The thermal fuse of one of the level
electrodes has been triggered.
Make sure
that the level electrode has been
mounted as specified in the installation manual.
Check
whether external influences have caused
built-up of heat in the electrode casing.
The data communication in the CAN bus
line is disrupted.
Make sure
that the CAN bus line has been wired
according to the wiring diagram.
Make sure
that the CAN bus is not interrupted
due to conductor breakage.
Make sure
the controllers and electrodes feature
the correct node IDs.
System malfunctions
– continued –
Fault finding list for troubleshooting
045%
3450
S/cm
S/cm
W
W
NRR 2-40
°C
°C
flashing
flashing
The thermal fuse of the conductivity
electrode has been triggered.
Make sure
that the conductivity electrode has
been mounted as specified in the installation
manual.
Check
whether external influences have caused
built-up of heat in the electrode casing.
LRG 16-40
°C
S
The conductivity electrode is defective.
The temperature sensor of the conductivity
electrode is either short circuited or interrupted.
Replace conductivity electrode
LRG 1640/41.
LRG 16-40
°C
S
5 times briefly
5 times briefly
5 times briefly
Содержание URB 1
Страница 1: ...1 E N English Operating Terminal Display Unit URB 1 Original Installation Instructions 810375 07 ...
Страница 9: ...9 045 3450 S cm S cm W W 8 Technical Data continued Dimensions Fig 2 6 3 95 95 ...
Страница 10: ...10 Design URB 1 Fig 3 9 8 7 8 ...
Страница 11: ...11 Functional Elements URB 1 Fig 4 1 6 5 4 3 2 ...
Страница 82: ...82 For your Notes ...
Страница 83: ...83 For your Notes ...