Setting the alarm threshold temperature
Use the
or
button key to set the maximum floor-level
temperature above which the timed thermostat suspends heating
to prevent any possible damage (the value is expressed as tenths
of °C, and can be set from 150 to 1000 in steps of 100). This
parameter is only visible if the NTC temperature probe sensor
connected to the timed thermostat has been enabled as a
temperature probe (TEMP).
To confirm your choice and move on to the next parameter,
press the
button key within 30 seconds.
Setting the local relay
Use the
or
button key to set the operating mode of the
relay on the timed thermostat (OFF = disabled, HEAT =
management of heating valve, COOL = management of
cooling valve, BOTH = management of cooling
valves).
To confirm your choice and move on to the next parameter,
press the
button key within 30 seconds.
Enabling the supplementary parameter pages
Use the
or
button key to enable/disable the three sets
of functions that the device configuration parameters are
divided into (G = General parameters, GF = General +
Operating parameters, GFC = General + Operating +
Control parameters). To confirm your choice and move on
to the next parameter, press the
button key within 30
seconds.
If the local modification function has been enabled from the
“Enabling the supplementary parameter pages” menu for
the General Parameters group only (option G), press the
button key to return to the start of the parameter
configuration menu. Otherwise, continue with the
configuration of the next group of parameters.