Establishing switchpoints and proportional coefficient Xp
– continued –
Press button
twice briefly to return to the start
window.
Press button
once briefly.
Switchpoint 2 marks the upper limit of the proportional
band for the level controller NRR 2-40.
The difference between switchpoint
2
and switchpoint
3
gives the magnitude of the proportional range Xp.
The example setting corresponds to a proportional
band of (060 – 040) 20 %.
The proportional band
must
be greater than “0”!
Press button
once briefly.
Switchpoint 3 marks the lower limit of the
proportional band for the level controller NRR 2-40.
The proportional coefficient and the MIN switch-
point of the NRR 2-40 as well as the switchpoints
of the NRS 2-40 can be adjusted as described
above.
3 : 040
040
4 : 020
020
2
1 [%]
[%]
*
0%
:
100%: 100
2 :
060
060
1 : 070
080
P
NRR 2-40
NRS 2-40
1
2
4 : 020
020
2
1 [%]
[%]
*
0%
:
100%: 100
2 : 060
060
1 : 070
080
3 :
040
040
P
NRR 2-40
NRS 2-40
1
2
Commissioning
– continued –
once briefly
once briefly
twice briefly