Abnormal
Description & Checkpoint
Solution
(14) All LED in
the front panel
light up.
CPU inserting error in 3A or 3R PCB
Insert the CPU into correct
socket.
(15)
Communication
interface is not
working
properly.
Communication cables are connected
improperly.
Correct the wiring.
Communication software is not installed
successfully.
Reinstall the software.
Communication port setup error.
Correct the setup.
CPU inserting error in 3R PCB.
Insert the CPU into right
socket.
If the abnormal cannot be corrected after
Refer to PCB LED
the solution actions have been taken.
Detecting Guide and check
the 3R PCB.