BATTERY MONITORING MODULE
-
DCMAN
TM
DCMAN
TM
is an intelligent module capable of monitoring each individual battery in a
UPS battery bank. The unit can identify batteries below specification limits, and cause
recharge or auto-repair procedures to be initiated, therefore prolonging battery life
expectancy. One module can monitor up to 64 ea.12V batteries. DCMAN will report
abnormal situations, such as total battery failure, abnormal cable connections, or
battery charge less than preset values.
(A) Module Outlook and Contents
MONITORING MASTER
DETECTING UNIT
1. MONITORING MASTER
There are three keys (UP
↑∕
DOWN
↓∕
ENTER
←┘
) and two LEDs on the front
panel of MORNITORING MASTER, as seen in the above photo. The green LED
lights for power ON. The red LED illuminates, and an audible alarm sounds, when
an abnormal situation occurs. Such anomalies include battery failure, abnormal
cable connections, or battery charge less than preset values.
To make the display more legible, the LCD is backlit by LEDs. To prolong the life of
the LED, power to the LEDs is cut off 15 seconds after the last key. Backlighting
will resume when any key is again pressed.
2. DETECTING UNIT
There are two LEDs on the front cover of the DETECTING UNIT, as seen in the
above photo. The green LED lights for power ON, and the red for battery failure or
abnormal battery connections.
1
Содержание T3UPS-33-700K
Страница 18: ...1 7 Dimension Drawings 10KVA 60KVA OUTLINE DRAWING 1 13 ...
Страница 19: ...10KVA 60KVA INTERIOR DRAWING 1 14 ...
Страница 20: ...75KVA 160KVA OUTLINE DRAWING 1 15 ...
Страница 21: ...75KVA 160KVA INTERIOR DRAWING 1 16 ...
Страница 22: ...175KVA 320KVA OUTLINE DRAWING 1 17 ...
Страница 23: ...175KVA 320KVA INTERIOR DRAWING 1 18 ...
Страница 24: ...INTER PCB DIAGRAM 1 19 ...
Страница 31: ...1 ...
Страница 35: ...3 3 ...
Страница 70: ...ONE TO TWO SERIAL REDUNDANCY 8 3 ...
Страница 77: ...Appendices Additional Data on Options UPSCOMTM UPSCALLTM DCMANTM ...
Страница 80: ...3 ...
Страница 81: ......