20
Basic Settings
– continued –
Factory setting
The display unit features the following factory set default values:
n
Baud rate:
250 kb/s
n
Node ID:
060
Note: This node ID should only be changed if necessary, max. node ID: 123.
Establishing / changing node ID
If several identical systems are to communicate in a CAN bus network, allocate a different node ID for
each system (e. g. limiter, controller, etc). In most cases it is sufficient to commission the equipment
with the default factory settings.
The code switch
7
is on the back of the equipment.
Attention
n
We recommend that you commission the CAN bus devices with the default factory
setting.
n
Do
not
use a node ID for more than one piece of equipment in the CAN bus system.
Fig. 8
(Factory setting 250 kBit/s)
Code switch settings
S1
S2
S3
Baud rate
Cable length
OFF
ON
OFF
250 kBit/s
125 m
ON
ON
OFF
125 kBit/s
250 m
OFF
ON
ON
100 kBit/s
335 m
ON
ON
ON
50 kBit/s
500 m
OFF
ON
ON
20 kBit/s
1,000 m
ON
ON
ON
10 kBit/s
1,000 m