4-2
MIMIC DISPLAY UNDER NORMAL OPERATION
(d) Push inverter ON switch – To turn on the inverter, the inverter ON switch
and the control switch must be pressed simultaneously. The
inverter will start working and inverter output will be established
in 4 seconds. The load will automatically be transferred to the
inverter 3 seconds later. Now the UPS is in normal operation.
~
~
~
/
~ ~
~
/
~
(e) Check if the mimic LED is correct, as shown in the figure, above. All
warning LEDs on the right side are off, two LEDs: ‘INVERTER
ON’ and ‘INVERTER SS’ on the left side should be lit. If the load
is over 70%, the ‘70% LOAD’ LED will also be lit.
4.2. Shutdown Procedure
If you want to shutdown the UPS completely (no power at output or inside),
please follow the steps below. This procedure is for generally standard systems, 3
phases 4 wire “WYE” Input. For special inputs, please refer to the brief
instruction label in front of the PCB holder.
(a) Switch off the inverter – The inverter can be switched off by pressing the
inverter OFF switch and the control switch simultaneously. The
load will be automatically transferred to reserve without
interruption.
Содержание T3UPS-33-700K
Страница 18: ...1 7 Dimension Drawings 10KVA 60KVA OUTLINE DRAWING 1 13 ...
Страница 19: ...10KVA 60KVA INTERIOR DRAWING 1 14 ...
Страница 20: ...75KVA 160KVA OUTLINE DRAWING 1 15 ...
Страница 21: ...75KVA 160KVA INTERIOR DRAWING 1 16 ...
Страница 22: ...175KVA 320KVA OUTLINE DRAWING 1 17 ...
Страница 23: ...175KVA 320KVA INTERIOR DRAWING 1 18 ...
Страница 24: ...INTER PCB DIAGRAM 1 19 ...
Страница 31: ...1 ...
Страница 35: ...3 3 ...
Страница 70: ...ONE TO TWO SERIAL REDUNDANCY 8 3 ...
Страница 77: ...Appendices Additional Data on Options UPSCOMTM UPSCALLTM DCMANTM ...
Страница 80: ...3 ...
Страница 81: ......