cally all the instruments connected to the network and the simultaneous connection to 

all the instruments, entering the data received by the instruments  into a database, 

viewing the data in the database and configuring some basic parameters of the devic-

es (alarms, logging interval, …). The HD35AP-CFR21 software option (available with 

both HD35AP-S and HDServer1) allows the protection of recorded data and configura-

tion in response to FDA 21 CFR part 11 recommendations. 
The internal clock can be regularly synchronized with a NIST reference server. 
Brushed stainless steel front panel. 
The instrument is supplied factory calibrated. 

Содержание Delta OHM HD50CR

Страница 1: ...Operating manual Low pressure transmitter data logger HD50CR Keep for future reference www deltaohm com English Companies Brands of GHM...

Страница 2: ...NETWORK 8 4 1 HD35AP CFR21 SOFTWARE OPTION 8 5 ALARMS 10 6 STATISTICAL FUNCTIONS 12 7 CALIBRATION 13 8 WEB SERVER 14 8 1 SETTINGS MENU 15 8 2 MONITOR MENU 20 8 3 CONNECTIVITY MENU 22 8 4 FILES MENU 29...

Страница 3: ...a PC For each detected quantity two alarm thresholds can be set by the user Exceeding a threshold is signaled acoustically by means of the internal buzzer visually by lighting the alarm LEDs on the fr...

Страница 4: ...l functions MIN MAX AVG In menu decreases the displayed value or move to the previous parameter Enters the menu In menu confirms the displayed value Cancel the operation or goes back to the previous l...

Страница 5: ...drilling pattern shown below then wall mount the instrument by using the 4 holes on the front panel The connections on the upper part of the housing are as follows ETHERNET port Pressure input Pressur...

Страница 6: ...channel 1 2 or 3 are associated with the same quantity Collegamento RS485 Connect any combined temperature and relative humidity probe to the 8 pole M12 connector on the bottom of the housing 3 1 CONF...

Страница 7: ...rotocol and the RS485 connection for the Modbus RTU protocol or Ethernet connection for the Modbus TCP IP protocol see chapter 10 For the use of the HD35AP S and HDServer1 application softwares see th...

Страница 8: ...se management system included in the HD35AP S soft ware package must be installed Thanks to the availability of two TCP IP listening ports each of which can operate with proprietary for the connection...

Страница 9: ...can be defined The HD35AP CFR21 option works with USB hardware key to be connected to any PC con nected to the same local network of the PC in which the basic software is installed Note if the HD35AP...

Страница 10: ...e hysteresis is in percentage 0 100 of the difference between the two alarm thresholds For example if the hysteresis is 2 default value the lower threshold is 10 C and the upper threshold is 60 C the...

Страница 11: ...encing of the buzzer with Latch option disabled The following example shows the silencing of the buzzer with Latch option enabled off off on on off Hysteresis Hysteresis Upper threshold Lower threshol...

Страница 12: ...alue of the displayed quantity To scroll the maximum values of the various quantities use the key By pressing FUNC again the instrument shows the minimum value of the dis played quantity By pressing F...

Страница 13: ...connect the front inputs to a low differential pressure generator The differential pressure zero calibration is also possible via the Modbus Coil register with address 72 see chapter 10 At the end of...

Страница 14: ...TION Modbus parameters user code and belonging group MEASURES Selection of the quantities to be displayed LOGGING Logging settings ALARMS Setting of the alarms UNITS Units of measurement CHANNELS Sele...

Страница 15: ...ion status o Modbus address firmware version o logging interval o measurement interval o calibration date CONFIGURATION panel Setting of Modbus parameters user code and belonging group defining a grou...

Страница 16: ...of o Logging interval o Measuring interval o Logging status active or not active o Memory management mode when it is full cyclic overwriting or stop logging Select the quantities to be displayed cycl...

Страница 17: ...e event of an alarm of the alarm can be configured Logging interval Measuring interval Press Apply to send the changes to the instrument Cyclic cyclic overwriting of the memory NO Cyclic logging is st...

Страница 18: ...yed in real time with the Monitor function and in what order The panel has two lists the quantities available to the left and the quantities to be displayed to the right The quantities are displayed i...

Страница 19: ...e first three quantities of the list of se lected quantities in the CHANNELS panel Press Apply to send the changes to the instrument Button to refresh the settings Quantity value corresponding to 0 4...

Страница 20: ...rted in CSV format MEASURES panel Displays the current value of the quantities only those selected for logging The measurements in alarm are highlighted with a red background The L and H sym bols indi...

Страница 21: ...nual scroll interval X axis manual scroll buttons Pause Start automatic scroll Displays the data in the From To interval Single all quantities on the same graph Multiple a graph for each quantity Y ax...

Страница 22: ...mber of an instrument with IP address 192 168 1 2 in the web browser you need to type 192 168 1 2 40 The WLAN LAN module has two TCP IP ports For each of the two ports set the fol lowing o the protoco...

Страница 23: ...in the address automatically dynamic IP address via DHCP protocol Dynamic Host Configuration Protocol Note it is suggested to use a static IP for the communication with the HD35AP S soft ware with a w...

Страница 24: ...nter the user name of the account o Account Password enter the password of the account o SMTP Server Address enter the outgoing mail server name supplied by your e mail service provider o SMTP Server...

Страница 25: ...ed in a determined interval of time indicate the interval starting instant in the Start Date Time field and the interval ending instant in the Stop Date Time field then press Execute Note sending e ma...

Страница 26: ...hour 2 hours 4 hours 8 hours 12 hours 1 day 2 days 4 days 1 week o In the Data Mode field select the format of the data sent via FTP LOG format for the database and displaying with the Monitor functi...

Страница 27: ...field The available options are Real Time 15 min default 30 min 1 hour 2 hours 4 hours 8 hours 12 hours 1 day 2 days 4 days 1 week o To require the sending to the Cloud of all the data memorized subse...

Страница 28: ...Time Upload field and press Execute o To require the sending to the HDServer1 software of all data memorized in a de termined interval of time indicate the interval starting instant in the Start Date...

Страница 29: ...the files to be imported multiple files can be se lected The instrument corresponding to the imported files appear in the Device list select an instrument and press View data to display the data CHAR...

Страница 30: ...he password will blink Set the remaining digits in the same way 3 Using keys select a main category in the menu and confirm MENU key 4 If the selected main category has a submenu select the desired it...

Страница 31: ...ndex CH1 CH6 default CH1 Set a measurement to OFF to exclude it F300 submenu DISP LOOP VIEW Selection of the quantities to be displayed cyclically Note in the F300 submenu only the quantities to be de...

Страница 32: ...ction enabling On OFF default OFF F469 buzzer silencing time in minutes 0 1080 default 0 F500 submenu UNIT MEAS MENU Units of measurement F501 temperature unit of measurement C F default C F502 differ...

Страница 33: ...test mode The current output goes to the value entered Set OFF to exit the test mode F726 analog output test mode The voltage output goes to the value entered Set OFF to exit the test mode F730 analo...

Страница 34: ...default 15 min F812 enable the sending of data to the PC in which the server function of the HDServer1 software is active On OFF default OFF F813 sending interval of the of data to the PC in which the...

Страница 35: ...d is locked keep the MENU key pressed for 7 seconds to unlock it FC00 submenu CAL MENU Calibration settings FC03 relative humidity sensor calibration at 75 RH FC04 relative humidity sensor calibration...

Страница 36: ...value expressed as an integer e g if the content of the reg ister is 500 the value is to be intended as 5 00 The commands for requesting units of measurement return an index according to the correspon...

Страница 37: ...bled 1 enabled 35 b Enabling of the upper alarm threshold for the quantity 1 0 disabled 1 enabled 36 b Enabling of the upper alarm threshold for the quantity 2 0 disabled 1 enabled 37 b Enabling of th...

Страница 38: ...t alarm 0 OFF 1 lower threshold alarm 2 higher threshold alarm 10 SW ABSOLUTE HUMIDITY in g m3 x10 11 B Absolute humidity alarm 0 OFF 1 lower threshold alarm 2 higher threshold alarm 12 SW WET BULB TE...

Страница 39: ...t measurement unit x10 13 SW Wet bulb temperature higher alarm threshold in the set measurement unit x10 84 SW DIFFERENTIAL PRESSURE lower alarm threshold in the set measurement unit the multiplier de...

Страница 40: ...t 1 0 0 10 V 1 0 5 V 10079 SW Value of the quantity associated with the analog output 1 corresponding to 0 4 mA and 0 V 10080 SW Value of the quantity associated with the analog output 1 corresponding...

Страница 41: ...antity 5 da 20060 a 20071 B User code with ASCII codification of the quantity 6 da 20072 a 20083 B User code with ASCII codification of the quantity 7 Measurement alarm hysteresis and delay time 30002...

Страница 42: ...5 2 mm barbed inputs Overpressure 24 9 kPa Type of fluid Air and neutral gases Temperature optional Sensor 4 wire Pt100 Measuring range 40 150 C Resolution 0 01 C Accuracy 1 3 DIN Stability 0 1 C yea...

Страница 43: ...configuration and viewing the real time measurements Protocols Proprietary Modbus RTU Modbus TCP IP SMTP FTP HTTP NIST Measuring interval 1 2 5 10 15 30 s 1 2 5 10 15 30 60 min Logging interval 1 2 5...

Страница 44: ...HD50CR 44 V1 0 Dimensions mm...

Страница 45: ...as the specific measures described in this operating manual The proper operation and the operational safety of the instrument can be ensured on ly under the climatic conditions specified in this manua...

Страница 46: ...sor operating temperature 40 150 C 8 pole M12 female connector Accessories HD35AP CFR21 Software option that adds to the features of the basic software both HD35AP S and HDServer1 the management of th...

Страница 47: ...HD50CR 47 V1 0 Approvals IEEE 802 11 Wi Fi certifications HD50CR contains IEEE 802 11b g n module FCC ID XM5 SMG2N2 IC ID 8516A SMG2N2 TELEC certified RF module R 204 520077...

Страница 48: ...rent from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Notice To satisfy FCC IC RF exposure requirements for mobile and base station transm...

Страница 49: ...HD50CR 49 V1 0 NOTES...

Страница 50: ...HD50CR 50 V1 0 NOTES...

Страница 51: ......

Страница 52: ...zed third parties is excluded from the guarantee The instrument shall be returned FREE OF SHIPMENT CHARGES to your dealer The jurisdiction of Padua applies in any dispute The electrical and electronic...

Страница 53: ...e result of the constant development of the product This may produce some differences between the information written in this manual and the instrument you have purchased We cannot completely exclude...

Страница 54: ...GHM GROUP Delta OHM Delta Ohm S r l a socio unico Via Marconi 5 35030 Caselle di Selvazzano Padova ITALY Phone 39 049 8977150 Fax 39 049 635596 www deltaohm com info deltaohm com V1 0 27 03 2020...

Отзывы: