72
Enabling automatic (AUTO) temperature compensation
Press button
twice briefly
to activate the line editing mode.
The split-screen start window shows which GESTRA
bus devices can be indicated:
n
High level limiter NRS 1-41
n
Low level limiter NRS 1-40
n
Level switch NRS 2-40
n
Level controller NRR 2-40
n
Conductivity controller LRR 1-40
Press button
4 times briefly.
The AUTO curves for temperature compensation are
suitable for boilers operating with variable pressure,
which means that the boiler does not have a fixed
working pressure/temperature (e. g. low load 10 bar,
full load 15 bar).
The procedure for recording an AUTO curve is
described on pages 69 to 71.
In our example we have started from the setting
“TK:NORM”.
OFF
Tk [Auto]
Temp.
C.
: 0181,7 °C
15
: 0,210
NORM
:
/ Start
Stop
AUTO
Tk:
Tk [Tab ]
: 01
LIN
P
P
OFF
Tk [Auto]
Temp.
C.
: 0181,7 °C
15
: 0,210
NORM
:
/ Start
Stop
AUTO
Tk:
Tk [Tab ]
: 01
LIN
P
flashing
Commissioning
– continued –
4 times briefly
twice briefly
Содержание URB 1
Страница 1: ...1 E N English Operating Terminal Display Unit URB 1 Original Installation Instructions 810375 07 ...
Страница 9: ...9 045 3450 S cm S cm W W 8 Technical Data continued Dimensions Fig 2 6 3 95 95 ...
Страница 10: ...10 Design URB 1 Fig 3 9 8 7 8 ...
Страница 11: ...11 Functional Elements URB 1 Fig 4 1 6 5 4 3 2 ...
Страница 82: ...82 For your Notes ...
Страница 83: ...83 For your Notes ...