53
Press button
once briefly to de-activate the
line editing mode.
All conductivity readings will now be indicated
in [ppm].
Press button
once briefly.
In this line you can calibrate the graphical
representation (bar chart) of the conductivity value
shown in the main window. This setting will also
standardize the actual value output (4-20mA).
First ascertain the conductivity measuring range
used in your installation (e. g.
0.5 µS/cm to
20 µS/cm
).
Press button
once briefly to select the unit
[ppm].
Press button
once briefly to activate the line
editing mode.
You can choose between the following ranges:
n
0.5 to 20 µS/cm
n
0.5 to 1000 µS/cm
n
0.5 to 100 µS/cm
n
0.5 to 2000 µS/cm
n
0.5 to 200 µS/cm
n
0.5 to 6000 µS/cm
n
0.5 to 500 µS/cm
n
0.5 to 12000 µS/cm
Adjusting conductivity controller
– continued –
MIN:
MAX:
w:
07000,0
05000,0
01000,0
0,5 - 12000
Range:
ppm
S/cm
S/cm
S/cm
S/cm
S/cm
P
MIN:
MAX:
w:
07000,0
05000,0
01000,0
0,5 - 12000
Range:
ppm
S/cm
S/cm
S/cm
S/cm
S/cm
P
E
MIN:
MAX:
w:
07000,0
05000,0
01000,0
0,5 - 12000
ppm
S/cm
S/cm
S/cm
S/cm
S/cm
P
Range:
P
MIN:
MAX:
w:
07000,0
05000,0
01000,0
0,5 - 12000
ppm
S/cm
S/cm
S/cm
S/cm
S/cm
P
Range:
flashing
flashing
Commissioning
– continued –
once briefly
once briefly
once briefly
once briefly
Содержание URB 1
Страница 1: ...1 E N English Operating Terminal Display Unit URB 1 Original Installation Instructions 810375 07 ...
Страница 9: ...9 045 3450 S cm S cm W W 8 Technical Data continued Dimensions Fig 2 6 3 95 95 ...
Страница 10: ...10 Design URB 1 Fig 3 9 8 7 8 ...
Страница 11: ...11 Functional Elements URB 1 Fig 4 1 6 5 4 3 2 ...
Страница 82: ...82 For your Notes ...
Страница 83: ...83 For your Notes ...